SecureAire PlatinumPLUS Operating manual

www.secureaire.com | Proudly made in the U.S.A. | MN900-500-Rev E
User and
Installation Manual
Congratulations on selecting SecureAire’s most advanced
Air Purication System! SecureAire’s patented design utilizes
ACTIVE Particle Control technology, proven to capture and
remove airborne contaminants from your home while
INACTIVATING™ (killing) viable airborne pathogens including
bacteria, viruses, and mold.
Air
Purication
for a Safe,
Healthy,
and Clean
Environment™
PlatinumPLUS
Air Purication System

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E2
Preface
About your new SecureAire PlatinumPLUS
Air Purication System
The PlatinumPLUS Air Purication System easily mounts into the return air ductwork of any gas, oil, or
electric forced air furnace or central air conditioning system with design airow up to 2000 cfm.
ACTIVE Particle Control™ – How It Works
The SecureAire PlatinumPLUS Air Purication System is based upon ACTIVE Particle Control™ technology
that is continuously working to remove airborne contaminants in the living space, including particulates,
pathogens, and VOCs.
Legal Notices
The information contained in this document is
subject to change without notice.
This document contains proprietary information that
is protected by copyright. All rights are reserved. No
part of this document may be photocopied, reproduced,
or translated to another language without the prior
written consent of SecureAire Incorporated.
SecureAire Technologies, LLC
1968 Bayshore Blvd, Dunedin, Florida 34698
www.secureaire.com, Phone: 813-300-6077
Technical Support
Please contact us at 813-300-6077 with any
questions.
Printing History
This manual was rst printed in October 2021. The
edition number will change when a new edition is
printed. Minor changes may be made at reprint
without changing the edition number. The part
number will change when extensive changes
are made.
Airfl
o
w
4
1
Conditioned
Particles
Conditioning Zone
Transport of “Net Neutrals” into the occupied space
2
Colliding
Particles
Coagulated
Particles
(”Net Neutrals”)
Colliding & Coagulating Zone
3
Captured + Killed
Particles
Capture / Kill Zone

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E 3
Before installation
When Installing This Product:
1. This document provides instructions for the installation and electrical wiring of SecureAire’s
PlatinumPLUS Air Purication System.
2. Read these instructions carefully as failure to comply can damage the product or cause a hazardous
condition.
3. Review the specications provided to ensure that it is suitable for your application.
4. The installer must be a trained, experienced mechanical and electrical technician.
5. After the installation is complete, please complete the system start-up procedures to ensure correct
installation and operation of the product.
What’s Inside the Box:
• SecureAire Platinum Air Purier
• 8-foot electrical plug-in cord
Installation Tools Needed:
• Phillips screwdriver • Custom sheet metal ttings
• Wire cutter • Sheet metal cutting tools
• Wire stripper • Locking pliers or clamps
• Wire crimper • Sheet metal screws
• Drill • Silicone sealant
SecureAire Product Model Numbers and Airow Rating:
Model Numbers Maximum Airow (cfm)
ACS1620-NG2 1200
ACS2020-NG2 1400
ACS1625-NG2 1400
ACS2025-NG2 2000
Replacement Air Purication Cartridge Part Numbers:
ROC1620-NG2 Platinum Series Cartridge Part Number
16x20x2 ROC1620-NG2
20x20x2 ROC2020-NG2
16x25x2 ROC1625-NG2
20x25x2 ROC2025-NG2

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E4
Before installation (continued)
Application Considerations:
The SecureAire Air Purier is designed to work with gas, oil, and electric forced air furnaces and central air
conditioning systems.
Airow considerations are vital to the heating and cooling system’s performance, longevity, and safety, as
well as the performance of the SecureAire Air Purier. Industry standards are established to ensure
proper design and installation of this product and the associated ductwork.
Choosing a Mounting Position:
The SecureAire Air Purier mounts in any position within the return air duct, usually next to the furnace
blower compartment. There are directional arrows on the lter to conrm proper cabinet location. See
below for proper locations for the SecureAire Air Purier in a variety of furnace and air handler installations.
Type Description
1Upow with side install. The SecureAire Air Purier
is mounted vertically where return enters side inlet
of furnace.
2Upow with install beneath furnace. The SecureAire
Air Purier is mounted horizontally where return
enters from below.
3Upow with closet install. The SecureAire Air Purier
is mounted vertically on furnace between furnace
and louvered return air opening in closet door.
4Counterow with the SecureAire Air Purier is
mounted horizontally in return plenum just above
furnace and opposite heating plenum.
Type Description
5Counterow furnace with the SecureAire Air Purier
mounted horizontally in return duct or plenum just
above furnace.
6Central fan installation, with the SecureAire Air
Purier mounted horizontally in central return duct.
7Horizontal furnace, with the SecureAire Air Purier
mounted vertically in return duct near furnace.
8Two or more SecureAire Air Puriers used in a
high-capacity system.

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E 5
Installing the SecureAire Air Purier: Upow Furnace Example
The following procedure describes a typical installation on an existing upow furnace with a side return.
(Figure 1-1). Other changes in installation procedures may be necessary to complete your installation.
NOTE: Prior to beginning your installation, remove and discard the existing furnace lter (if used).
Thoroughly clean the blower compartment. EPA recommends a professional duct cleaning whenever the
system’s normal airow will stir up and circulate dust or debris into the treated indoor environment.
https://www.epa.gov/indoor-air-quality-iaq/should-you-have-air-ducts-your-home-cleaned.
WARNING
Electric Shock Hazard!
Can cause personal injury!
Do not, under any circumstances, use an electrical extension cord
other than the 8-foot cord provided with the unit.
Before installing or servicing this system, always make sure that the
main power to the system is turned o. There may be more than one
electrical disconnect switch.
The Step-by-Step Installation Process
Step 1: Review the installation plan and airow direction
Temporarily place the SecureAire Air Purier on the oor, orienting as it will be when installed.
Temporarily insert and remove the SecureAire Air Purier to make sure there is adequate clearance
for easy removal if that is ever necessary.
If the installation of the unit requires the airow direction to be reversed, this is easily
accomplished by removing the main assembly (Step 6) and rotating it into the proper
ow direction.

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E6
Installing the SecureAire Air Purier: Upow Furnace Example
Step 2: Remove the PlatinumPLUS Assembly
A. Unlatch the front door.
B. Remove the main assembly.

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E 7
Installing the SecureAire Air Purier: Upow Furnace Example
Step 3: Pre-wire the power supply
(PRE-WIRE ONLY. DO NOT CONNECT TO POWER.)
Installation of the SecureAire Air Purier should be performed by a licensed electrician or a certied HVAC
technician. Electrical wiring must comply with applicable local codes and standards.
These are pre-wire instructions only. Power is not connected to the unit at this point.
Wire ring lugs must be used when connecting input line voltage to the terminal block. These are
supplied on the plug-in power cord supplied with the SecureAire unit.
If connecting directly from another source, the technician must install wire ring lugs on the power
wires that connect to the SecureAire terminal block.
The supply line voltage power source is 120V/60 Hz.
A. Remove the 2 (two) Phillips head lock screws from the cabinet’s top access panel.
B. If the existing wiring connection out of the
back of the power supply will be obstructed
when the unit is installed, additional
knockouts are provided on both sides of the power
supply. Remove the existing wiring strain relief and
relocate it if needed.

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E8
Installing the SecureAire Air Purier: Upow Furnace Example
E. Tighten the wiring strain relief on the outside of the power supply box.
F. Re-install the access panel with the 2 (two) lock screws.
Step 4: Connect the cabinet to the furnace or air handler
A. If needed, cut an opening in the equipment cabinet to match the SecureAire Air Purier’s cabinet or
provide a proper sheet metal transition from the cabinet to the equipment.
B. If necessary, place blocks under the SecureAire Air Purier to make sure the unit sits securely.
C. Connect the SecureAire Air Purier securely to the furnace. Fasten with sheet metal screws or use S-cleat
type slip joints. If you are drilling holes, use locking pliers to help hold the cabinet in place during drilling.
Step 5: Connect the cabinet to the return air plenum
A. If needed, install turning vanes to help distribute air equally over the full surface of the upstream side
of the SecureAire Air Purier.
B. Connect the SecureAire Air Purier securely to the return air ductwork. Fasten with sheet metal screws
or use S-cleat type slip joints. If you are drilling holes, use locking pliers to help hold the cabinet in place
during drilling.
C. Inspect the SecureAire Air Purier to make sure that no metal lings are lodged in the unit and the
cabinet is free of any debris.
C. Connect unpowered wire ring lugs as shown. D. When using the supplied plug-in cord, match the
cord wiring color to the same color wires on the
wiring terminal block.

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E 9
Installing the SecureAire Air Purier: Upow Furnace Example
Step 7: Seal all sheet metal joints
Seal all joints in the sheet metal connections you made to prevent ambient air from entering or leaving
the ductwork. May use silicone sealant, mastic, or UL-approved sealant tape.
Step 8: Connect power to the power supply
Installation of the SecureAire Air Purier should be performed by a licensed electrician or a certied HVAC
technician. Electrical wiring must comply with applicable local codes and standards.
Wire ring lugs must be used when connecting input line voltage to the terminal block.
The supply-line voltage power source is 120V/60 Hz. When using the supplied plug-in power
cord, plug the cord into an accessible outlet. When connecting power through another source,
such as the equipment manufacturer’s provided EAC terminals, follow the equipment
manufacturer’s directions on how to make that connection.
Step 6: Reinstall the PlatinumPLUS Assembly
Reinstall the cartridge assembly making sure that the airow arrows are pointing in the desired
airow direction.
SecureAire Wiring Terminal Block
Line Voltage: 120V/60 Hz

10
Installing the SecureAire Air Purier: Upow Furnace Example
Note: The SecureAire Air Purier may be wired to be on continuously, even without the system
fan being on, as there are no harmful byproducts, such as ozone, produced by this device.
Step 9: System Operation Check
A. With the door closed, turn on the SecureAire Air Purier with the ON/OFF switch. The switch will glow
with a green light indicating that the power supply is on and operating properly.
B. Turn o the SecureAire Air Purier and the ON/OFF switch light turns o, indicating the entire
SecureAire power supply is powered o. The SecureAire Air Purier is now safe to access.
Built-in User Safety — Opening the front door before turning o the SecureAire Air Purier will disable
the high voltage circuit and de-energize the entire device.
Congratulations!
The SecureAire Air Purier installation is complete.

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E 11
Post-Installation Checklist
Please check the installation for the following:
System Airow is in the direction of the arrows on the SecureAire .
Turning vanes and transitions, if used, are properly installed.
Joints in all sheet metal connections are sealed.
All sheet metal connections are complete.
Original furnace lter has been removed and blower compartment is cleaned.
Replace any equipment access doors removed during the installation.
Run the furnace or cooling system through one complete cycle to ensure system
is operating.
Consider asking the homeowner if they would like to program the thermostat’s
fan control for intermittent, circulate, or constant fan control.

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E12
Replacing the Filter Cartridge
Step 3: Carefully remove the PlatinumPLUS assembly to access
the replacement cartridge.
Once the assembly is removed, the air purication replacement cartridge is accessed by separating the assembly
at the male and female tabs. Once separated, gently pull out the used air purication cartridge without disturbing
the accumulated dirt on the cartridge and place the cartridge in a large plastic bag for disposal.
The SecureAire Whole Home Air Purication System is designed to require minimal
maintenance. System maintenance is limited to the replacement of the system’s air
purication cartridge, which is easily accomplished using the following steps.
Step 1: Turn o the system power button.
Step 2: Unlatch and remove the front door.

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E 13
Replacing the Filter Cartridge (continued)
Step 4: Insert the new replacement air purication cartridge.
Once the replacement air purication cartridge has been installed, simply snap the assembly back together.
With the assembly back together, re-insert it into the SecureAire cabinet with the airow arrows on the
lter pointing in the direction of the airow.
Step 5: Reinserting the
PlatinumPLUS Assembly
Step 6: Re-attaching the front door
and turning on the power switch.
The SecureAire Air Purier cartridge
replacement is now complete!

www.secureaire.com | Proudly made in the U.S.A. | PlatinumPLUS Installation Guide | June 2022 | Part Number MN900-500-Rev E14
Specications, Dimensions, and Approvals
SecureAire Specications
System Specication ACS1620-NG2 ACS2020-NG2 ACS1625-NG2 ACS2025-NG2
Color Alpine White
Cabinet Material Aluminum/Galvanized Steel
Electrical 120/240 VAC at 60 Hz, Single Phase, 0.5A max
Operating Temperature Range -40 to 165 F (-40 to 74 C)
Operating Humidity Range 0 to 95% RH (non-condensing)
Maximum Airow (CFM) 1200 1400 1400 2000
Unit Weight (lbs.) 14 15 15 17
Initial Pressure Drop (in WC.) (0.11) (0.10) (0.10) (0.10)
SecureAire Air Purier Dimensions
Part Numbers Height Width Depth
ACS1620-NG2 16” 20” 6.75”
ACS2020-NG2 20” 20” 6.75”
ACS1625-NG2 16” 25” 6.75”
ACS2025-NG2 20” 25” 6.75”
SecureAire Cartridge Dimensions – Nominal
Part Number Height Width Depth
ROC1620-NG2 16” 20” 2”
ROC2020-NG2 20” 20” 2”
ROC1625-NG2 16” 25” 2”
ROC2025-NG2 20” 25” 2”
Model Width Height Depth
ACS1620-NG2 20” 16” 6.75”
ACS1625-NG2 25” 16” 6.75”
Model Width Height Depth
ACS2020-NG2 20” 20” 6.75”
ACS2025-NG2 25” 20” 6.75”
Dimensional drawings of the SecureAire Whole Home Residential System
1 ½
1 ¼
1¼
18 ¼
6 ¾
16
17
17
20
3 ¼
5 ¼5¼
13 ¼
6 5/86 5/8
16x20
2.06
5
/
8
6
5
/
8
17 ¼
22 ¼
6 ¾
20
21 ¾
8 ¼8¼
22
25
4 ¼
1 ½
1 ¼
20x25
5 ¼5¼
13 ¼
18 ¼
6 ¾
16
17 ¾
8 ¼
8 ¼
22
25
4 ¼
1 ½
1 ¼
1¼
16x25
6 5/86 5/8
17 1
/4
22 ¼
6 ¾
20
21 ¾
6 5/86 5/8
17
20
3 ¼
17
/8
1 ¼
1 ½
20x20

15
SecureAire Technologies, LLC
1968 Bayshore Boulevard, Dunedin, FL 34698
813.300.6077 | www.secureaire.com
© 2022 SecureAire Technologies, LLC. All rights reserved. Made in USA. 7.22
Specications, Dimensions, and Approvals
Platinum Series Pressure Drop Curves
Standards and Approvals
The SecureAire PlatinumPLUS Air Purication System has been tested and veried
to meet or exceed the following:
• UL 867 Electrical Standard
• CSA C22.2 No. 187-09 Electrical Standard
• ASHRAE 52.2 Filter Eciency Rating Standard. (Current version)
Revision Table
Rev Description ECO# Date Approval
E Fifth Release 6/22/2022 JC
Safe, Healthy, and Clean Indoor Air!
To Learn More
Visit our website at: www.secureaire.com/residential
0.25
0.2
0.15
0.1
0.05
0
200 400 600 800 1000 1200 1400 1600 1800 2000
Pressure Drop (in wg)
Airflow (CFM)
Air purification
cartridge size
key:
16 x20
20x20/
16 x25
25x20