Senju Sprinkler RC-RES User manual

www.senjusprinkler.com Document No.U086209 • 01-29-2021Page 1 of 8
The Model RC-RES Residential Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder
type. They are decorative and fast responding. The Cover Plate Assembly hides the Deector, Heat Responsive Element
etc., which is concealed above the ceiling. The cover plate has a at prole, and its diameter is extremely small (2-5/8
inch, 68mm). The push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows for easy
installation of the cover plate. Therefore, the Model RC-RES should be your rst choice when aesthetics is the major
consideration for ultimate appeal and unbeatable performance is desired. The Model RC-RES is designed for residential
occupancies and is perfect for use in homes, hotels and other living quarters.
The Model RC-RES is to be used in wet pipe residential sprinkler systems for One- and Two- Family Dwellings and
Manufactured Homes per NFPA 13D; wet pipe residential sprinkler systems for Residential Occupancies up to and Including
Four Stories in Height per NFPA 13R; or, wet pipe sprinkler systems for the residential portions of any occupancies per
NFPA 13.
The Model RC-RES has a 3.7 (53.3 LPM/bar1/2) K-factor that meets the required residential ow rates with minimal residual
pressure, which allows for smaller pipe sizes and water supply requirements. For extended installation exibility, the
Model RC-RES provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in installation decreases the need for
precise cutting of the pipe that drops to the sprinkler and allows for a perfect t with a range of pipe lengths.
The heat sensitivity and water distribution design of Model RC-RES allows for an increased chance of residents to escape
or evacuate in case of a re. However, residential re sprinkler systems are not a substitute for re safety awareness or re
safety construction required by building codes.
“Lead Free” is dened in the Reduction of Lead in Drinking Water Act (S.3874) endorsed by AWWA’s Water Utility Council,
and California Assembly Bill #1953 as having less than or equal to a weighted average of 0.25% lead in wetted surface of
pipes, plumbing ttings and xtures.
GENERAL DESCRIPTION
Residential Lead Free
Flat Concealed Sprinkler, Pendent
Model RC-RES
K-Factor: 3.7 •SIN: SS8261
C US
NSF/ANSI/CAN 61 & 372

www.senjusprinkler.com Document No.U086209 • 01-29-2021Page 2 of 8
• Approvals:
{cULus Listed
{NSF/ANSI/CAN 61, NSF/ANSI 372
• Sprinkler Identication Number (SIN): SS8261
• Maximum Working Pressure: 175psi (12.1bar)
• Discharge Coefcient (Nominal K-Factor):
{K = 3.7 GPM/psi1/2 (53.3 LPM/bar1/2)
• Temperature Rating:
{162°F (72°C) Sprinkler with 140°F (60°C) Cover Plate
{205°F (96°C) Sprinkler with 162°F (72°C) Cover Plate
• Color Code (Sprinkler)
{162°F (72°C): Uncolored
{205°F (96°C): White
• Color Code (Cover Plate)
{140°F (60°C): No Mark
{162°F (72°C): White-Colored Mark
• Vertical Adjustment: 1/2 inch (12.8 mm)
• Cover Plate Finishes:
{Standard Finishes: White, Ivory, Beige, Brown, Black,
Nickel, Wood Grain
{Custom Finishes: Custom color and custom pattern
cover plates are available on special order. Contact a
Senju Sprinkler representative with any custom orders.
Please see chart on Page 8 for more detail.
• Physical Characteristics: Ref. Figures 1 and 1.1
Figure 1: Model RC-RES K = 3.7
Figure 1.1: Marking (Color Code)
The Model RC-RES must be installed and maintained in accordance with the rules stated herein as well as in
compliance with the applicable standards of the National Fire Protection Association regulations and the standards
of any other authorities having jurisdiction.
In the event of this condition, consult the authorities having jurisdiction for guidance and approval. Failure to do so
may impair the integrity of these devices.
It is the responsibility of the installing contractor to provide a copy of this document to the owner or their representative,
and in turn, it is the obligation of the owner to provide a copy of this document to a succeeding owner. The owner
is responsible for maintaining their re protection system and devices in proper operating condition. The installing
contractor or sprinkler manufacturer should be contacted with any related questions.
WARNINGS
TECHNICAL DATA

www.senjusprinkler.com Document No.U086209 • 01-29-2021Page 3 of 8
The herein stated rules for use and installation of Model RC-RES are provided by the manufacturer and must be strictly
implemented for safe and full results.
DESIGN CRITERIA
Notes
Residential Fire Sprinkler Systems should only be designed and installed by individuals who are completely familiar with
automatic sprinkler system design, installation procedures, and techniques.
Several criteria may apply to the installation and usage of each sprinkler. Consequently, it is recommended that the sprinkler
system designer review and develop a working understanding of the complete list of criteria prior to initiating the design of the
sprinkler system.
Questions concerning sprinkler installation and usage criteria, which are not covered by the following instructions, should be
submitted to your contracted company. Include sketches and technical details, as appropriate.
In some instances, the requirements of this document may concern specications which are more stringent, and which take
precedence over those specied in NFPA 13, 13D, 13R, or by the authority having jurisdiction.
The Model RC-RES must not be used in applications where the air pressure above the ceiling is greater than that below.
Inspect all sprinklers after installation to ensure that both the gap between the cover plate, ceiling and the 6 slots in the cup
are open and free from any air ow impediment.
The spray from the sprinkler is distributed radially outward and downward from the sprinkler deector. Consequently, the
sprinklers must be located such that there will be no blind spaces shielded from spray by partitions, room dividers, overhangs
or other parts of the dwelling structure.
The number of sprinklers within each compartment (as dened by NFPA 13D, 13R, or 13) must be kept as few as possible while
observing all guidelines relating to obstructions and spacing.
Use only the Cover Plate provided for the Model RC-RES. The sprinkler must be secured in place by rmly fastening the
sprinkler system piping to the structure. If the sprinkler is not properly secured in position, reaction forces resulting from
sprinkler operation could alter its orientation and its water distribution pattern.
OPERATION
In case of re, the solder component that holds together the Cover Plate and the Retainer melts. Then the Cover Plate is
released at once. As a result, the Deector drops down to the intended position. Two Heat Collectors are exposed to re,
and when sufcient heat from the re is reached, internal components of the sprinkler fall apart. This leads to the water
ow to be distributed on the affected re area. (Ref. Figure 2)
Figure 2: Operation Process (For illustrative purposes only)

www.senjusprinkler.com Document No.U086209 • 01-29-2021Page 4 of 8
Available Sprinkler Temperature Ratings
Sprinkler Temperature
Classication
Sprinkler Nominal
Temperature Rating
Maximum Ambient Ceiling
Temperature
Temperature Rating of the
Cover Plate Assembly
Ordinary 162°F (72°C) 100°F (38°C) 140°F (60°C)
Intermediate 205°F (96°C) 150°F (66°C) 162°F (72°C)
Obstruction to Water Distribution
Locations of sprinklers must follow the obstruction rules of NFPA 13, 13D and 13R for Residential Sprinklers.
General Service Conditions
The Model RC-RES must only be utilized in WET PIPE sprinkler systems.
Heat Source Criteria
Refer to NFPA 13D, 13R or 13 for the requirements relating to the prevention of possible activation of the Heat Responsive
Element of Model RC-RES, due to the exposure of a heat source other than an actual re.
Precautionary Warnings for Corrosive Environments
Model RC-RES sprinklers should not be installed where they may be subjected to a corrosive environment including the
following:
1. Chlorine ion and Chloride environment
Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride. Exposure to
this environment may result in sprinklers operating under Non-Fire conditions or Not Operating when exposed to an
actual re.
2. Sprinkler system piping with Copper
Sprinkler systems should be constructed in compliance with the applicable standards and the requirements for
copper piping when copper piping is used in the sprinkler system. (Reference standards NFPA 13, ASTM B813, B828,
and CDA (Copper Development Association) – Solder Joint)
All residual ux must be removed from the interior and exterior of the copper piping by thoroughly ushing before
installation of the Sprinkler Heads. Otherwise, residues of ux may cause corrosion and/or leakage in the sprinkler
system.
Hydraulic Design Criteria
The minimum required sprinkler ow rates for systems designed to NFPA 13D or 13R are given in Table A as a function of
temperature rating and the maximum allowable coverage area. The sprinkler ow rate is the minimum required discharge
from the most hydraulically demanding sprinkler from each of the total number of “design sprinklers” as specied in NFPA
13D or 13R.
For systems designed to NFPA 13, the number of designed sprinklers is to be the four most hydraulically demanding
sprinklers. The minimum required discharge from each of the four sprinklers is to be the greater of the following:
• The ow rates given in Table A for NFPA 13D and 13R as a function of temperature rating and maximum allowable
coverage area.
• A minimum discharge of 0.1GPM/sq.ft. [4.07LPM/sq.m] over the “design area” comprised of the four most hydraulically
demanding sprinklers for the actual coverage area being protected by the four sprinklers.

www.senjusprinkler.com Document No.U086209 • 01-29-2021Page 5 of 8
INSTALLATION
The Model RC-RES must be installed in accordance with the following instructions:
a. For coverage area dimensions less than the above mentioned, it needs to use the minimum required ow for the Next
Higher Coverage Area listed.
b. Requirement is based on minimum ow in GPM (LPM) from each sprinkler. The associated residual pressures are
calculated using the nominal K-Factor. Refer to Hydraulic Design Criteria Section for details.
NOTES
Do not use any sprinklers which have been subjected to potential mechanical damage. Do not use any sprinklers which show
deformation or cracking in either the Sprinkler or the Protective Cap.
Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for
damage to the sprinklers that could cause improper operation or non-operation.
The Protective Cap must remain on the sprinkler during installation. After the installation is completed, the Protective Cap must
be removed to place the sprinkler in service.
Use a torque of 7 to 14 ft·lbs (9.5 to 19.0 N·m) to achieve a 1/2 inch NPT sprinkler joint. If you exceed the recommended maximum
torque, this could result in damage to the sprinkler inlet, which may lead to leakage from the sprinkler.
Use only NR-H model wrench socket for installation of RC-RES sprinklers. Use of any other wrench or socket is prohibited and
may cause damage to the sprinkler.
In case of insufcient adjustment in Cover Plate installation, do not try to overly tighten, screw the sprinkler too loosely or make
any modication to the cover plate assembly. Readjust the sprinkler tting for a better t.
Do not rotate the Cap Removal Tool for RC to the left with force when placing the two hook arms into place. The installed sprinkler
may become loosened, which may cause water leakage.
Sprinkler Spacing Criteria
The minimum spacing between sprinklers is 8 feet (2.4m). The maximum spacing between sprinklers cannot go beyond
the coverage area calculated by using the specic hydraulic factors. (Ref. Table A)
Table A. NFPA 13D & 13R Wet Pipe Hydraulic Design Criteria for Model SS8261
For systems with ceiling types smooth at horizontal, or beamed, or sloped, in accordance with NFPA 13D, 13R or 13 as
applicable.
Maximum
Coverage
Area(a)
Ft. x Ft.
(m x m)
Maximum
Spacing
Ft.
(m)
Ordinary Temperature
Rating 162˚F (72˚C)
Intermediate Temperature
Rating 205˚F (96˚C) Deector to
Ceiling
Installation
Type
Minimum
Spacing
Ft. (m)
Flow(b) GPM
(LPM)
Pressure(b)
PSI (bar)
Flow(b) GPM
(LPM)
Pressure(b)
PSI (bar)
12 x 12
(3.7 x 3.7)
12
(3.7)
10
(37.9)
7.3
(0.50)
10
(37.9)
7.3
(0.50)
Smooth
Ceilings 3/8
to 7/8 Inches.
Beamed
Ceilings per
NFPA 13D,
13R or 13.
Installed in
beam 3/8 to
7/8 inches
below bottom
of beam.
Concealed 8
(2.4)
14 x 14
(4.3 x 4.3)
14
(4.3)
10
(37.9)
7.3
(0.50)
10
(37.9)
7.3
(0.50)
15 x 15
(4.6 x 4.6)
15
(4.6)
12
(45.4)
10.5
(0.72)
12
(45.4)
10.5
(0.72)
16 x 16
(4.9 x 4.9)
16
(4.9)
13
(49.2)
12.3
(0.85)
13
(49.2)
12.3
(0.85)

www.senjusprinkler.com Document No.U086209 • 01-29-2021Page 6 of 8
Figure 5: Protective Cap Removal
Figure 3: Installation Figure 4: Ratchet & Socket
Installation Steps
Step 1: The installation requirements for the sprinkler are as follows: to be installed only in the pendent position with the
waterway perpendicular to the ceiling. Install the sprinkler tting so that the distance from the face of the tting to the
mounting surface will be nominally 2 inches (50.8mm) as shown in Figure 3.
Step 2: With pipe thread sealant applied to the threads, hand tighten the sprinkler into the sprinkler tting. Then tighten it
with the Socket NR-H or Ratchet (3/8” drive) & Socket NR-H Combination (Ref. Figure 4). The teeth of the Socket must t
perfectly with the grooves on the Sprinkler for proper installation (Ref. Figure 4).
Step 3: If desired, the Protective Cap may also be used to locate the center of the clearance hole by gently pushing the
ceiling material against the center point of the Protective Cap. Before the installation of the ceiling, the sprinkler installation
can be started with a 2-3/8 inch (60mm) diameter clearance hole (Ref. Figure 3). Use the “Vertical Adjustment” indicator
on the Protective Cap to check for proper installation height (Ref. Figure 3).
Step 4: Use the Cap Removal Tool for RC to remove the Protective Cap (Ref. Figure 5), and then push or screw a Cover
Plate Assembly on the Cup of the Sprinkler by hand until its ange just has contact with the ceiling (Ref. Figure 6 and
Figure 7). Stop tightening the Cover Plate Assembly once the ange has contact with the ceiling. If the ceiling has been
lifted from its normal position in the process of tightening the Cover Plate Assembly, readjust the cover plate assembly as
necessary. If the ange of the Cover Plate Assembly cannot contact the ceiling sufciently, readjust the sprinkler tting as
necessary. When properly installed, there is a nominal 1/16 inch (1.6mm) air gap between the lip of the Cover Plate and
the ceiling, as shown in Figure 6.

www.senjusprinkler.com Document No.U086209 • 01-29-2021Page 7 of 8
CARE & MAINTENANCE
The following instructions must be implemented for the maintenance and service of the Model RC-RES.
Notes
Wet pipe sprinkler systems must be maintained at a minimum temperature of 40°F / 4°C to prevent freezing and bursting of the
pipe and/or sprinklers.
Automatic sprinklers are not to be tested with a heat source. Operation of the heat responsive element can result.
Absence of a Cover Plate Assembly may delay the response time of the sprinkler in case of a re.
Install the cover plate assembly properly, as shown in Figure 6. Improper installation of the cover plate assembly may cause
improper operation or non-operation.
If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does not
seal off any of the air gap.
Factory painted Cover Plates must not be repainted. They should be replaced, if necessary, by factory painted cover plates. Non-
factory applied paint may adversely delay or prevent sprinkler operation in case of a re.
Do not pull the Cover Plate. Separation may result.
In preparation for maintenance of the re protection system, permission to close the main control valve must be obtained from the
proper authorities, and all affected parties by this action, and must be informed before the maintenance session can commence.
Do NOT enclose any sprinklers within drapes, curtains, or valances.
Do NOT hang anything from the sprinklers.
Do NOT clean the sprinklers with soap and/or water, detergents, ammonia, cleaning uids, or other chemicals. Remove dust,
lint, cobwebs, cocoons, insects, and larvae by gently brushing with a feather duster or gently vacuuming with a soft bristle (i.e.,
dusting) brush attachment.
Exercise suitable safety precautions in the use and storage of highly ammable materials. The rapid rate of re development and
spread of these materials can reduce the ability of the sprinkler system to aid in the control of a re involving such hazards.
Figure 7: Installation (Correct and Incorrect)
Figure 6: Installation (Cover Plate Assembly)

www.senjusprinkler.com Document No.U086209 • 01-29-2021Page 8 of 8
ORDER PROCEDURE
LIMITED WARRANTY
When placing an order, please contact a local distributor with the following information (Model Name, Temperature
Rating and Finish).
For details of warranty, refer to Sales Contract.
Leaking or corroded sprinklers must be replaced.
Automatic Sprinklers must be kept in a cool and dry place.
Automatic sprinklers must never be physically altered, such as painted, plated, or coated, once shipped from the factory. If the
sprinklers have been in any way modied, they must be replaced.
Great caution must be applied to prevent damage to the sprinklers at all stages - before, during, and after installation. Damaged
units because of dropping, hitting, over-tightening, or wrench slippage, must be replaced.
The Model RC-RES must only be replaced with pendent sprinklers which are listed for residential re protection service and
which have the same nominal K-Factor, the same coverage area, and the same or lower ow ratings (as indicated under Table A
“Hydraulic Design Criteria”).
When remodeling, such as by adding false beams or light xtures or changing the location of compartment walls, rst verify that
the new construction will not violate the installation requirements of the applicable standards of NFPA. Alter the new construction
and/or the sprinkler system to suit the requirements of this document and the applicable NFPA regulations.
The owner is responsible for the maintenance of the sprinkler system, including inspection and testing of its compliance with
this document, as well as the standards of the National Fire Protection Association (e.g., NFPA 25), and the regulations of any
other authorities having jurisdiction. The owner should direct any questions regarding the above rules and regulations to the
installing contractors or the sprinkler manufacturer. It is recommended that automatic sprinkler systems be inspected, tested,
and maintained by a qualied Inspection Service in accordance with NFPA 25.
Sprinkler
• Model: RC-RES
SIN: SS8261, Residential Flat Concealed Sprinkler, Pendent, K3.7, Temperature: 162°F (72°C) or 205°F (96°C)
Cover Plate Assembly
• 2-5/8 inch (φ68mm) or 3-1/4 inch (φ83mm) or 2-5/8 inch square (□68mm), Order separately from Sprinkler
Please refer to the chart below for available sizes, temperature, and nishes.
Tools & Accessories
• Socket NR-H
for use with a 3/8” drive ratchet (not included)
• Socket NR-H Plastic
for use with a 1/2” drive ratchet (not included)
• Cap Removal Tool for RC
• Cover Plate Installation Tool
Standard Finishes Custom
Finishes
White Ivory Beige Brown Black Nickel Copper Wood
Grain
Custom
Color
Custom
Pattern
2-5/8” Round, 140°F ------
3-1/4” Round, 140°F
2-5/8” Square, 140°F -------
2-5/8” Round, 162°F -------
3-1/4” Round, 162°F - -
2-5/8” Square, 162°F - - - - - - -
Other manuals for RC-RES
2
This manual suits for next models
1
Table of contents
Other Senju Sprinkler Irrigation System manuals

Senju Sprinkler
Senju Sprinkler HF-RES User manual

Senju Sprinkler
Senju Sprinkler FR-QR User manual

Senju Sprinkler
Senju Sprinkler SS8464 User manual

Senju Sprinkler
Senju Sprinkler ZN-RES User manual

Senju Sprinkler
Senju Sprinkler ZN-UF User manual

Senju Sprinkler
Senju Sprinkler RC-QR-EC User manual

Senju Sprinkler
Senju Sprinkler RC-QR User manual

Senju Sprinkler
Senju Sprinkler CN-RES User manual

Senju Sprinkler
Senju Sprinkler ZN-QR User manual

Senju Sprinkler
Senju Sprinkler RC-RES User manual