Sentera RSCOX-R Service manual

Mounting and operating instructions
RSCOX-R MULTIFUNCTIONAL
ROOM TRANSMITTER

www.sentera.eu
MIW-RSCOX-R-EN-000 - 17 / 06 / 2020 2 - 9
Table of contents
SAFETY AND PRECAUTIONS 3
PRODUCT DESCRIPTION 4
ARTICLE CODES 4
INTENDED AREA OF USE 4
TECHNICAL DATA 4
STANDARDS 4
OPERATIONAL DIAGRAMS 5
WIRING AND CONNECTIONS 6
MOUNTING & OPERATING INSTRUCTIONS IN STEPS 6
OPERATING INSTRUCTIONS 8
VERIFICATION OF INSTALLATION INSTRUCTIONS 9
TRANSPORT AND STORAGE 9
WARRANTY AND RESTRICTIONS 9
MAINTENANCE 9
RSCOX-R MULTIFUNCTIONAL
ROOM TRANSMITTER

www.sentera.eu
MIW-RSCOX-R-EN-000 - 17 / 06 / 2020 3 - 9
back to the table of contents
SAFETY AND PRECAUTIONS
Read all the information, the datasheet, Modbus map, mounting and operating
instructions and study the wiring and connection diagram before working with the
product. For personal and equipment safety, and for optimum product performance,
make sure you entirely understand the contents before installing, using, or maintaining
this product.
For safety and licensing (CE) reasons, unauthorised conversion and/ or modifications
of the product are inadmissible.
e product should not be exposed to abnormal conditions, such as extreme
temperatures, direct sunlight or vibrations. Long-term exposure to chemical
vapours in high concentration can affect the product performance. Make sure the
work environment is as dry as possible; avoid condensation.
All installations shall comply with local health and safety regulations and local
electrical standards and approved codes. is product can only be installed by
an engineer or a technician who has expert knowledge of the product and safety
precautions.
Avoid contacts with energised electrical parts. Always disconnect the power
supply before connecting, servicing or repairing the product.
Always verify that you apply appropriate power supply to the product and use
appropriate wire size and characteristics. Make sure that all the screws and nuts
are well tightened and fuses (if any) are fitted well.
Recycling of equipment and packaging should be taken into consideration and these
should be disposed of in accordance with local and national legislation/regulations.
In case there are any questions that are not answered, please contact your
technical support or consult a professional.
RSCOX-R MULTIFUNCTIONAL
ROOM TRANSMITTER

www.sentera.eu
MIW-RSCOX-R-EN-000 - 17 / 06 / 2020 4 - 9
back to the table of contents
PRODUCT DESCRIPTION
RSCOX-R are multifunctional room transmitters which measure
temperature, relative humidity, carbon monoxide and nitrogen dioxide
levels. Based on the temperature and relative humidity measurements,
the dew-point temperature is calculated. They feature a wide range of
low voltage power supply and three analogue / modulating outputs -
one for temperature, one for relative humidity and one for CO / NO2.
All the parameters and measurements are accessible via Modbus RTU.
ARTICLE CODES
Code Supply Imax
RSCOF-R 18—34 VDC
119 m A
RSCOG-R 18—34 VDC /
15—24 VAC ±10%
INTENDED AREA OF USE
■Measurement of indoor temperature, relative humidity and CO and NO2trends
■Monitoring of CO and NO2trends in buildings and parking garages
■For indoor use only
TECHNICAL DATA
■Analogue / modulating output type:
►0—10 VDC mode: min. load 50 kΩ (RL≥ 50 kΩ)
►0—20 mA mode: max. load 500 Ω (RL≤ 500 Ω)
►PWM mode (open-collector type): PWM Frequency: 1 kHz, min. load 50 kΩ (RL≥
50 kΩ); PWM voltage level 3,3 or 12 VDC
■Selectable temperature range: 0—50 °C
■Selectable relative humidity range: 0—100 %
■Selectable CO range: 0—1.000 ppm
■Replaceable CO / NO2sensor element
■Warm-up time: 1 hour
■3 LEDs with adjustable light intensity for status indication
■Accuracy: ±0,4 °C (0—50 °C); ±3 % rH (0—100 % rH)
■Enclosure:
►rear plate: plastic ABS, black (RAL 9004)
►front cover: ASA, ivory (RAL 9010)
■Protection standard: IP30 (according to EN 60529)
■Typical range of use:
►temperature: 0—50 °C
►rel. humidity: 0—95 % rH, (non-condensing)
►CO: 0—1.000 ppm
■Storage temperature: -10—60 °C
STANDARDS
■EMC directive 2014/30/EU:
►EN 60730-1:2011 Automatic electrical controls for household and similar use -
Part 1: General requirements
►EN 61000-6-1:2007 Electromagnetic compatibility (EMC) - Part 6-1: Generic
standards —Immunity for residential, commercial and light industrial
environments
►EN 61000-6-3:2007 Electromagnetic compatibility (EMC) - Part 6-3: Generic
RSCOX-R MULTIFUNCTIONAL
ROOM TRANSMITTER

www.sentera.eu
MIW-RSCOX-R-EN-000 - 17 / 06 / 2020 5 - 9
back to the table of contents
standards —Emission standard for residential, commercial and light-industrial
environments Amendments A1:2011 and AC:2012 to EN 61000-6-3
►EN 61326-1:2013 Electrical equipment for measurement, control and laboratory
use - EMC requirements - Part 1: General requirements
►EN 61326-2-3:2013 Electrical equipment for measurement, control and
laboratory use - EMC requirements - Part 2-3: Particular requirements —Test
configuration, operational conditions and performance criteria for transducers
with integrated or remote signal conditioning
■Low Voltage Directive 2014/35/EU
►EN 60529:1991 Degrees of protection provided by enclosures (IP Code)
Amendment AC:1993 to EN 60529
►EN 60730-1:2011 Automatic electrical controls for household and similar use -
Part 1: General requirements
■WEEE 2012/19/ EC
■RoHs Directive 2011/65/EC
OPERATIONAL DIAGRAMS
10
0
20
30
40
50
60
70
80
90
100
Minimum
range
Minimum
alert
Maximum
alert
Analogue /
modulating
outputs [%]
T [°C] / rH [%] / CO / NO2 [ppm] *
Maximum
range
* LED indicaons - T (default), rH or CO / NO2
Analogue / modulang
output 2 [%]
100
0Min range Max range 100 rH [%]
Analogue / modulang
output 1 [%]
100
0 0
Min range Max range 50 T [°C]
Analogue / modulang
output 3 [%]
100
1
0,05
Min range Max range 1.000
10
CO [ppm]*
NO2[ppm]
*During warming-up, CO and NO2measurements will return 0 ppm
RSCOX-R MULTIFUNCTIONAL
ROOM TRANSMITTER

www.sentera.eu
MIW-RSCOX-R-EN-000 - 17 / 06 / 2020 6 - 9
back to the table of contents
WIRING AND CONNECTIONS
Article type RSCOF-R RSCOG-R
VIN 18—34 VDC 18—34 VDC 15—24 VAC ±10%
GND Ground Common ground AC ~
AModbus RTU (RS485), signal A Modbus RTU (RS485), signal A
/B Modbus RTU (RS485), signal /B Modbus RTU (RS485), signal /B
AO1 Analogue / modulating output 1 for temperature
measurement (0—10 VDC / 0—20 mA / PWM)
Analogue / modulating output 1 for temperature
measurement (0—10 VDC / 0—20 mA / PWM)
GND Ground AO Common ground
AO2 Analogue / modulating output 2 for relative humidity
measurement (0—10 VDC / 0—20 mA / PWM)
Analogue / modulating output 2 for relative humidity
measurement (0—10 VDC / 0—20 mA / PWM)
GND Ground AO Common ground
AO3 Analogue / modulating output 3 for CO / NO2*
measurement (0—10 VDC / 0—20 mA / PWM)
Analogue / modulating output 3 for CO / NO2*
measurement (0—10 VDC / 0—20 mA / PWM)
GND Ground AO Common ground
Connections Spring contact terminal blocks, cable cross section: 1,5 mm2
*Adjustable via Modbus Holding register 67 (default is CO measurement).
ATTENTION e -F version of the product is not suited for 3-wire connection. It has separate
grounds for power supply and analogue output. Connecting both grounds
together might result in incorrect measurements. Minimum 4 wires are required
to connect -F type sensors.
e -G version is intended for 3-wire connection and features a ‘common ground’.
is means that the ground of the analogue output is internally connected with
the ground of the power supply. For this reason, -G and -F types cannot be
used together on the same network. Never connect the common ground of -G
type articles to other devices powered by a DC voltage. Doing so might cause
permanent damage to the connected devices.
MOUNTING & OPERATING INSTRUCTIONS IN STEPS
Before you start mounting the unit, read carefully “Safety and Precautions”.
Choose a smooth surface for installation (a wall, panel and etc.).
ATTENTION Mount the sensor in a well-ventilated area, where it receives adequate airflow
for proper operation and hide it from direct sunlight. Make sure it can be easily
accessed for service.
Follow these steps:
1. Using a flat screwdriver, remove the front white cover by releasing the snap-fits
on its both sides (see Fig. 1 Snap-fits release).
2. Insert the cables through the opening on the rear plate (see Fig. 2 Mounting
dimensions.)
3. Using suitable fastening materials (not supplied), position the room sensor at
least 1,5 m from the floor. When planning the installation, allow enough clearance
for maintenance and service. Mount the sensor in a well-ventilated area. Mind
the correct mounting position and unit dimensions. See Fig. 2 and Fig. 3.
RSCOX-R MULTIFUNCTIONAL
ROOM TRANSMITTER

www.sentera.eu
MIW-RSCOX-R-EN-000 - 17 / 06 / 2020 7 - 9
back to the table of contents
Fig. 1 Snap-fits release Fig. 2 Mounting dimension
Push here to
release
2x Ø 6
59,8
9,8
74,5
104,5
20
104,5
25,6
70,5
Fig. 3 Mounting position
Correct Incorrect
Position at min. 1,5 m
from the floor
4. Do the wiring according to the wiring diagram (see Fig.4).
Fig. 4 Wiring and connections
Supply voltage
RSCOF-R: 18—34 VDC
RSCOG-R: 18—34 VDC /
15—24 VAC ±10 %
Modbus
RTU
A
/B
Analogue / modulating output 1 -
temperature
Analogue / modulating output 2 -
relative humidity
Analogue / modulating output 3 -
CO/NO2
5. Put back the cover snap it in.
6. Switch on the mains supply.
7. Customise the factory settings to the desired ones via the 3SModbus software
or Sensistant (if necessary). For the default factory setting refer to the product
Modbus register map.
RSCOX-R MULTIFUNCTIONAL
ROOM TRANSMITTER

www.sentera.eu
MIW-RSCOX-R-EN-000 - 17 / 06 / 2020 8 - 9
back to the table of contents
5.
For the complete Modbus register data, refer to the product Modbus Register
Map, which is a separate document attached to the article code on the website
and contains the registers list. Products with earlier firmware versions may not be
compatible with this list.
NOTE
Optional settings
To assure correct communication, the NBT needs to be activated in only two devices
on the Modbus RTU network. If necessary, enable the NBT resistor via 3SModbus or
Sensistant (Holding register 9).
Example 1 Example 2
RX
ТX
NBT
NBT
Slave 2
Master
Slave n
Slave 1
Slave 2
Slave 1
RX
ТX
NBT
NBT
Master
Slave n
On a Modbus RTU network, two bus terminators (NBTs) need to be activated.
NOTE
NOTE e sensor is not designed, manufactured or intended for use or re-sale as control
or monitoring equipment in environments requiring life safety performance, in
which the failure of the sensor could lead directly to death, personal injury, or
severe physical or environmental damage.
OPERATING INSTRUCTIONS
e warm-up time for the sensor to attain its highest accuracy and performance
level once the voltage supply has been applied is 1 hour. During warm-up time, CO
and NO2measurement will return 0 ppm.
NOTE
Calibration procedure:
Sensor calibration is not necessary. All sensor elements are calibrated and tested in
our factory.
In the unlikely event of CO / NO2sensor element failure, this component can be
replaced.
Bootloader
anks to the bootloader functionality, the unit firmware can be updated via Modbus
RTU communication. With 3SM boot Application (part of 3SM center software
suite), ‘boot mode’ is automatically activated and the firmware can be updated.
NOTE Make sure the power supply does not get interrupted during “bootload” procedure,
otherwise you risk losing unsaved data.
LED indications
1. When the green LED is on, the measured value (temperature, relative
humidity or CO / NO2) is between the minimum and maximum alert range
values (Fig. 5 - 1).
2. When the yellow LED is on, the measured value (temperature, relative
humidity or CO / NO2) is in the alert range (Fig. 5 - 2).
3. When the red LED is on, the measured value (temperature, relative humidity
or CO / NO2) is below the minimum measurement range value or above the
RSCOX-R MULTIFUNCTIONAL
ROOM TRANSMITTER

www.sentera.eu
MIW-RSCOX-R-EN-000 - 17 / 06 / 2020 9 - 9
back to the table of contents
maximum value. Blinking red LED indicates loss of communication with a
sensor (Fig. 5 - 3).
Fig. 5 LED indications
3
2
1
NOTE By default, the LED indication refers to temperature measurements. is can be
changed to relative humidity or CO / NOvalues via Modbus Holding Register 79
(see Table Holding registers).
NOTE Green LED intensity can be adjusted between 0 and 100 % with a step of 10 %
according to the value set in Holding register 80.
Ambient light sensor
e measured light intensity in lux is available in Input Register 41. Additionally,
an active and standby level can be defined in Holding registers 35 and 36. Input
Register 42 indicates if the measured value is below standby level, above active
level or in between both levels:
■Ambient light level < standby level: Input Register 42 indicates “Standby”.
■Ambient light level > active level: Input Register 42 indicates “Active”.
■Standby level < Ambient light level < Active level: Input Register 42 indicates “Low
intensity”.
VERIFICATION OF INSTALLATION INSTRUCTIONS
After switching on the power supply one of the LEDs lights up according to the
status of the measured variable. If this is not the case, check the connections.
TRANSPORT AND STORAGE
Avoid shocks and extreme conditions; stock in original packing.
WARRANTY AND RESTRICTIONS
Two years from the delivery date against defects in manufacturing. Any modifications
or alterations to the product after the date of publication relieve the manufacturer
of any responsibilities. e manufacturer bears no responsibility for any misprints or
mistakes in this data.
MAINTENANCE
In normal conditions this product is maintenance-free. If soiled, clean with a dry or
damp cloth. In case of heavy pollution, clean with a non-aggressive product. In these
circumstances the unit should be disconnected from the supply. Pay attention that
no fluids enter the unit. Only reconnect it to the supply when it is completelydry.