ENVIRONMENTAL CONDITIONS
Ambient/storage temperature
Relative humidity
Pollution degree
Overvoltage category
Altitude
Protection
OUTPUT
INPUT
GENERAL
ERPA1-240-F
40
180 - 280
150
400
1,6
5
880
50 - 60
>0,75
160
0/4-20mA, 0/1-5V DC, 0/2-10V DC or 1kΩ ~ 10kΩ potentiometer. (Device may be damaged at 12V DC and above voltages).
≥0,2mA (for mA input), ≥0,08V (for V input).
≤0,18mA (for mA input), ≤0,075V (for V input).
15ms.
≤100Ω (for mA input), ≥10kΩ (for V input).
Protection feature for reverse connection is available.
ERPA1-xxx-F-xx
90-250V AC, 50/60Hz.
W46 x H110 x D117mm (for ERPA1-x40-F and ERPA1-550-F) , W79 x H120 x D132mm (for ERPA1-570-F).
Approx. 450g (for ERPA1-x40-F and ERPA1-550-F) , Approx. 550g (for ERPA1-570-F) (boxed).
2500 Vrms between I/O terminals for 1 min.
For power line 16mm² cable (with 25mm² cable terminal) cable, for signal line can be connected 4mm² cable.
Max. 1,2Nm.
EN 60947-4-3
Rail mountable (EN60715,TH35 or G-32).
Self extinguishing plastics (According to EN 60695-11-10 V-O).
Fan is controlled with thermostat and works at temperatures over 50°C.
ERPA1-440-F
40
180 - 480
110
290
1,8
8
610
50 - 60
>0,75
200
ERPA1-550-F
50
180
270
10
720
300
180 - 500
1,8
50 - 60
>0,75
3A, 250V AC, NO or NC can be selected by program.
ERPA1-570-F
70
400
600
15
4000
400
Order Code
Load Current, AC51/25ºC (Arms)
Load Voltage (Vrms)
Overload Current t=1s/25°C (Arms)
Non rep. Surge current/25°C (Arms)
On-state Voltage Drop (Vrms)
Leakage Current (mArms)
I²t for Fusing t=10ms (A²s)
Frequency (Hz)
Power Factor (CosΦ)
Minimum Operating Current (mArms)
Alarm Output
Input Signal
Transmission Signal
Drop-out Signal
Turn-on Time
Dynamic Input Impedance
Protection
Order code
Power supply
Dimensions
Weight
Isolation Voltage
Connection
Terminal screw torque
Product standard
Mounting
Enclosure material
Fa n (Optional)
ORDER CODE
Thank you for choosing ENDA ERPA1 Series power regulators.
ERP A 1 - 5 50 - F - V - RS
ENDA ERPA1 Series Power Regulators
Product Basic Code
Rail Mounted ERP
Fan (*)
Fan F
Communication (*)
RS485 ModBus RS
Blank (N/A)
Load Voltage
AC A
Number of Pole
Single pole 1
Load Current
40A AC 40
50A AC 50
70A AC 70
Load Voltage
180 - 280V AC 2
180 - 480V AC 4
180 - 500V AC 5
Please rea this document carefully before using this product. The guarantee will be invalidated if the device is damaged by
not following instructions detailed in the manual. The company shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
ERPA1-xxx-EN-06-210303
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Şerifali Mah. Y.Dudullu 34775
ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
Barbaros Cad. No:18
1/4
ENDA
TM
40 -50 -70A AC Load current.
280 -480 -500V AC Load voltage.
0/4-20mA, 0/1-5V DC, 0/2-10V DC or 1kΩ ~ 10kΩ Potentiometer input.
4 Digits LED display.
Phase angel or zero-cross controlled.
Soft Start or Kick Start feature.
Overheat alarm output.
Varistor protection for peak voltages.
Vibration coil control (Optional).
RS485 ModBus Communication feature (Optional).
CE Marked according to European Norms.
A A
V V
Optional features must be specified at order.
90% Relative humidity for temperatures up to 20 % °C, decreasing linearly to 50% at 40°C. (Shouldn't be condensation).
-25... +60 °C / -30... +100 °C (Shouldn't be icing and condensation in ambient.)
2
II
Max. 1000m.
IP20 According to EN60529
Vibration Control (*)
Vibration Control V
Blank (N/A)
KEEP AWAY device from exposed to corrosive, volatile and flammable gases or liquids and DO NOT USE the device in similar hazardous locations.
Avoid any liquid contact while the device is switched on. DO NOT clean the device with solvent (thinner, gasoline, acid etc.) and / or abrasive cleaning agents.
*
*
*
*
*
*
*
*
*
*
*
( )
*
While assembling,
there must be at least
25mm clearance
between the devices.
Potentiometer
Removing the device from rail ;
By using a screwdriver, lock the tab of
the mounting bracket by pulling it
upwards in direction 1 and pull the
device from the rail.
Mounting the device to the rail :
By using a screwdriver, lock the tab of
the mounting bracket by pulling it
upwards in direction 1 .
Place the device on the rail and push
the tab in direction 2 (sideways) to
hold the device on the rail.
ERPA1-240-F , ERPA1-440-F , ERPA1-550-F
2
1
ERPA1-440-F-RS
1kΩ to 10kΩ
ERPA1-240-F
DIMENSIONS
Supply
Voltage
90-250VAC
7VA
1kΩ to 10kΩ
Potentiometer
ERPA1-570-F
ENDA
ERPA1
POWER
REGULATOR
SET
ENDA
ERPA1
POWER
REGULATOR
SET
SUPPLY
90-250VAC
50/60Hz
7VA
LOAD
40A
N L
180-280VAC
MADE IN TURKEY SN : 140335044
ENDA
INDUSTRIAL ELECTRONICS
ERPA1-240-F
POWER REGULATOR
ENDA
ERPA1
POWER
REGULATOR
SET
ALARM
OUT
1kΩ to 10kO
0-10V
0/4-20mA
+
8680407713981
_
~
SUPPLY
90-250VAC
50/60Hz
7VA
LOAD
40A
N L
180-280VAC
MADE IN TURKEYSN : 140335044
ENDA
INDUSTRIAL ELECTRONICS
ERPA1-240-F
POWER REGULATOR
ENDA
ERPA1
POWER
REGULATOR
SET
ALARM
OUT
1kΩ to 10kO
0-10V
0/4-20mA
+
8680407713981
_
~
25 mm
INSTALLATION
APPLICATION
111mm 46mm
9mm
100mm 16mm
1 2
345
10 9
8
76
WARNING
Heatsink at
high temperature
ENDA
ERPA1
POWER
REGULATOR
SET
126mm 72mm
79mm
9mm
58mm
21mm
100mm 26mm
5mm
WARNING
Heatsink at
high temperature
46mm
1 2
345
10 9
8
76
ENDA
ERPA1
POWER
REGULATOR
SET
5mm
Alarm
Out
0/4-20mA
or
0-10V
- +
ENDA
ERPA1
POWER
REGULATOR
SET
SUPPLY
90-250VAC
50/60Hz
7VA
MADE IN TURKEY SN : 140335044
ENDA
INDUSTRIAL ELECTRONICS
ERPA1-240-F
POWER REGULATOR
ENDA
ERPA1
POWER
REGULATOR
SET
ALARM
OUT
1kΩ to 10kO
0-10V
0/4-20mA
+
8 68040 7 71398 1
_
~
LOAD
40A
180-280VAC
N
L
1 2
345
10 9
8
76
Fuse
L N
Load
180-280VAC
Alarm
Out
0/4-20mA
or
0-10V
- +
A
B
COM
{
Rs485
ModBus
ENDA
ERPA1
POWER
REGULATOR
SET
A
B
COM
Rs485
ModBus
ENDA
ERPA1
POWER
REGULATOR
LOAD
40A
180-480VAC
MADE IN TURKEY SN : 140335045
ENDA
INDUSTRIAL ELECTRONICS
ERPA1-440-F-RS
POWER REGULATOR
ALARM
OUT
8 68040 7 71406 3
A
B
COM
Rs485
ModBus
A
B
COM
Rs485
ModBus
SUPPLY
90-250VAC
50/60Hz
7VA
SET
1kΩ to 10kO
0-10V
0/4-20mA
+
_
~
L1
L2
1 2
345
10 9
8
76
Fuse
L N
Load
180-280VAC
Supply
Voltage
90-250VAC
7VA
ERPA1-xxx-EN-06-210303
2/4
SET SET
SET
Running
Mode
a. 3.0
o. 30
diSp. = curr.
Output as
Current.
diSp. = out
Output as
Percentage.
SET
Communication Mode
In "Running Mode", by held down to and then pressed to key, "Programming Mode" is entered. If no key is pressed during in "Programming Mode" for 20 seconds,
adjusted parameter(s) (if any) is stored and returned to the "Running Mode".
Or ; if pressed and than keys, access to menu headers are entered. By pressing and than keys are pressed together, information is saved and returns to
Run Mode.
SET
++
If key is pressed in “Running Mode” for 3 seconds, “manual Running Mode” is entered. Manual output value flashes and
desired value can be selected by using navigation keys. By pressing the key, value is set and “Running Mode” is
entered.
SET
SET
SET
SET
Manual Running Mode
m. 50 m. 51 m. 50
*
SET
t0 r t 0r
Device starts in
“Running Mode"
every power-up.
PARAMETER TABLE
inp.
4 20
Parameter Options
/ [units] Description
0 20
conf. Configuration menu
0 10
1 5
2 10
0 5
pot.
manu.
4-20mA
0-20mA
0-10V
1-5V
2-10V
0-5V
Potentiometer input.
Manual Run Mode.
disp. out
curr.
Output as Percentage in Run Mode.
Output as Current in Run Mode.
c.typ. phaS.
croS.
Control with phase angle.
Control with Zero-cross.
St.ti.
Soft
ic.St.
Output is energized with soft start.
Output is energized with kick start.
al.ou. no.
nc.
Alarm relay normally open.
Alarm relay normally closed.
Err.c. auto
Stop
Returns to Run Mode when error disappeares.
Remains in Eror Mode when error disappeares.
out.c. Output Control Menu
ou.hi. Takes a value between ou.lo. and100.
ou.lo. Takes a value between 0 . and ou.hi.
cu.hi. Takes a value between 0 and load current.
Start duration (0 - 200).
ou.of. Takes a value between -50. and 50.
[Ampere]
[Second]
[%]
[%]
[%]
conn. Communication Menu (*)
d.adr. Takes a value between 1. and 247 .
baud 1200, 2400, 4800, 9600 and 19200 values are selectable.
5ECU Security Menu
a.con. Configuration menu invisible.
Configuration menu can be changed.
Only configuration menu visible.
a.out. Output control menu invisible.
Output control menu can be changed.
Only Output control menu visible.
Communication menu invisible.
Communication can be changed.
Only communication menu visible.
(*) This menu is only available on ModBus featured devices.
(**) Takes 40, 50 or 70 values for according to device models.
Input selection.
Programming Mode
inp.
Control type
selection.
c.typ.
Start type
selection.
st.ty.
Display selection
in “Running Mode”
disp.
st.ti.
Alarm relay
selection.
Data menu security
parameter.
A.out..
Communication menu
security parameter.
A.cnn.
A.con. Control menu security
parameter.
codE. Security menu access
code is 124.
baud
d.adr.
Max. acceptable
value for output.
Min. acceptable
value for output.
ou.hi.
ou.lo. Modbus speed.
Modbus address.
Start duration.
ou.of.
If Err.c parameter is set as stop , only when key is pressed, auto , when
key is pressed or when the error disappeared, it returns to Running Mode. When return to the operating mode,
if overheating continues device passes to the error Mode.
If Err.c parameter is set as
Output offset value.
Err.c. Quit method
from error status.
conf.
al.ou.
out.c. conn.
SET
SET
sECU. St.ty.
nonE
p.yES
p.no
nonE
p.yES
p.no
a.cnn. nonE
p.yES
p.no
Default
values
out
phaS.
Soft
4
no.
auto
p.yES
p.yES
p.yES
100
0
If key is held down while the device is powered up, d.PAr message will appears on display and factory
settings will be restored.
0
1
9600
If held down key, the selected parameter will flash and can be adjusted to desired value with the keys.
Parameter Adjustment Method
ou.hi 51 50
50
If keys are pressed for 0.4 seconds then the parameter is changed faster.
SET
SET
SET SET SET SET
cu.hi.
+ + + +
(**)
0 10
(If disP. = curr. )
Max. current value for
connected load
in curr. selection ERPA does not measures the load current. It indicates
the calculated current value for according to the entered
cu.hi. parameter.
Psc
Err.1
When the device overheats, Err.1 appears on display and enters to error mode and alarm relay triggers.
Error Messages
Psc
Err.2
If input values are selected as 4-20 or 0-20 and if above current flows, Err.2 appears on display and enters
to error mode and alarm relay triggers.
Psc
Err.3
*
If input value is selected as and if master device not response for 15 seconds, Err.3 appears on display
and enters to error mode and alarm relay triggers.
m.bus
m.bus. Modbus input
m.sft. Output is energized with soft start according to manual output value.
m.ic.S. Output is energized with kick start according to manual output value.
If key is pressed in “Running Mode” for 3 seconds, “Communication Mode” is entered. By pressing the key, “Running
Mode” is entered. " 0 " sign, point the communication status. During data received from Modbus, " 0 " blinks at the left side of "
ModBus Connection Diagram
120 Ohm
120 Ohm
Master Slave - 1 Up to 127 Slave devices
can be controlled.
Slave - 2 Slave
127
-
+
A
B
-
+
A
B
-
+
A
B
120 Ohm Terminating resistors should be added.
-
+
A
B
3/4 ERPA1-xxx-EN-06-210303
Factory Settings
Holding Register
addresses
Decimal (Hex)
Data
type Data content Parameter
Name
Read / Write
permission
inp.
disp.
st.ti.
ou.hi.
ou.lo.
cu.hi.
ou.of.
A.con.
A.out.
A.cnn.
d.adr.
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
Input selection (0: 4-20mA, 1: 0-20mA, 2: 0-10V, 3: 1-5V, 4: 2-10V,
5: 0-5V, 6: potentiometer, 7: manual, 8: Modbus).
Display selection on Running Mode (0: output as percent,
1: output as current, 2: set manually in percent output).
Kick-Soft start duration (adjustable between 0 and 200 seconds).
Max. acceptable value for output. (Acceptable between ou.lo. and 100).
Modbus device address (adjustable between 0 and 247).
Max. output current. (Acceptable value between 0 and load current).
Output offset value. (Adjustable between -50 and 50).
Security parameter for configuration menu (0: Menu invisible,
1: Menu programmable 2: Only configuration menu visible).
Output parameter for configuration menu (0:Menu invisible,
1: Menu programmable 2: Only configuration menu visible).
Communication parameter for configuration menu (0: Menu invisible,
1: Menu programmable 2: Only configuration menu visible).
Modbus input (adjustable between ou.lo. and ou.hi. ).
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
0012d (000Ch)
0011d (000Bh)
0010d (000Ah)
0009d (0009h)
0008d (0008h)
0007d (0007h)
0006d (0006h)
0005d (0005h)
0004d (0004h)
0003d (0003h)
0002d (0002h)
0001d (0001h)
0000d (0000h)
1.1 Memory Map for Holding Registers
1.2 Memory Map for Coils
Coil addresses
Input register address
Data
Type Data content Parameter
Name
c.typ.
a.lou.
--
Err.c.
R / W
Only Readable
R / W
R / W
Control selection type (0: Phase angel, 1: Zero-cross)
Min. acceptable value for output. (acceptable between 0 and ou.hi. ).
Output value as percent
Alarm relay selection (0: NO, 1: NC)
Alarm control management (0: Returns to Run Mode when error
disappeares., 1: Remains in Eror Mode when error disappeares.)
Bit
Byte
Bit
Bit
(0000)h
(0000)h
(0001)h
(0002)h
1.3 Memory Map for Input Registers
--
Byte
ENDA ERPA1 MODBUS PROTOCOL ADDRESS MAP
Read / Write
permission
Data content Parameter
Name
Read / Write
permission
Only Readable
Current value as percent
Output rate %20 Output rate %20
Output rate %50 Output rate %50
Output rate %80 Output rate %80
It is a proportional control method used in inductive and variable resistive loads
(cosØ <1). The disadvantage of this method is that it causes high electrical noise.
It is a control method used in capacitive and variable resistive loads (cosØ =1).
The advantage of this method is that it does not causes high electrical noise.
With Phase Angle Control With Zero-Crossing Control
Start Method
t : Start time ( St.ti. )
Output
Ratio
Max. 100 Max. 100
0 0
t tSecond
Soft Start Kick Start
Output Ratio : Manually set or changed
by the input signal is
output as a percentage.
Out
%
Control Method
Out
%
Output
Ratio
Second
Output Ratio : Manually set or changed
by the input signal is
output as a percentage.
t : Start time ( St.ti. )
baud R / W
Modbus baud rate (0: 1200, 1: 2400, 2: 4800, 3: 9600, 4: 19200)
Byte
0013d (000Dh)
st.ty. R / W
Start type selection. ( 0 : Soft Start according to input signal. 1 : Kick Start according to
input signal. 2 : Soft Start according to manual output. 3 : Kick Start according to manual output ).
Note : Modbus default Parity and Data Bits settings can not be changed. (Parity : None. Data Bits : 8)
Data
Type
ERPA1-xxx-EN-06-210303
SİSEL MÜHENDİSLİK ELEKTRONİK SAN. VE TİC. A.Ş.
Şerifali Mah. Y.Dudullu 34775
ÜMRANİYE/İSTANBUL-TURKEY
Tel : +90 216 499 46 64 Pbx. Fax : +90 216 365 74 01
url : www.enda.com.tr
Barbaros Cad. No:18
4/4
ENDA
TM

This manual suits for next models

4

Other sisel Controllers manuals

sisel ENDA ET1413R User manual

sisel

sisel ENDA ET1413R User manual

sisel ENDA ERFA1 Series User manual

sisel

sisel ENDA ERFA1 Series User manual

sisel ENDA ERFA1-NTC-240 Series User manual

sisel

sisel ENDA ERFA1-NTC-240 Series User manual

sisel ENDA ET4430 User manual

sisel

sisel ENDA ET4430 User manual

sisel ENDA EUP Series User manual

sisel

sisel ENDA EUP Series User manual

Popular Controllers manuals by other brands

Galil Motion Control DMC-1600 Series user manual

Galil Motion Control

Galil Motion Control DMC-1600 Series user manual

Axxess AX200 Installation & user guide

Axxess

Axxess AX200 Installation & user guide

Sices GC250 Technical manual

Sices

Sices GC250 Technical manual

HPE Aruba 650-US Product End-of-Life Disassembly Instructions

HPE

HPE Aruba 650-US Product End-of-Life Disassembly Instructions

Switchmate Home SimplySmartHome Secure Quick start guides

Switchmate Home

Switchmate Home SimplySmartHome Secure Quick start guides

Weil-McLain ProtoNode FPC-N34 quick guide setup

Weil-McLain

Weil-McLain ProtoNode FPC-N34 quick guide setup

Johnson Controls York 366-70488 Installation and Maintenance

Johnson Controls

Johnson Controls York 366-70488 Installation and Maintenance

Toshiba TS3000 Series instruction manual

Toshiba

Toshiba TS3000 Series instruction manual

ABB MotiFlex e180 Application guide

ABB

ABB MotiFlex e180 Application guide

Grundfos PM 1 Installation and operating instructions

Grundfos

Grundfos PM 1 Installation and operating instructions

Vexve AM40 Instructions & user's manual

Vexve

Vexve AM40 Instructions & user's manual

SPL 2489 user manual

SPL

SPL 2489 user manual

Siemens GAMMA wave GE 561/01 Technical product information

Siemens

Siemens GAMMA wave GE 561/01 Technical product information

NOVAK HAVOC PRO SC - TRACK GUIDE manual

NOVAK

NOVAK HAVOC PRO SC - TRACK GUIDE manual

ICP DAS USA CAN-8123 user manual

ICP DAS USA

ICP DAS USA CAN-8123 user manual

Verkada AC41 installation manual

Verkada

Verkada AC41 installation manual

Rinnai BRIVIS Touch installation manual

Rinnai

Rinnai BRIVIS Touch installation manual

Kontron CP347 user guide

Kontron

Kontron CP347 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.