Seeley LCB250 User manual

ILL1456-A
(English) (LCB, CPL, BM)
OWNER’S MANUAL
Evaporative Cooler
®

®
1CPL LCB BM Evaporative Cooler
Introduction
Wall Control Functions
Drain Valve & Bleed System
Maintenance
Service Checklist
Troubleshooting
7
9
6
3
2
10
®
INTRODUCTION
Cooler Models
Exhaust
Opening
2.0m2
LCB250 BM500 CPL450
CPL700
CPL850
CPL1100
BM750
BM900
BM1150
LCB350
LCB450
LCB550
2.5m2
3.0m2
4.0m2
2
SEELEY INTERNATIONAL – OWNER’S MANUAL
Congratulations on choosing a new Seeley
International cooler for your home.
Your cooler is built from the highest quality
materials and engineered to provide many years
of economical, trouble free cooling.
Please take a few minutes to read these
instructions so you have a full understanding of
how to operate your cooler. Your installer should
demonstrate the features and procedures set out
in these instructions. The installer should also
provide you with a Model and Serial number,
which can be filled out on the last page.
Keep these instructions in a safe place for
future reference.
This appliance is not intended for use by
persons (including children) with reduced
physical, sensory or mental capabilities, or lack
of experience and knowledge, unless they have
been given supervision or instruction concerning
use of the appliance by a person responsible for
their safety.
Children should be supervised to ensure that
they do not play with the appliance.
Effective cooling
To provide efficient cooling or ventilation the
building must have sufficient exhaust openings
to outdoors in the form of doors, windows or
other vents. To assist air circulation, open
windows or doors that are furthest from the
outlet vent in each room. In every room that has
an outlet vent, provide an exhaust opening about
2 or 2.5 times the vent size of the room. Where
the design of the building prevents adequate
exhaust, consideration should be given to the
provision of mechanical extraction such as an
exhaust fan.
Total minimum openings for the whole building
are demonstrated by the following table:
Please note that an average size door is 1.5m2

®
1CPL LCB BM Evaporative Cooler
Introduction
Wall Control Functions
Drain Valve & Bleed System
Maintenance
Service Checklist
Troubleshooting
7
9
6
3
2
10
®
INTRODUCTION
Cooler Models
Exhaust
Opening
2.0m2
LCB250 BM500 CPL450
CPL700
CPL850
CPL1100
BM750
BM900
BM1150
LCB350
LCB450
LCB550
2.5m2
3.0m2
4.0m2
2
SEELEY INTERNATIONAL – OWNER’S MANUAL
Congratulations on choosing a new Seeley
International cooler for your home.
Your cooler is built from the highest quality
materials and engineered to provide many years
of economical, trouble free cooling.
Please take a few minutes to read these
instructions so you have a full understanding of
how to operate your cooler. Your installer should
demonstrate the features and procedures set out
in these instructions. The installer should also
provide you with a Model and Serial number,
which can be filled out on the last page.
Keep these instructions in a safe place for
future reference.
This appliance is not intended for use by
persons (including children) with reduced
physical, sensory or mental capabilities, or lack
of experience and knowledge, unless they have
been given supervision or instruction concerning
use of the appliance by a person responsible for
their safety.
Children should be supervised to ensure that
they do not play with the appliance.
Effective cooling
To provide efficient cooling or ventilation the
building must have sufficient exhaust openings
to outdoors in the form of doors, windows or
other vents. To assist air circulation, open
windows or doors that are furthest from the
outlet vent in each room. In every room that has
an outlet vent, provide an exhaust opening about
2 or 2.5 times the vent size of the room. Where
the design of the building prevents adequate
exhaust, consideration should be given to the
provision of mechanical extraction such as an
exhaust fan.
Total minimum openings for the whole building
are demonstrated by the following table:
Please note that an average size door is 1.5m2

ILL1085-A
3
Starting your cooler
The ON/OFF button turns the air cooler on and
off.
There are two modes of operation to choose
from, Automatic mode or Manual mode. When
the air cooler is turned on, it will start in the
mode of operation it was in when last turned off.
If your air cooler has not been operated for a
while, then when you start it, “Pre Cool Cycle”
may sometimes flash on the display as shown.
This indicates that the water pump will operate to
saturate the cooling pads for a few minutes
before the fan is turned on. This is to ensure that
when the fan starts, only cool air enters the
building.
WALL CONTROL FUNCTIONS
WALL CONTROL FUNCTIONS - cont.
SEELEY INTERNATIONAL – OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®4
Automatic mode
Manual mode
The AUTO button is used to select Automatic
mode or Manual mode. When “Auto” is displayed
the cooler is under Automatic control and will
operate according to the temperature sensed at
the wall control.
When the air cooler is turned on, it will read the
temperature and set the cooler operation
accordingly. If the temperature increases at the
wall control, then the fan speed will increase. As
the temperature decreases the fan speed will
decrease until the cooler turns off.
Press S or T to overide the automatic
cooling level setting and adjust your room
temperature.
To switch to Manual mode, press AUTO until
“Man” appears in the display. In Manual mode
the cooling level can be manually adjusted.
In Manual mode, press to choose
between circulating cool air or un-cooled air.
When “Cool” is displayed, fresh cool air will
circulate into the building. When “Vent” is
displayed as shown, fresh un-cooled air will
circulate through the building.
Press S to increase the fan speed and
circulate more air. Press T to decrease the fan
speed and circulate less air. Press once to
change the speed by one increment. Hold the
button down to change the speed more quickly.
COOL
AUTOMATIC MODE DISPLAY
MANUAL MODE DISPLAY

ILL1085-A
3
Starting your cooler
The ON/OFF button turns the air cooler on and
off.
There are two modes of operation to choose
from, Automatic mode or Manual mode. When
the air cooler is turned on, it will start in the
mode of operation it was in when last turned off.
If your air cooler has not been operated for a
while, then when you start it, “Pre Cool Cycle”
may sometimes flash on the display as shown.
This indicates that the water pump will operate to
saturate the cooling pads for a few minutes
before the fan is turned on. This is to ensure that
when the fan starts, only cool air enters the
building.
WALL CONTROL FUNCTIONS
WALL CONTROL FUNCTIONS - cont.
SEELEY INTERNATIONAL – OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®4
Automatic mode
Manual mode
The AUTO button is used to select Automatic
mode or Manual mode. When “Auto” is displayed
the cooler is under Automatic control and will
operate according to the temperature sensed at
the wall control.
When the air cooler is turned on, it will read the
temperature and set the cooler operation
accordingly. If the temperature increases at the
wall control, then the fan speed will increase. As
the temperature decreases the fan speed will
decrease until the cooler turns off.
Press S or T to overide the automatic
cooling level setting and adjust your room
temperature.
To switch to Manual mode, press AUTO until
“Man” appears in the display. In Manual mode
the cooling level can be manually adjusted.
In Manual mode, press to choose
between circulating cool air or un-cooled air.
When “Cool” is displayed, fresh cool air will
circulate into the building. When “Vent” is
displayed as shown, fresh un-cooled air will
circulate through the building.
Press S to increase the fan speed and
circulate more air. Press T to decrease the fan
speed and circulate less air. Press once to
change the speed by one increment. Hold the
button down to change the speed more quickly.
COOL
AUTOMATIC MODE DISPLAY
MANUAL MODE DISPLAY

5
Timed automatic start
Timed automatic stop
You can set the air cooler so that it will turn on
after a set number of hours.
1. To set the delayed start time, press
with the cooler turned OFF. “Starting in” will
be displayed as shown with the last mode of
operation (Manual or Automatic).
2. If you want the air cooler to turn on in
Automatic mode with the previous settings,
then press until “Auto” is displayed.
Alternatively, if you want the air cooler to
turn on in Manual mode, press until
“Man” is displayed and then press
and then S or T to set the required fan
speed.
3. To set the time until the start, press .
4. Then press S or T to adjust the time.
The cooler can start up to 24 hours in
advance.
5. Press again to initiate the timed
automatic start. The timed start will not
repeat.
You can also set the air cooler so that it will turn
off after a set number of hours.
1. To set a delayed stop time, press
with the cooler running. ”Stopping in” will
display.
TIMER
AUTO
AUTO
COOL
TIMER
TIMER
TIMER
2. Press S or T to adjust the number of
hours before the air cooler will stop. The
maximum delay setting is 24 hours.
3. Press again to begin the timed stop.TIMER
SEELEY INTERNATIONAL – OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®6
Using the cooler
Now that you have read these instructions, press
the button to turn your air cooler on. If
the air cooler has not operated for a while, “Pre
Cool Cycle” will flash on the display. The “Pre
Cool Cycle will begin and will take only a few
minutes to complete. After this time, the fan will
come on automatically, and you can enjoy the
comfort of cool fresh air!
POWER
Air too cold
With the cooler running in Automatic mode, you
may find that you are too cold or that the air
cooler is blowing too much air. Press T to
lower the automatic temperature setting and
reduce the amount of cooling.
If you are too cold with the cooler running in
Manual mode, then press T to reduce the fan
speed. You can also circulate fresh un-cooled air
by pressing until “Vent” displays.COOL
Air not cold enough
You may find that with the air cooler running in
Automatic mode, you are not cool enough.
Simply press S to increase the cooling rate.
If you are not cool enough with the air cooler
running in Manual mode, then press S to
increase the fan speed. Ensure that cooled air is
circulating by pressing until “Cool”
displays.
COOL
You can experiment with the settings on your
wall control. This is the best way to get the
most from your air cooler.
WALL CONTROL FUNCTIONS - cont.
WALL CONTROL FUNCTIONS - cont.
This cooler comes with a continuous bleed
system (Coolair CPL, Braemar BM) or automatic
Drain Valve (standard for Braemar LCB, optional
for Coolair CPL and Braemar BM).
During operation, the bleed system will drain
small amounts of water. This ensures fresh water
is continually added to dilute salt accumulation in
the water caused through evaporation. This
helps keep the air cooler in good condition and
ensure optimum performance. The bleed rate will
depend on local operating conditions and will be
set by the installer.
If the drain valve was installed instead of the
continuous bleed system then your cooler will
automatically drain periodically. This ensures the
water is always fresh and helps maintain your
cooler in good condition to ensure optimum
cooling performance. The frequency of the
automatic drain may have been adjusted by your
installer according to the general water quality in
your area.
When the cooler is turned off for 72 hours, the
drain valve will open automatically and empty
water from the cooler. When the cooler is turned
on again, fan operation will delay for a few
minutes while the tank refills and the cooling
pads are saturated again.
At any time when the thermostat is OFF, you can
drain the cooler by pressing and holding S
and T for 1 second. The display will show “dr”
to confirm the operation has activated.
Continuous bleed system
Automatic drain valve
DRAIN VALVE & BLEED SYSTEM
ILL1478-A

5
Timed automatic start
Timed automatic stop
You can set the air cooler so that it will turn on
after a set number of hours.
1. To set the delayed start time, press
with the cooler turned OFF. “Starting in” will
be displayed as shown with the last mode of
operation (Manual or Automatic).
2. If you want the air cooler to turn on in
Automatic mode with the previous settings,
then press until “Auto” is displayed.
Alternatively, if you want the air cooler to
turn on in Manual mode, press until
“Man” is displayed and then press
and then S or T to set the required fan
speed.
3. To set the time until the start, press .
4. Then press S or T to adjust the time.
The cooler can start up to 24 hours in
advance.
5. Press again to initiate the timed
automatic start. The timed start will not
repeat.
You can also set the air cooler so that it will turn
off after a set number of hours.
1. To set a delayed stop time, press
with the cooler running. ”Stopping in” will
display.
TIMER
AUTO
AUTO
COOL
TIMER
TIMER
TIMER
2. Press S or T to adjust the number of
hours before the air cooler will stop. The
maximum delay setting is 24 hours.
3. Press again to begin the timed stop.TIMER
SEELEY INTERNATIONAL – OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®6
Using the cooler
Now that you have read these instructions, press
the button to turn your air cooler on. If
the air cooler has not operated for a while, “Pre
Cool Cycle” will flash on the display. The “Pre
Cool Cycle will begin and will take only a few
minutes to complete. After this time, the fan will
come on automatically, and you can enjoy the
comfort of cool fresh air!
POWER
Air too cold
With the cooler running in Automatic mode, you
may find that you are too cold or that the air
cooler is blowing too much air. Press T to
lower the automatic temperature setting and
reduce the amount of cooling.
If you are too cold with the cooler running in
Manual mode, then press T to reduce the fan
speed. You can also circulate fresh un-cooled air
by pressing until “Vent” displays.COOL
Air not cold enough
You may find that with the air cooler running in
Automatic mode, you are not cool enough.
Simply press S to increase the cooling rate.
If you are not cool enough with the air cooler
running in Manual mode, then press S to
increase the fan speed. Ensure that cooled air is
circulating by pressing until “Cool”
displays.
COOL
You can experiment with the settings on your
wall control. This is the best way to get the
most from your air cooler.
WALL CONTROL FUNCTIONS - cont.
WALL CONTROL FUNCTIONS - cont.
This cooler comes with a continuous bleed
system (Coolair CPL, Braemar BM) or automatic
Drain Valve (standard for Braemar LCB, optional
for Coolair CPL and Braemar BM).
During operation, the bleed system will drain
small amounts of water. This ensures fresh water
is continually added to dilute salt accumulation in
the water caused through evaporation. This
helps keep the air cooler in good condition and
ensure optimum performance. The bleed rate will
depend on local operating conditions and will be
set by the installer.
If the drain valve was installed instead of the
continuous bleed system then your cooler will
automatically drain periodically. This ensures the
water is always fresh and helps maintain your
cooler in good condition to ensure optimum
cooling performance. The frequency of the
automatic drain may have been adjusted by your
installer according to the general water quality in
your area.
When the cooler is turned off for 72 hours, the
drain valve will open automatically and empty
water from the cooler. When the cooler is turned
on again, fan operation will delay for a few
minutes while the tank refills and the cooling
pads are saturated again.
At any time when the thermostat is OFF, you can
drain the cooler by pressing and holding S
and T for 1 second. The display will show “dr”
to confirm the operation has activated.
Continuous bleed system
Automatic drain valve
DRAIN VALVE & BLEED SYSTEM
ILL1478-A

7SEELEY INTERNATIONAL – OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®8
Health regulations
Note that some regulating authorities require
services to be conducted at specific intervals.
Removal of pad frames
To remove a pad frame, insert a flat screw driver
tip into the slot as shown and lever until
disengagement occurs.
MAINTENANCE MAINTENANCE - cont.
Take hold of the pad frame and pull it towards
you until the internal side clips disengage.
Pivot the pad frame outwards and lift up. Take
care not to damage the pad. Repeat these steps
for the remaining pad frames.
End of season service
!
!
!
!
!
Turn off the power supply to the cooler.
External inspection
1 Inspect the external cabinet for any
damage or deterioration.
2 Inspect the dropper duct, flashing etc.
for signs of corrosion
3 Check water supply valve for correct
operation and leakage.
Turn off the water supply to the cooler.
Remove the pad frames as shown.
A. Turn off the power switch in the cooler.
!B. Check and clean the lid water channels.
!C. If fitted, first unclip and then remove the
bleed system as shown. Allow the tank
water to drain. Do not lose the o-ring.
A
ILL1060-B
B
C
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Thoroughly clean the tank and pump filter.
Do not replace the bleed system. (If a Drain
Valve is fitted it will automatically drain.)
Any time the thermostat is OFF, you can
drain the cooler by pressing and holding S
and T for 1 second. The display will show
“dr” to confirm the operation has activated.
Re-fit the pad frames.
Turn off the power supply to the cooler
Repeat external inspections as per End of
Season Service.
Remove the pad frames as shown.
Ensure the power switch in the cooler is off.
Gently wash the pads to remove any dust
build up during the winter period. If the pads
are in poor condition, replace them.
Inspect pad retention pins and washers for
damage and that they are securely fitted.
Replace the bleed system if it was removed
during previous maintenance and ensure
the o-ring is fitted. (If the cooler is fitted with
a drain valve this will not be necessary as it
will automatically close when the cooler
turns on).
Check the fan motor, mounts and blades for
damage.
Check electrical isolation switch operates
correctly.
Turn on the power switch inside the cooler.
Turn on the water and then the power to the
cooler
Check float valve operation.
Check water pump operation.
Re-fit the pad frames and run the cooler.
Check the pads are wetting evenly.
Check there are no water leaks either
internally or external to the cooler.
Check Drain Valve/Bleed Funnel operation.
Check Wall Control operation.
1 Manual and Auto modes
2 Speed Control
3 Display Panel.
Pre-season service
IMPORTANT: Do not damage the pads
with high pressure water spray.
Seasonal maintenance is only required if you
have a cooler fitted with a bleed system. The
following pages outline the maintenance
required at the end of the season and then at the
start of the next season. This ensures that your
cooler continues to operate efficiently.
If your cooler is fitted with a drain valve no
seasonal maintenance is required. However, we
require that the following components and the
operation thereof, be checked after the first year,
then every 2 years as routine maintenance.
(1)...... Pump.
(2)...... Drain Valve.
(3)...... Solenoid and associated filter.
(4)...... Fan motor operation and current.
(5)...... Float valve.
Routine maintenance may be required more
frequently in adverse environmental
situations or where the appliance is installed
in non-domestic applications.
Regular maintenance is essential to ensure the
cooler operates efficiently for many years.
Services must be performed before and after the
summer season. More frequent servicing may be
required in dusty conditions or in areas with poor
water quality. It is important to note that all
evaporative coolers have components that may
need periodic replacement (eg. filter pads, hoses,
o-rings etc).
WARNING: We recommend maintenance is
carried out by an authorised service agent.
Climbing onto the roof is hazardous and can
result in personal injury or property damage.
Failure to carry out maintenance will affect
your warranty coverage.

7SEELEY INTERNATIONAL – OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®8
Health regulations
Note that some regulating authorities require
services to be conducted at specific intervals.
Removal of pad frames
To remove a pad frame, insert a flat screw driver
tip into the slot as shown and lever until
disengagement occurs.
MAINTENANCE MAINTENANCE - cont.
Take hold of the pad frame and pull it towards
you until the internal side clips disengage.
Pivot the pad frame outwards and lift up. Take
care not to damage the pad. Repeat these steps
for the remaining pad frames.
End of season service
!
!
!
!
!
Turn off the power supply to the cooler.
External inspection
1 Inspect the external cabinet for any
damage or deterioration.
2 Inspect the dropper duct, flashing etc.
for signs of corrosion
3 Check water supply valve for correct
operation and leakage.
Turn off the water supply to the cooler.
Remove the pad frames as shown.
A. Turn off the power switch in the cooler.
!B. Check and clean the lid water channels.
!C. If fitted, first unclip and then remove the
bleed system as shown. Allow the tank
water to drain. Do not lose the o-ring.
A
ILL1060-B
B
C
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
!
Thoroughly clean the tank and pump filter.
Do not replace the bleed system. (If a Drain
Valve is fitted it will automatically drain.)
Any time the thermostat is OFF, you can
drain the cooler by pressing and holding S
and T for 1 second. The display will show
“dr” to confirm the operation has activated.
Re-fit the pad frames.
Turn off the power supply to the cooler
Repeat external inspections as per End of
Season Service.
Remove the pad frames as shown.
Ensure the power switch in the cooler is off.
Gently wash the pads to remove any dust
build up during the winter period. If the pads
are in poor condition, replace them.
Inspect pad retention pins and washers for
damage and that they are securely fitted.
Replace the bleed system if it was removed
during previous maintenance and ensure
the o-ring is fitted. (If the cooler is fitted with
a drain valve this will not be necessary as it
will automatically close when the cooler
turns on).
Check the fan motor, mounts and blades for
damage.
Check electrical isolation switch operates
correctly.
Turn on the power switch inside the cooler.
Turn on the water and then the power to the
cooler
Check float valve operation.
Check water pump operation.
Re-fit the pad frames and run the cooler.
Check the pads are wetting evenly.
Check there are no water leaks either
internally or external to the cooler.
Check Drain Valve/Bleed Funnel operation.
Check Wall Control operation.
1 Manual and Auto modes
2 Speed Control
3 Display Panel.
Pre-season service
IMPORTANT: Do not damage the pads
with high pressure water spray.
Seasonal maintenance is only required if you
have a cooler fitted with a bleed system. The
following pages outline the maintenance
required at the end of the season and then at the
start of the next season. This ensures that your
cooler continues to operate efficiently.
If your cooler is fitted with a drain valve no
seasonal maintenance is required. However, we
require that the following components and the
operation thereof, be checked after the first year,
then every 2 years as routine maintenance.
(1)...... Pump.
(2)...... Drain Valve.
(3)...... Solenoid and associated filter.
(4)...... Fan motor operation and current.
(5)...... Float valve.
Routine maintenance may be required more
frequently in adverse environmental
situations or where the appliance is installed
in non-domestic applications.
Regular maintenance is essential to ensure the
cooler operates efficiently for many years.
Services must be performed before and after the
summer season. More frequent servicing may be
required in dusty conditions or in areas with poor
water quality. It is important to note that all
evaporative coolers have components that may
need periodic replacement (eg. filter pads, hoses,
o-rings etc).
WARNING: We recommend maintenance is
carried out by an authorised service agent.
Climbing onto the roof is hazardous and can
result in personal injury or property damage.
Failure to carry out maintenance will affect
your warranty coverage.

9SEELEY INTERNATIONAL – OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®
SERVICE
“SERVICE”
immediately on power
up indicates
communications needs
to be established
Push & hold the
button for at
least 10 seconds until
the word
disappears
“DOWN”
“SERVICE”
10
PROBLEM – Unpleasant Odour
CAUSE ACTION
1. Odour from new pads. Allow time to condition by running the air
cooler. Drain the water, then allow the tank to
re-fill.
PROBLEM – Inadequate Cooling
CAUSE ACTION
1. Dry pads. Check water flow to pads.
Inspect fitment of distributor cap.
Check for blocked or kinked hose. If blocked,
dismantle, clean and flush or un-kink the hose.
2. Insufficient exhaust openings for
conditioned air.
Ensure sufficient openings. Refer to chart on
Pg. 2
3. Excessive ambient humidity
(See also Insufficient exhaust)
On days where the ambient humidity is high,
the cooler will not reduce the temperature as
much as on drier days.
If your wall control displays SERVICE or should you consider that your cooler requires service, contact
your local Dealer or the Service number on the back of this manual.
Note! If on initial start up the word “Service” appears on the controller and by pushing the on/off button
nothing happens, then you will need to establish communication between the wall control and the
electronic controller. Simply push and hold the “DOWN” button for approx. 10 seconds or until the
word “Service” disappears. If by pushing the on/off button a number appears, contact your local
Dealer or the Service number on the back of this manual.
TROUBLE-SHOOTING GUIDE
ROUTINE MAINTENANCE SERVICE SCHEDULE CHECKLIST
Service Item Check/adjust Clean Replace
1 2 3 4 5 1
Water Distribution System
Component Function
General Operation
Chillcel pads (replace as required)
Pad retaining washers / pins
Base / water reservoir
Pump filter basket
Water probes
Water distribution system
Washers, seals and O-rings (replace
as required)
Drain operation
Bleed rate set (where required)
Pump operation
Drain valve operation
Motor operation (set motor amps
where required)
Solenoid operation
Wall control operation
Water level set point
Water fill time
Water drain time
Water distribution across pads (no dry spots)
Airflow through system / outlets
General product condition
Service No Service Date Service Technician Service Company
No 1 ..................... .......................................... ........................................................
(includes correct fitting of all components and items -
replace as required)
234512345
No 2 ..................... .......................................... ........................................................
No 3 ..................... .......................................... ........................................................
No 4 ..................... .......................................... ........................................................
No 5 ..................... .......................................... ........................................................

9SEELEY INTERNATIONAL – OWNER’S MANUAL
®
CPL LCB BM Evaporative Cooler
®
SERVICE
“SERVICE”
immediately on power
up indicates
communications needs
to be established
Push & hold the
button for at
least 10 seconds until
the word
disappears
“DOWN”
“SERVICE”
10
PROBLEM – Unpleasant Odour
CAUSE ACTION
1. Odour from new pads. Allow time to condition by running the air
cooler. Drain the water, then allow the tank to
re-fill.
PROBLEM – Inadequate Cooling
CAUSE ACTION
1. Dry pads. Check water flow to pads.
Inspect fitment of distributor cap.
Check for blocked or kinked hose. If blocked,
dismantle, clean and flush or un-kink the hose.
2. Insufficient exhaust openings for
conditioned air.
Ensure sufficient openings. Refer to chart on
Pg. 2
3. Excessive ambient humidity
(See also Insufficient exhaust)
On days where the ambient humidity is high,
the cooler will not reduce the temperature as
much as on drier days.
If your wall control displays SERVICE or should you consider that your cooler requires service, contact
your local Dealer or the Service number on the back of this manual.
Note! If on initial start up the word “Service” appears on the controller and by pushing the on/off button
nothing happens, then you will need to establish communication between the wall control and the
electronic controller. Simply push and hold the “DOWN” button for approx. 10 seconds or until the
word “Service” disappears. If by pushing the on/off button a number appears, contact your local
Dealer or the Service number on the back of this manual.
TROUBLE-SHOOTING GUIDE
ROUTINE MAINTENANCE SERVICE SCHEDULE CHECKLIST
Service Item Check/adjust Clean Replace
1 2 3 4 5 1
Water Distribution System
Component Function
General Operation
Chillcel pads (replace as required)
Pad retaining washers / pins
Base / water reservoir
Pump filter basket
Water probes
Water distribution system
Washers, seals and O-rings (replace
as required)
Drain operation
Bleed rate set (where required)
Pump operation
Drain valve operation
Motor operation (set motor amps
where required)
Solenoid operation
Wall control operation
Water level set point
Water fill time
Water drain time
Water distribution across pads (no dry spots)
Airflow through system / outlets
General product condition
Service No Service Date Service Technician Service Company
No 1 ..................... .......................................... ........................................................
(includes correct fitting of all components and items -
replace as required)
234512345
No 2 ..................... .......................................... ........................................................
No 3 ..................... .......................................... ........................................................
No 4 ..................... .......................................... ........................................................
No 5 ..................... .......................................... ........................................................

seeleyinternational.com AU 0112
834955-F
Affix serial & model
number ker herestic
It is the policy of Seeley International to introduce continual
product improvement. Accordingly, specifications are
subject to change without notice. Please consult with your
dealer to confirm the specifications of the model selected.
When you contact your Dealer regarding service
or warranty please quote the cooler model
number and serial number as shown below.
®
Warranty Service
Australia 1-300-650-644
seeleyinternational.com
Other manuals for LCB250
1
This manual suits for next models
11
Table of contents
Other Seeley Air Cleaner manuals

Seeley
Seeley Breezair TBA Series User manual

Seeley
Seeley MobileMAX Series User manual

Seeley
Seeley BREEZAIR EXVQ User manual

Seeley
Seeley Breezair EXV User manual

Seeley
Seeley TBA250 User manual

Seeley
Seeley LCB250 User manual

Seeley
Seeley Convair CTA500 User manual

Seeley
Seeley LCQ User manual

Seeley
Seeley Braemar RPCQi Series User manual

Seeley
Seeley EXQ User manual