
4 |LCB/CPS/BM Evaporative Cooler
INTRODUCTION
Cooler Models Exhaust
Opening
LCB250 BM500 CPL450 CPS450 2.0m2
LCB350 BM750 CPL700 CPS700 2.5m2
LCB450 BM900 CPL850 CPS850 3.0m2
LCB550 BM1150 CPL1100 CPS1100 4.0m2
* Please note that an average size door is 1.5m2
At Seeley International we manufacture
evaporative coolers from the highest quality
materials, and we have designed the product
to provide many years of economical, trouble-
free cooling.
Please take a few moments to read these
operating instructions, so that the most can
be gained from this investment. Keep these
instructions in a safe place for future reference.
Your installer should demonstrate the features
and procedures set out in these instructions.
The installer should also provide you with a
Model and Serial number, which can be lled
out on the last page.
KEEP THESE INSTRUCTIONS IN A SAFE
PLACE FOR FUTURE REFERENCE.
This appliance is not intended for use by
persons (including children) with reduced
physical, sensory or mental capabilities, or
lack of experience and knowledge, unless they
have been given supervision or instruction
concerning the use of the appliance by a
person responsible for their safety. Children
should be supervised to ensure they do not
play with the appliance.
Important Notes!
In areas where temperatures can cause water
supply pipes to freeze, a drain down facility
should be provided during the installation. This
drain down facility must be activated prior to
freezing conditions, to avoid possible damage
to the cooler components.
If the supply cord is damaged, it must be
replaced by a Seeley service agent or similarly
qualied person in order to avoid hazard.
New hose sets supplied with the appliance
are to be used. Old hose sets (from previous
installations) should not be re-used.
EFFECTIVE COOLING
To provide efcient cooling or ventilation the
building must have sufcient exhaust openings
to outdoors in the form of doors, windows or
other vents. To assist air circulation, open
windows or doors that are furthest from the
outlet vent in each room. In every room that
has an outlet vent, provide an exhaust opening
about 2 or 2.5 times the vent size of the room.
Where the design of the building prevents
adequate exhaust, consideration should be
given to the provision of mechanical extraction
such as an exhaust fan.
Total minimum openings for the whole building