Sidite SR882 User manual

Manual of Solar Pump Station SR882
for Split Pressurized Solar Hot water System
2011.07.07

SR882 operation manual
~ 1 ~
Contents
Solar pump station installation and operation manual
Contents...................................................................................................................... 1
Solar pump station installation and operation manual............................................... 4
1. Solar pump station with integrated controller.......................................................................4
1.1 Scope of delivery....................................................................................................................4
1.2 About solar pump station.......................................................................................................4
1.3 Safety instructions..................................................................................................................4
1.4 Station dimensions.................................................................................................................5
1.5 Specification of components.................................................................................................5
1.6 Technical Data.........................................................................................................................6
2. Mounting pump station ............................................................................................................6
3. Commissioning of station........................................................................................................7
3.1 Flushing and filling the solar system...................................................................................7
3.2 Flow check...............................................................................................................................8
3.3 Airstopp ....................................................................................................................................8
3.4 Electrical connection..............................................................................................................9
3.5 Flushing and filling unit (Spar part A06)............................................................................10
Manual of integrated controller of solar station.........................................................11
1. Safety information...................................................................................................................11
1.1 Description of symbols ........................................................................................................11
2. Overview ..................................................................................................................................11
2.1 Introduction of controller......................................................................................................11
2.2 Technical data .......................................................................................................................12
2.3 Terminal connection.............................................................................................................13
2.4 Menu Structure......................................................................................................................14
2.5 Menu description..................................................................................................................15
2.6 System description...............................................................................................................17
3. Controller functions and parameters setup ( User grade)...............................................18
3.1Set time/week/day/month/year............................................................................................18
3.2 tHET Timing heating.............................................................................................................18
3.3 CIRC DHW pump control function.....................................................................................22
4. Controller functions and parameters setup (engineer grade).........................................26

SR882 operation manual
~ 2 ~
4.1 Access main menu...............................................................................................................26
4.2 DT Temperature difference function..................................................................................26
4.3 TEMP Temperature..............................................................................................................27
4.3.1 EMOF Switch-on temperature of collector emergency function...............................28
4.3.2 EMON Switch-off temperature of collector emergency function...............................29
4.3.3 CMX Maximum limited collector temperature (collector cooling function)..............29
4.3.4 CMN low temperature protection of collector...............................................................30
4.3.5 CFR frost protection of collector.....................................................................................31
4.3.6 REC Tank re-cooling function .........................................................................................31
4.3.7 SMX1 Maximum temperature of tank 1.........................................................................32
4.4 PUMP Circuit pump speed adjust set...............................................................................32
4.4.1 DTS Standard temperature difference for circulation pump 1 (speed adjusting)...33
4.4.2 RIS Gain for circulation pump 1 (speed adjusting) .....................................................34
4.5 OHQM Thermal energy measuring...................................................................................34
4.5.1 FTYPE Flow counter type option....................................................................................35
4.5.2 FMAX Flow rate.................................................................................................................36
4.5.3 MEDT Type of heat transfer liquid..................................................................................36
4.5.4 MED% Concentration of heat transfer liquid................................................................37
4.6 INTV Pump interval function...............................................................................................37
4.6.1 ISTAR Turn-on time for pump interval running function.............................................38
4.6.2 IEND Turn-off time for pump interval running function...............................................38
4.6.3 ISTP Pump interval time..................................................................................................38
4.6.4 IRUN Pump running time.................................................................................................39
4.7 SFB Solid fuel boiler turn on/off.........................................................................................39
4.7.1 SFON Minimum turn-on temperature of tank...............................................................40
4.7.2 SFOF Maximum turn-off temperature of tank ..............................................................40
4.7.3 MAX3 Maximum turn-off temperature of solid fuel boiler...........................................40
4.7.4 MIN3 Minimum turn-on temperature of solid fuel boiler.............................................41
4.8 FUN Auxiliary function .........................................................................................................41
4.8.1 DVWG Anti legionnaires' function..................................................................................41
4.8.2 COOLTank cooling function............................................................................................42
4.8.3 AHO Auto thermostat function.........................................................................................43
4.9 OSDC SD card data save function....................................................................................44
4.9.1 OSDC card function switch-on and off..........................................................................45

SR882 operation manual
~ 3 ~
4.9.2 LOGI Data save intervals.................................................................................................45
4.10 UNIT Display unit oC and ℉switches ..........................................................................46
4.11 HND Manual control...........................................................................................................46
4.12 REST Recovery to factory set..........................................................................................47
4.13 PASS Password set...........................................................................................................47
5. Operation button function......................................................................................................49
5.1 Holiday function....................................................................................................................49
5.2 Manual heating .....................................................................................................................49
5.3 Temperature check...............................................................................................................50
6. Protection function..................................................................................................................51
6.1. Memory protection ..............................................................................................................51
6.2 Screen protection .................................................................................................................51
6.3 Circuit pump protection........................................................................................................51
7. Trouble shooting .....................................................................................................................51
7.1 Trouble protection.................................................................................................................51
7.2 Trouble checking...................................................................................................................52
8. Quality Guarantee...................................................................................................................54
9. Accessories..............................................................................................................................55

SR882 operation manual
~ 4 ~
Solar pump station installation and operation manual
1. Solar pump station with integrated controller
Integrated solar controller
Outstanding design
Safety assembly with safety valve and manometer
High-Quality casing for reduce heat loses
Flow rate check
1.1 Scope of delivery
1* solar pump station
1* integrated solar controller
1* flushing and filling unit (optional)
1* collector sensor PT1000
2* storage sensor NTC10K
1* wall mounting bracket
1* accessory bag(include 2 * screw and dowel ; 2 * strain relief)
1* manual
1.2 About solar pump station
This solar pump station is a preinstalled and leak-tested group of fitting for transferring heat
from collector to storage. It contains important fittings and safety devices for the operation of
a solar thermal system:
Ball valves on flow and return in combination with check valves to prevent gravity
circulation.
Airstopp for manual or automatic bleeding of the solar thermal system
Flow rate check for displaying the flow rate
Manometer for displaying the system pressure
Safety valve to prevent inadmissible overpressure
Flushing and filling unit (optional) for flushing, filling and emptying the solar thermal
system.
1.3 Safety instructions
The installation and commissioning of the solar station as well as the connection of
electrical components requires technical knowledge commensurate with a recognized
vocational qualification as a fitter for plumbing, heating and air conditioning technology, or

SR882 operation manual
~ 5 ~
a profession requiring a comparable level of knowledge. The following must be observed
during installation and commissioning:
The relevant regional and national regulations.
The technical and safety instructions of these instructions.
Warning: risk of scalding
There is danger of steam emission from safety valves. Therefore a discharge pipe must be
connected to the safety assembly, please observe the enclosed instructions regarding the
safety valve when doing this.
Attention: damage of solar pump station
The group of fittings must be installed with sufficient spacing to the collectors because
temperatures in the vicinity of the collectors can be very high. An intermediate vessel
may be necessary for installation in the attic.
It is imperative that you make sure the PTFE sealing elements of the solar pump
station do not come into contact with substances containing mineral oil. Mineral oil
products cause lasting damage to the material, whereby its sealant properties are lost.
If necessary, ask the manufacturer whether the solar fluid, fats or installation aids
contain mineral oils. We don’t assume liability nor provide warranty for damage to solar
station resulting from sealants damaged in this way.
1.4 Station dimensions
Height ( with insulation): 410mm
Width (with insulation): 350mm
Depth (with insulation): 165mm
Install height(centre): 1600mm
Distance axis/wall: 55mm
Pipe connections: 3/4’ IT (inner thread)
Connection for expansion vessel set:
3/4’ET, flat sealing
Outlet safety valve: 1/2 IT
1.5 Specification of components
1.5.1 Safety valve: 6bar
1.5.2 Manometer: 0-6bar
1.5.3 Non-return valve: opening pressure 200mm H2O height

SR882 operation manual
~ 6 ~
1.5.4 Sensor on the collector flow pipe: NTC10K, B=3950
1.5.5 Circuit pump: Wilo 15-6
1.5.6 Digital flow counter (alternative
mechanical flow counter)
1.5.7 Tank return connection (from tank):
3/4 IT
1.5.8 Tank flow connection (to tank): 3/4
IT
1.5.9 Airstopp for manual or automatic
bleeding of the solar thermal system
1.5.10 Sensor on the collector return
pipe: NTC10K, B=3950
1.5.11 Collector return pipe connection
(from collector): 3/4 IT
1.5.12 Integrated solar controller
Material:
Fitting: brass
Seals: PTFE
Insulation: EPP, λ= 0.041W/ (m.K)
1.6 Technical Data
Max. permitted pressure: 6bar
Max. permitted operating temperature:
120oC
Digital flow rate: 0.1-20 L/Min
Mechanical flow rate: 2-8 L/Min
2. Mounting pump station
Determine the mounting site of the station.
Take the station out of packing; Remove the front half of the insulation.
Hold the enclosed wall mounting bracket against the wall and mark the fastening holes,
drill holes and insert dowels.
Fasten the wall mounting bracket to the wall with the screws.
Push the station against the wall mounting bracket, the station catches and is then
attached to the wall.
1.5.1
1.5.2
1.5.6
1.5.7
1.5.11
1.5.10
1.5.3
1.5.4
1.5.5
1.5.9
1.5.12
1.5.8

SR882 operation manual
~ 7 ~
Connect the station to the solar thermal system.
Check the inlet pressure of the expansion vessel and if necessary, adjust it to the local
conditions, Pinlet(bar) = 1bar+∆ Th(m)*1/10 (∆Th=height difference between collector
and station).
Connect the electrical components of the solar station, mount the store and collector
sensor and connect them to the controller, plug the controller into the socket.
Tighten all union nuts and screw connections. And mount the front half of the insulation
to the station.
3. Commissioning of station
Attention: Risk of scalding!
In order to prevent the boiling of solar fluid in the collectors, the system should not be
flushed or filled during periods of strong sunshine.
Attention: Risk of frost!
Solar thermal system cannot be completely emptied after flushing. There is a danger of
frost damage if water is used for flushing. Only use solar fluid to flush and fill the solar
thermal system. Use water –propylene glycol mixture as solar fluid (Maximum 50%
propylene glycol).
3.1 Flushing and filling the solar system
Flushing and filling unit is the optional
component, it can be installed horizontally
at the lowest point of the solar circuit (see
figure). A filter must be installed between
the store and solar pump in order to
prevent the flushed-out scale from store
re-entering the solar circuit.
Flushing and filling steps:
Disconnect the expansion vessel from
the solar thermal system.
Connect the pressure hose of a flushing and filling station to the fill ball valve (1) of
flushing and filling unit.
Connect the flushing hose of a flushing and filling station to the drain ball valve (3) of

SR882 operation manual
~ 8 ~
flushing and filling unit.
Close the ball valve (2) in the centre of the flushing and filling unit.
Open the filling ball valve (1) and drain ball valve (3).
Flush the solar thermal system using the flushing and filling station for at least
15minutes to remove all air from the system.
During the flushing, bleed the solar thermal system several times at the airstopp until
the discharged solar fluid is free of air bubbles.
Close the drain ball valve(3) of flushing and filling unit, and continues run the pump and
increase the system pressure to approx.5 bar, system pressure can be read from the
manometer.
Close the filling ball valve (1) of the flushing and filling unit, and then close the filling
pump.
Check the manometer to see whether the system pressure reduces and eliminate leaks
where necessary.
Reconnect the expansion vessel to the solar thermal system.
3.2 Flow check
The flow counter is used for measurement and display of flow rate 1-20L/M, in order to
guarantee the flawless function of the measuring device the system must be flushed and
free from foreign substances.
3.3 Airstopp
After pump station is filled and commissioning, airstopp will automatically release air for
system, and it is possible to release air manually.
Factory default status of Airstopp is releasing air automatically.
Flow rate adjust
Scale of flow rate
Mechanical flow rate
counter 2-8L/min
Digital flow rate counter
0.1 -20L/min

SR882 operation manual
~ 9 ~
In the case that airstopp is in automatic status,
anti-clockwise turn the knob180oto switch the
status to manual air releasing. (See picture 1)
In the case that airstopp is in manual status,
clockwise turn the knob180oto switch the
status to automatic air releasing. (See picture 2)
Airstopp is used for releasing the air from system. The air
released from solar liquid will assemble at the top part of airstopp
(see picture 3), and released from airstopp. In order to take the
air from pipe to airstopp, minimum flow speed of 0.3m/s should
be ensured.
After air releasing, please check the system pressure, if need,
please increase the system pressure to the desired operation
pressure by filling and flush station.
Warning: high temperature scald!
During air releasing, temperature of released air and liquid maybe over 100oC.
3.4 Electrical connection
Warning: disconnect the controller from power supply before opening the housing!
The controller is already integrated in the station and ready to plug in. Pump, pipe
sensor and digital counter are already pre-connected with controller at factory. But
for connecting other wires, it needs to open the controller, doing follows below steps:
Switch off the system, disconnect plug from the
mains.
Remove the front half of the insulation.
Unscrew the cross-recessed screw 1 of the front
cover of controller and remove it by pulling it
downwards.
Connect the wires to controller, and doing reverse
steps to remount the front cover of controller and
insulation.
For further information on electrical connection of the controller, please see manual of
controller (2.3 Terminal layout and system description).
3
1
2

SR882 operation manual
~ 10 ~
3.5 Flushing and filling unit (Spar part A06)
Flushing and filling unit is a optional accessory part of system, it is not included in the
standard scope of delivery, please prepare separately
A06

SR882 operation manual
~ 11 ~
Manual of integrated controller of solar station
1. Safety information
We have carefully checked the text and figures of this manual and provided the best of our
knowledge and ideas, however inevitable errors maybe exist. Please note that we cannot
guarantee that this manual is given in the integrity of image and text, they are just some
examples, and they apply only to our own system. Incorrect, incomplete and erroneous
information and the resulting damage we do not take responsibility.
1.1 Description of symbols
Safety instruction:
The safety instruction in the manual is marked with a warning triangle. They
indicate measures, which can lead to personal injury and safety risks.
Operation steps: small triangle “►”is used to indicate operation step.
Notes: Contains important information about operation or function.
2. Overview
2.1 Introduction of controller
LCD display
3 relay outputs
6 sensor inputs
1 PWM outputs for speed control of pump
Data saved on SD card
RS485 remote control
Timing and temperature set point control function
Energy saved on/off operation model
Picture 1 Picture 2

SR882 operation manual
~ 12 ~
Picture 3 Picture 4
2.2 Technical data
Material of cases: ABS
Available ambient temperature: 0 ... 40oC
Dimensions: 188 x 138 x 43 mm
Mounting: on wall or in the electrical cases
Operation button: 6 operation buttons on panel
Communication port: SD card groove.
Power supply: 100 ... 240V ~, 50 ... 60 H z
Power consumption :<1W
Accuracy of temperature measuring : ±2oC
Range of collector temperature measuring: -10- 200oC
Range of tank or pipe temperature measuring: 0-110oC
Inputs: 1 x Pt1000 sensor (≤500oC) for collector (silicon cable≤280oC),
5 x NTC10K, B3950 sensor (≤ 135oC) for tank, (PVC cable ≤105oC),
1 x RS485 remote control connection
Outputs:1 PWM outputs(≤200W)
1 relays outputs ( each available power≤300W)
1 output for electrical booster (available power≤1500W)
Ambient temperature:-10-50oC
Water proof grade:IP40
Note: SD card isn’t included within the delivery scope of controller.

SR882 operation manual
~ 13 ~
2.3 Terminal connection
Before opening the terminal, please be sure to switch-off the power and pay
attention to the local electricity supply rules.
Input ports
Inputs T1:For PT1000 temperature sensor, used for measuring the temperature of collector.
Inputs T2~T6:for NTC10K,B=3950 temperature sensor, used for measuring the
temperature of storage or pipe.
VBus (485): for RS485 remote control connection.
Advice regarding the installation of temperature sensors:
1) Only original factory enclosed Pt1000 temperature sensors are approved for use with
the collector, it is equipped with 1.5meter silicon cable and suitable for all weather
conditions, the temperature sensor and cable are temperature resistant up to 280oC,
not necessary to distinguish the positive and negative polarity of the sensor connection.
2) Only original factory enclosed NTC10K,B=3950 temperature sensors are approved for
use with tank and pipe, it is equipped with 1.5meter PVC cable, and they are
temperature resistant up to 105oC, not necessary to distinguish the positive and
negative polarity of the sensor connection.
3) All sensor cables carry low voltage, and to avoid inductive effects, must not be laid
close to 230 volt or 400-volt cables (minimum separation of 100mm)
4) If external inductive effects are existed, e.g. from heavy current cables, overhead train
cables, transformer substations, radio and television devices, amateur radio stations,
microwave devices etc, then the cables to the sensors must be adequately shielded.
5) Sensor cables may be extended to a maximum length of ca. 100 meter, when cable’s
length is up to 50m, and then 0.75mm2 cable should be used. When cable’s length is

SR882 operation manual
~ 14 ~
up to 100m, and then 1.5mm2 cable should be used.
Output ports
Power terminal : L, N,GND
Input ports L, N is power connection terminal, please connect correctly.
is Ground line terminal.
Output P1:For solar circuit pump, also suitable for RMP control, semiconductor relay, max.
switching current 1A.
Output P2:Electromagnetic relay, its max. switching current 3.5A.
Output H1:For back-up electrical heater, electromagnetic relay, max. switching current
10A,
2.4 Menu Structure
Submenu:
Through submenu, user can set the parameter as desired value, please check it carefully.

SR882 operation manual
~ 15 ~
2.5 Menu description
Code
(Main
menu)
Code
(Submen
u)
Code
(Subme
nu)
Menu Description
DT
Temperature difference
TEMP
Set Temperature
EMOF
The maximum switch-off temperature of collector
EMON
The maximum switch-on temperature of collector
CMX
Maximum temperature of collector
(Collector cooling function)
CMN
Low temperature protection of collector
CFR
Frost protection of collector
REC
Tank re-cooling function
SMX1
Maximum temperature of tank
PUMP
Set parameters for pump speed adjust
nMIN
Speed controlling of circulation pump (RPM pump
controlling)
DTS
Standard temperature difference (for circulation pump
speed adjust)
RIS
Increase scale (circulation pump speed adjusting
parameter set)
OHQM
Thermal energy measuring
FTYPE
Select type of flow counter
FMAX
Flow rate
MEDT
Type of heat transfer liquid
MED%
Concentration of heat transfer liquid
INTV
Pump interval function
ISTAR
Switch-on time for pump interval function
IEND
Switch-off time for pump interval function
IRUN
Pump running time
ISTP
Pump interval time
SFB
Switch on/off of solid fuel boiler
SFON
Minimum switch-on temperature of tank
SFOF
Maximum switch-off temperature of tank

SR882 operation manual
~ 16 ~
MAX3
Maximum switch-off temperature of solid fuel boiler
MIN3
Minimum switch-on temperature of solid fuel boiler
FUN
Auxiliary functions
DVWG
Anti legionnaires' function
COOL
High temperature cooling function
AHO
Switch-on temperature for thermostat
AHF
Switch-on temperature for thermostat
OSDC
SD card function
LOGI
Data saving interval time (in minute)
NOCRD
FAT16
FAT32
No card in groove
EMS memory< 2G
EMS memory >2G
RTIME
Rest days for data saving ( in day)
FSYS
LOGG
System file error
Log possible
UNIT
Celsius and Fahrenheit temperature switch
HDN
Manual controlling
REST
Recovery to factory set
PASS
Password set

SR882 operation manual
~ 17 ~
2.6 System description
Note:
T3 is alternative sensor, when no sensor (T3) is installed on the top part of tank, controller
will use the signal of sensor T2 automatically to control the auxiliary heating or the
circulation pump.
1 collector array –1 storage tank –1 pump and auxiliary heating
Description:
The solar circuit pump (P1) is switched on as soon as the switch-on temperature difference
(△Ton) between the collector array (T1) and the storage tank (T2) is reached. If the
temperature difference between the collector array (T1) and storage tank (T2) drops below
the switch-off temperature difference (△Toff), or the temperature of storage tank (T3)
reaches the preset maximum storage temperature, then the solar circuit pump (P1) is
switched off.
Back-up heating by auxiliary boiler (detailed see paragraph 3.2):
Within the preset schedule of back-up heating, if the temperature T3 is below the preset
switch-on temperature, then the back-up heating(H1)is triggered, when T3 is heated to
the preset switch-off temperature, back-up heating H1 is ceased.
T1: Sensor on collector array
T2: Sensor on the bottom part of tank.
T3: Sensor on the top part of tank
(optional sensor)
T4: Sensor on hot water pipe, on solid
fuel boiler or for thermostat (alternative)
T5: Sensor on tank return pipe (for
measuring thermal energy)
T6: Sensor on tank flow pipe
P1: Solar circuit pump
P2: Hot water circuit pump, solid fuel boiler circuit pump, output for thermostat or output for
high temperature cooling (Note: this output can only used as one of above mentioned four
functions, depend on which function is activated)
H1: Output for back-up electrical heater

SR882 operation manual
~ 18 ~
3. Controller functions and parameters setup ( User grade)
3.1Set time/week/day/month/year
►Press “SET”button, “TIME”displays on the screen.
►Press “SET”button, hour area “00”blinks on the
screen.
►Press “+、-”button, to adjust hour
►Press “SET”button, minute area “00”blinks on
the screen.
►Press “+、-”button, to adjust minute
►Press “SET”button, week area “MO”blinks on
the screen.
►Press “+、-”button, to adjust week
►Press “SET”button, “day/month/year”area “year”
blinks on the screen.
►Press “+、-”button, to adjust year
►Press “SET”button, “day/month/year”area “month”
blinks on the screen.
►Press “+、-”button, to adjust month
►Press “SET”button, “day/month/year”area “day”blinks on the screen.
►Press “+、-”button, to adjust day
►Press “ESC”button, to exit program or wait for 20 second to exit automatically.
3.2 tHET Timing heating
Description:
Electrical heater, gas boiler or oil boiler can be integrated into solar system used as back-up
of system, and they can be triggered automatically at preset schedule by preset
temperature. Within a preset schedule, when the temperature (T3) of top part of tank
drops below the preset switching-on temperature of this function, back-up heating starts to
work, when T3 rises up to the preset turning off temperature, back-up heating is stopped.
Within 24 hours, three time sections can be set with this controller.
Factory set:
The first schedule: back-up heating function starts at 4:00 and ends at 5:00 am. Within
this time section, switch-on temperature is 40oC; switch-off temperature is 45oC.
CODE
WEEK
MO
Monday
TU
Tuesday
WE
Wednesday
TH
Thursday
FR
Friday
SA
Saturday
SU
Sunday

SR882 operation manual
~ 19 ~
The second schedule: from 10:00 to 10:00 am, it means there is no back-up heating in this
time.
The third schedule: back-up heating function starts at 17:00 and ends at 22:00 pm.
Within this time section, the switch-on temperature is 50oC; switch-off temperature is 55oC.
The switch-on temperature adjustable range: 10 oC ~ (OFF-2oC)
The switch-off temperature adjustable range: (ON+2 oC) ~ 80oC
If you want to shut off one timing heating, then you can set the turning on time and turning
off time with a same value ( for example, no this function during the second time section,
then you can set turning on/off time is 10:00 ~ 10:00)
When time is outside of the preset schedule, back-up heating doesn’t work automatically
even when the tank temperature reaches the switch –on temperature of heating.
Note:
When there is no sensor installed in the top part of tank (no T3 sensor), controller will
take the signal of T2 (sensor in bottom of tank) automatically to control this function.
The time in this controlled is 24 hours mode, when you set schedule, the switch-off
time of heating should be larger than the switch-on time. For example: if you set the
switch-on time of heating is at 17:00, but switch-off time of heating is 6:00, then this
setting doesn’t take effect, that means within this time section, heating function doesn’t
work. The correct set is like flowing: it should be divided into two time sections, one
time section is from 17:00 to 23:59, the other time section is from 00:00 to 06:00.
Setup steps: under standby status.
►Press “SET” button, then press “+”button, “tHET”menu displays on the screen.
►Repress “SET” button, to access “tHET”program,
►Repress “SET” button, to access parameter setting
window of tHET program, “tH 1o 04:00” displays on
screen, “04” of hour time blinks on screen, the
switch-on time and temperature for the first schedule
of heating function can be
►Press “+”“-” button to adjust hour of time
►Repress “SET” button again, “00” of minute time blinks on screen
Table of contents
Popular Water System manuals by other brands

ENERGY KINETICS
ENERGY KINETICS EK-Pak Owners and installation manual

Judo
Judo BST-CA 15 Installation and operating instructions