manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Secutron
  6. •
  7. Fire Alarm
  8. •
  9. Secutron MRM-800MP Series User manual

Secutron MRM-800MP Series User manual

www.secutron.com LT-6168SEC Rev. 0 Feb. 2023
MRM-800MP(U) Series
Fire Alarm Manual Station
1
Secutron’s MRM-800MP(U) Series Fire Alarm Manual Stations
provide manual fire alarm activation.
This guide covers these models:
MRM-810MP Single Stage, Dual Action, MP Addressable Manual
Station
MRM-810MPU Single Stage, Dual Action, MP Addressable
Manual Station (US)
MRM-802MP Two Stage, Dual Action, MP Addressable Manual
Station
MRM-822MP Two Stage, Dual Action, MP Addressable Manual
Station with additional door contacts
Specifications & Dimensions
Compatible with MR-400 series and MMX™-4000 Fire Alarm
Control Panels
Electrical Rating:
Nominal Operating Voltage: 15-30 VDC
Maximum alarm current: 3.3 mA
Standby current: 2 mA
Electrical Rating for MRM-822MP maglock terminal:
1A at 30VDC
Dimensions:
139 mm H x 104 mm W x 34 mm D
(5 1/2” H x 4 1/8” W x 1 3/8” D)
Install the manual station
Contents of kit
MRM-810MP, MRM-810MPU: 2 mounting screws, 2 reset keys
(black)
MRM-802MP, MRM-822MP: 2 mounting screws, 2 reset keys
(black), 2 stage two keys
A. Open
1. Insert the reset key into the reset keyhole and turn it.
2. Pull the cover open.
Figure 1 Front of manual station
Figure 2 Opening the station
Notes
• Environment: Indoor, dry
• Do not change factory applied finishes.
• Wire as shown so that supervision of connections is
maintained.
• Maximum wire size: 14 AWG
• ADA compliant.
• To be installed per ADA 4.27.1 to 4.27.4 inclusive.
• Wiring must be in accordance with CSA C22.1, Canadian
Electrical Code, Part I, Safety Standard for Electrical
Installations, Section 32 and CAN/ULC-S524, Standard for
Installation of Fire Alarm Systems.
• All manual fire alarm stations shall be installed as per the
specific requirements outlined in the UL/ULC codes, as well
as all other applicable national or local codes. Final
acceptance is subject to the local authority having
jurisdiction.
• These devices may be operated with a blunt hand (no use of
fingers) and do not require a striking action, tight grasping,
pinching, or twisting of the wrist. The force required to
actuate the devices is less than 22 N (5 lbf).
RESET KEYHOLE
STAGE TWO
KEYHOLE (MRM-802MP
A
ND MRM-822MP)
PUSH BAR
PULL HANDLE
LED FLASHES RED
WHEN POLLING AND IS
STEADY RED IN ALARM
COVER
MOUNTING
PLATE
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 1-888-647-2665
U.S.A
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Tel: 1-888-647-2665
MRM-800MP(U) Series
Fire Alarm Manual Station
www.secutron.com LT-6168SEC Rev. 0 Feb. 2023
2
B. Wire
Note: The maximum wire size is 14 AWG.
1. Strip wires to 10 mm (25/64”) maximum.
2. Push the wire into the terminal.
Note: The terminals have a push-in lock. To remove the wire,
push the terminal in with the screwdriver and pull out the
wire at the same time. See Figure 3.
Figure 3 Removing the wire
3. Wire as shown in Figure 4.
Figure 4 Wiring
C. Mount
Flush mount indoor: Single-gang electrical box.
Surface mount indoor: MRM-800 backbox with or without
STI-1230 (Deep Cover without Gasket)
Note: Mount the manual station with the Secutron logo on the
bottom.
Figure 5 Back of manual station
D. Set the addressable module
CAUTION: To set the address on this device, disconnect it from
the loop, or ensure that the loop to which it is connected is both
disconnected from the panel and shorted across both pairs of +
and −terminals at the device. Failing to take either of these steps
may change the address programming of previously configured
sensors on the same loop.
Follow the instructions in LT-6146, the MIX-4090 Device
Programmer Installation Manual, available on
http://www.secutron.com.
If left at its factory setting, the panel will report this device as
having no address.
The connector for the device programmer is inside the unit above
the addressable module, as shown in Figure 6.
Figure 6 Connector for device programmer
Using the manual station
Activate the alarm
1. Push in the push bar.
2. Pull down the pull handle.
A qualified person must reset the station by opening it with the
reset key. See Reset the manual station below.
Activate the stage two alarm (MRM-802MP and MRM-
822MP)
• Insert the stage two key into the stage two keyhole, and then
turn the key.
The stage two alarm activates immediately.
Note: The stage two alarm will activate automatically a certain
amount of time after the handle has been pulled if no
action is taken. This time is set in the Fire Alarm Control
Panel.
Reset the manual station
Note: Resetting the station does not cancel the alarm at the
panel.
1. Insert the reset key into the reset keyhole and turn it.
2. Pull the cover open. The switch is now reset.
3. Close and lock the station with the reset key.
4. Reset the Fire Alarm Control Panel to reset the alarm.
TO REMOVE WIRE:
1) PLACE A SMALL FLATHEAD
SCREWDRIVER INTO THE
GROOVE AND PUSH IN.
AT THE SAME TIME:
2) PULL THE WIRE OUT OF THE
TERMINAL.
1
2
TO NEXT DEVICE OR
LEAVE IT EMPTY
FROM
PREVIOUS
DEVICE
TO MAGLOCK
(MRM-822MP)
NO
C
+
+
NC
í
í
MOUNTING
HOLES
CONNECTOR
FOR DEVICE
PROGRAMMER

This manual suits for next models

5

Other Secutron Fire Alarm manuals

Secutron MR-3500 Series User manual

Secutron

Secutron MR-3500 Series User manual

Secutron MMX-2009-12NDS User manual

Secutron

Secutron MMX-2009-12NDS User manual

Secutron MRM-800 Series User manual

Secutron

Secutron MRM-800 Series User manual

Secutron MR-2300 series User manual

Secutron

Secutron MR-2300 series User manual

Secutron MR-2312-AT User manual

Secutron

Secutron MR-2312-AT User manual

Popular Fire Alarm manuals by other brands

Honeywell Farenhyt Series manual

Honeywell

Honeywell Farenhyt Series manual

Ei Electronics EiA200 Series manual

Ei Electronics

Ei Electronics EiA200 Series manual

C-TEC HUSH-ACTIV KITS Installer's guide

C-TEC

C-TEC HUSH-ACTIV KITS Installer's guide

Ampac 4310-0082 installation guide

Ampac

Ampac 4310-0082 installation guide

Wheelock RSS-24MCW installation instructions

Wheelock

Wheelock RSS-24MCW installation instructions

Polon-Alfa POLON 6000 manual

Polon-Alfa

Polon-Alfa POLON 6000 manual

SILENT KNIGHT INTELLIKNIGHT 5820XL Installation and operation manual

SILENT KNIGHT

SILENT KNIGHT INTELLIKNIGHT 5820XL Installation and operation manual

FireClass 5B manual

FireClass

FireClass 5B manual

Ampac ACP-02 installation guide

Ampac

Ampac ACP-02 installation guide

Notifier ACS Series installation manual

Notifier

Notifier ACS Series installation manual

GST DC-M9415 Series Installation sheet

GST

GST DC-M9415 Series Installation sheet

Siemens HMS-SZ installation instructions

Siemens

Siemens HMS-SZ installation instructions

Zeta PBTA-200 user manual

Zeta

Zeta PBTA-200 user manual

GST DI-9204Exd Installation and operation manual

GST

GST DI-9204Exd Installation and operation manual

Sierra Monitor Corporation 3100-xx instruction manual

Sierra Monitor Corporation

Sierra Monitor Corporation 3100-xx instruction manual

ADEMCO 1022 Troubleshooting

ADEMCO

ADEMCO 1022 Troubleshooting

Evonicfires Newton 6 instruction manual

Evonicfires

Evonicfires Newton 6 instruction manual

Pro-tec 6000/LOOP/REPEATER Installation and user guide

Pro-tec

Pro-tec 6000/LOOP/REPEATER Installation and user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.