Sigma Myriad LC1 Series User manual

VISIT OUR WEBSITE SIGMACONTROLS.COM
MYRIAD ‘LC1’ LEVEL CONTROLLER
INSTRUCTION MANUAL
MYR LC1 MANUAL 062114

TABLE OF CONTENTS
INTRODUCTION………………………………………… 3
Ordering Inf rmati n
Specificati ns
Features
Dimensi ns
WIRING…………………………………………………… 7
Dwg # 02-131
Anal g Input
Anal g Output
Digital Input
Digital Output
PROGRAMMING AND INITIAL SETUP……………... 8
Input Range Selecti n
Terminal Bl ck Detail
Initial Setup & Pr gramming
Overview/Key Descripti n
TROUBLESHOOTING & MAINTENANCE …………..
14
APPENDIX ‘A’ …………………………………………… 1
WARRANTY……………………………………………… 17

INTRODUCTION:
The Sigma Myriad LC1 (Level C ntr ller) is a micr pr cess r based, state f the art, level c ntr ller
ffering unmatched perf rmance and full user c nfigurability.
The LC1 is used with a primary level measuring device wh se utput signal is c mpatible with c mm n
anal g utputs 4/20MA, 0-5VDC, 1-5VDC, and 0-10VDC.
Level indicati n is displayed in b th numeric and graphic f rmat n the LC1’s graphic LCD display al ng
with the current status f the unit’s 4 digital utputs.
All aspects f the unit are user c nfigurable thr ugh the ‘plain English’ menus and c mbinati ns f the
5 user data key push butt ns.
Available in 2 styles f m unting, ¼ DIN (4” x 4” n minal) and wall m unted Nema 4X encl sures, the
Myriad LC1 is suitable f r installati n in all industrial envir nments.
ORDERING INFORMATION:
1/4 DIN Case Sigma Myriad-LC1
Wall M unt Nema 4X Sigma Myriad-LC1-N4X
SPECIFICATIONS:
ANALOG INPUT (1 ea.)
Anal g, 4/20MA, 0-5V, 1-5V, 0-10VDC, is lated with c mm n negative, +-0.1% accuracy.
DIGITAL INPUTS (2 ea.)
Digital 10-30V AC r DC, 120 r 240 VAC (requires external resist r).
ANALOG OUTPUT: (1 ea.)
Anal g, with c mm n negative 0-20MA, 4/20MA, 0-5V, 0-10V (v ltage utput requires a
resist r).
DIGITAL OUTPUTS:
Opt is lated, s lid state, pen c llect r, 100MA 30VDC max.
RELAY OUTPUTS: (2 ea.)
SPDT, F rm ‘C’ 5A Relay
DISPLAY:
LCD, 128 X 32 pixel bitmapped graphic display
LOOP POWER:
24VDC regulated utput, 100MA max.

5 USER KEYS:
Up, D wn, Left, Right, Enter
ACCURACY:
0.1% f calibrated span
LOCKOUT:
User passw rd, user c nfigurable
LINEARIZER
20 p int pr grammable f r n n-linear inputs
INPUT IMPEDANCE:
V ltage 100K, current 100 OHMS
POWER:
120VAC (230VAC available)
ENVIRONMENTAL:
Operating, 0-65° C
St rage, -40° -80° C
R.H., 0-90% n n c ndensing
ENCLOSURE:
¼ DIN, ABS plastic 96 X 96 X 150MM
FRONT PANEL:
Gasketed Nema 4X
ACCESS:
Chassis & b ards rem ve fr m fr nt f case.
TERMINAL STRIP:
(40) ‘Pluggable’ f r ease f wiring 28 – 16 AWG
CONNECTIONS:
Rem vable screw terminal bl cks 28 – 16 AWG wire.
CONTROL OUTPUTS:
2 relay utputs, user pr grammable, SPDT F rm ‘C’ relays 5 AMP.
4 digital utputs, repeat digital inputs.
OUTPUT ANNUNCIATION:
On b ard piez buzzer

PROGRAMMING:
Menu based, all parameters and setp ints are user c nfigurable via menu pr mpts and user keys.
The pre-c nfigured screens and ‘pull d wn’ sub menus with English pr mpts assures rapid setup
and c mmissi ning.
1 YEAR WARRANTY
OPTIONS:
Include relay utput, real time cl ck, expansi n cards.
M.V. NET:
Netw rk all ws multiple units t be c nnected t gether f r distributed applicati ns, rem te
m nit ring SCADA applicati ns.
EXPANSION CARDS:
Significant expansi n is p ssible via additi nal c ntr l b ards and ‘MV’ netw rking. (C nsult
fact ry f r details.)
FEATURES:
Micr pr cess r Based
Graphic LCD Display
5 Functi n Keys
10 P int Linearizati n
Is lated 24VDC Sens r P wer
4/20MA, 1-5V, 0-5V, 0-10VDC Input
1 Anal g Input
1 Anal g Output
4 Digital Inputs
4 Digital Outputs
2 F rm ‘C’ Relay Outputs
Fully User Pr grammable in English
2 Ea. RS485 P rts (Pr gramming and SCADA)

WIRING DETAIL
Input/Output see Dwg # 02-131
CAUTION
!
All electrical wiring must be in accordance with all local state and
national codes that apply.
Do not exceed the rated current of the D.C. power supply (100MA)
or the form ’C’ relay outputs ( A/240VAC resistive).
WARNING
Hazardous voltages are present within the enclosure.
Installation or service should only be carried out by trained
personnel.


PROGRAMMING & SETUP
The Myriad LC1 utilizes a ‘plain English’ menu driven setup screens which are intuitive and easily
underst d.
Fr m the default screen (Fig. 1), push the ‘Enter’ butt n t enter the passw rd pr tected menus.
Default
Fig. 1
ENTER
Enter user selected passw rd (fact ry default is zer ) with the up and d wn keys, then with and
arr w butt ns, m ve curs r t ‘next’
Press ‘ENTER’ t access menu.
NOTE: Selecting ‘VIEW’ with the and and then pressing ‘ENTER’ will all w the user t
step thr ugh all LC1 settings with ut having the ability t change any parameter.
Parameter changes may nly be carried ut after entering the user selected passw rd as described ab ve.
INPUT RANGE SELECTION
With the ‘SCALE’ selecti n highlighted by the curs r, press ‘ENTER’ t access the input scale menu.
Pr cess Value
Engineering
Units
Relay
Status
Vertical Bar
CPU Status

Use the Up/D wn arr w butt ns t select the desired anal g input range. NOTE: INPUT TYPE MUST
BE CO-ORDINATED WITH INPUT SELECTOR SWITCH LOCATED ON THE BOTTOM OF
THE CIRCUIT BOARD (See Appendix ‘A’).
NOTE: If the application is linear between minimum input signal and maximum input signal, i.e.
“2 point”, then scroll the cursor to ‘NEXT’ and press ‘ENTER’ to continue the scaling process.
Note on non linear inputs
The Myriad ffers a 20 p int linearizer which all ws the user t cust mize the indicated display f r 20
p ints f input signal. This feature is ften used t read v lume in a n n-linear vessel such as a h riz ntal
tank with d med end caps. a “strapping table” must be created t all w the display t be linear with the
resultant n n-linear input signal.
If the user required a n n-linear display, scr ll the curs r t “# OF POINTS” and use the arr ws t
select the number f calibrati n p ints required, then select ‘NEXT’ and press ‘ENTER’ t c ntinue.
DECIMAL POINT SELECTOR SCREEN
The curs r will be p siti ned ver the decimal c unt wind w, use the Up/D wn arr w butt ns t
raise r l wer the unit number t the left f the decimal p int. (The example sh wn in this wind w will
change with y ur selecti n.)
Use the butt ns t m ve the curs r t the number behind the decimal p int and the
Up/D wn butt ns t change this selecti n. Once again the example will change t c nfirm y ur
selecti n.
Use the butt ns t highlight the ‘NEXT’ selecti n and press ‘ENTER’ t access the Input
Scale Screen.
INPUT SCALING TO ENGINEERING UNITS

NOTE: This screen sets what the Myriad LC1 displays in its ‘default screen’ f r the selected input.
The example sh wn ab ve will display 0.0 units when the input is 4.00 MA. B th the input and the
display at that input can be changed f r different requirements.
A) With the curs r selecting ‘INPUT = 4.00’ use the butt ns t change the input value f r the
required displayed value.
B) Use the butt ns t m ve the curs r t the ‘display’ value and the Up/D wn butt ns t change
the desired display f r the previ usly selected input. Once c mplete, scr ll t ‘SAVE’, press
‘ENTER’ t access ‘INPUT SCALE 2’ screen.
F ll w the steps utlined ab ve t set the values f ‘input’ and ‘display’ f r input Scale 2.
When c mplete with scale 2, scr ll the curs r t the ‘DONE’ p siti n and press ‘ENTER’ t m ve t the
“ENGINEERING UNITS” selecti n screen.
ENGINEERING UNITS SELECTION:
When ‘Scale Menu’ is c mplete the ‘INPUT TEXT” menu is the last menu in the scaling pr cess.
This screen all ws the selecti n f several engineering units. With the curs r n the default value as
sh wn, press the Up/D wn butt ns t select between ‘FEET OF WATER’
‘PSI’
‘GALLONS’
‘LITERS’
‘UNITS’
Use the ↑ ↓ keys t select the desired engineering units then with the → ← keys, highlight ‘NEXT’ and
press ‘ENTER’ t access the “display filter” screen.
DISPLAY FILTER SCREEN

Use the ↑ ↓ keys t change the am unt f filtering applied t the input signal. ‘O’ is n filter and ‘10’ is
high filter.
ANALOG OUTPUT PROGRAMMING
Fr m Menu 1 select ‘AOUT’ by highlighting with the curs r as previ usly described. Once selected
press ‘ENTER’ t access the anal g utput c nfigurati n screen.
Using the butt ns as described previ usly, select and adjust the values required f r the anal g utput.
B th the utput value and the display value f r that utput can be selected. When c mplete, select
‘NEXT’ and press ‘ENTER’.
This will bring up the scaling wind w f r anal g utput P int 2, which is set as bef re. When c mplete,
scr ll t ‘DONE’ and press ‘ENTER’ t return t Menu 1.
DIGITAL OUTPUT PROGRAMMING
The Myriad LC1 has 2 relay utputs, which can be c nfigured t ‘SET’ (turn n) and ‘RESET’ (turn ff)
at a user defined value f the input. Fr m Menu 1 select ‘OUTPUTS’ and press ‘ENTER’.
Using the butt ns scr ll t the value at which the utput ‘SETS’ r turns n, with this value highlighted,
use the Up/D wn butt ns t enter a value f input t activate the utput. Scr ll d wn t the
‘RESET’ p int and again change this value t input value, which will turn the digital OUTPUT 1 ff.
NOTE: The internal HORN will sound when the output setpoint is reached. To prevent the horn
from sounding, highlight the ‘Y’ symbol adjacent to the horn symbol and use the Up/Down buttons

to change the value to ‘N’ (NO). This will prevent the horn from sounding when the setpoint is
reached.
Once all values are selected, scr ll t ’NEXT’ press ‘ENTER’ t m ve t the #2 setp int screen and
pr ceed as described ab ve.
When b th setp ints are c nfigured, scr ll t ‘EXIT’ and press ‘ENTER’ t return t the ‘Main Menu’.
Fr m Menu 1 scr ll t ‘DIN’ and press ‘ENTER’ t access the Digital Input/Output pr gramming.
NOTE: The LC1 ffers the user the ability t select 2 digital inputs DI 1, DI 2 which are “mirr red” by
the digital utputs, i.e. when a digital input ccurs at the selected ‘DI’ then the pp site ‘DO’ will bec me
active. The nly pr grammability ffered in this screen is the ability t invert the utput functi n i.e.
when the DI is ‘ON’ the DO may be selected t be ‘ON’ r ‘OFF’.
With the curs r ver the ‘Y’ r ‘N’ p siti n use the Up/D wn arr ws t select the desired
functi n, scr ll t ‘NEXT’ and press ‘ENTER’ t m ve the DI 2 screen. Repeat the steps described
ab ve, scr ll t ‘EXIT’ and press ‘ENTER’ t return t the default ‘MAIN’ screen.
MENU 2 ‘PEAKS’
The ‘PEAKS’ feature f the Myriad LC1 rec rds the highest and l west pr cess values that have ccurred
since the last ‘CLR’ functi n.
A sec nd pr gramming menu can be accessed fr m MENU 1 by selecting ‘NEXT’ and pressing
‘ENTER’. This m ves the user t MENU 2.
With the curs r highlighting ‘PEAKS’ press the ‘ENTER’ butt n t review the PEAK & VALLEY
(highest and l west) values that the Myriad LC1 has seen since last reset.

Select the ‘CLR’ t reset these values t the current pr cess value and ‘EXIT’ and ‘ENTER’ t return t
the main screen.
MENU 2 ‘PASSWORD’
All access t the pr grammable functi ns are passw rd pr tected. T change the unit’s access passw rd,
Select the ‘PASSWORD’ bl ck in menu 2, press ‘ENTER’ and using the Up/D wn butt ns, enter a new
numerical passw rd.
Scr ll t ‘EXIT’ t return t the main screen.
CAUTION: ENSURE THAT A RECORD IS KEPT OF THE PROGRAMMED PASSWORD.
ACCESS IS RESTRICTED TO ALL PROGRAMMABLE PARAMETERS WITHOUT THE
CORRECT PASSWORD.
MENU 2 ‘DIAGNOSTICS’ (DIAG)
By m ving the curs r t the ‘DIAG’ menu and pressing ‘ENTER’ a diagn stic screen will be activated.
This screen sh ws the status f the anal g input/anal g utput ‘raw’ values and the current status f the
digital utputs. An active digital utput is sh wn by a rectangular bl ck r bl cks. The utput is active
when the bl ck is present. The m del number (e.g. LC1) is sh wn in the left hand l wer c rner and the
s ftware revisi n level is sh wn in the right hand l wer c rner.
Press ‘ENTER’ t return t ‘MENU 2’.

MAINTENANCE AND TROUBLE SHOOTING
MAINTENANCE:
The Myriad LC1 is a digital s lid-state device which requires n peri dic maintenance.
Occasi nal physical checks f the unit sh uld be carried ut f r physical and mechanical security f
m unting, terminal bl cks, and electrical wiring.
TROUBLE SHOOTING:
UNIT ‘LOCKS UP’ – Recycle p wer t the unit by rem ving AC p wer, waiting 10 sec nds and
rec nnecting p wer.
.
LCD display g es dim r c ntrast is p r. Rem ve p wer fr m the unit, release the 2 rear m unting
screws and slide the unit f rward in its case appr ximately 1 inch. On the left side f the circuit
b ard is an adjustable p tenti meter. With a small screwdriver adjust this “p t” t all w alter the
c ntrast t the desired am unt. Return the unit t its n rmal p siti n and secure the rear screws.
DISPLAY REMAINS AT ZERO OR SHOWS NO CHANGE -- If the display remains at zer r
sh ws n change but the pr cess is changing, check f r D.C. v ltage n the l p. With 2 wire
(4/20MA) instruments check with a D.C. v ltmeter at the level instrument, by disc nnecting the level
instrument fr m its 2 wires and measuring acr ss these 2 wires with a D.C. v ltmeter f r the presence
f 24VDC.
If D.C. v ltage is present, rec nnect the negative wire f the supply and insert a milliamp meter
between the p sitive wires. The l p sh uld pr vide a signal between 4 and 20 MA. If n current is
present r Y current exceeds 20MA c nsult the level instrument supplier.
If D.C. v ltage is n t present check the user supplied p wer supply r if using the Myriad supply
measure acr ss terminals 24VDC and A/C. If n 24VDC is present c nsult fact ry. If 24VDC is
present check field wiring between the Myriad and the field device and recheck ‘SCALE’ functi ns t
insure c rrect setup.
NOTE: This should be done by using the user provided circuit breaker or fuse,
not by removing the power wires at the terminal block. Serious injury or death
can occur if contact is made with the incoming ac power.
WARNING

APPENDIX ‘A’
SWITCH SELECTION OF ANALOG INPUT RANGES (Fact ry default 4/20MA).
The range dip switches are l cated n the b tt m f the main circuit b ard. Disc nnect p wer, rem ve
tw rear screws, rem ve terminal strips and slide the entire unit ut f its case. Turn the unit upside d wn
t l cate the range dip switches.
SW1 SW2 INPUT 4 DESCRIPTION
0 0
AIn4 range = 5V
0 1 AIn4 range = 10V
1 0
AIn4 range = 20mA
1 1 N t Used
SW3 SW4 DESCRIPTION
0 0 AIn2 range = 5V
0 1 AIn2 range = 10V
1 0 AIn2 range = 20mA
1 1 N t Used
SW SW6 DESCRIPTION
0 0 AIn3 range = 5V
0 1 AIn3 range = 10V
1 0 AIn3 range = 20mA
1 1 N t Used
SW7 SW8 DESCRIPTION
0 0 AIn1 range = 5V
0 1 AIn1 range = 10V
1 0 AIn1 range = 20mA
1 1 N t Used
ON
1
2
3
4
5
6
7
8
EXAMPLE ONLY

SIGMA MYRIAD LC1 & LC2 PROGRAMMING RECORD SHEET
Model Number: ________________ Serial Number: _________________
Vers: ________________
assword: ___________________
• Scale:
Input Type ______________
Input Points _____________
Decimal Point ___________
Input Scale 1:
Input = _____________
Display = ___________
Input Scale 2:
Input = _____________
Display = ___________
Engineering Units _________
Display Filter # ___________
• Setpoints:
Output 1 Setpoints
Set _____________
Reset ____________
L 1
& L 2
Output 2 Setpoints
Set _______________
Reset _____________
Output 3 Setpoints
Set _______________
Reset _____________
L 2 Only
Output 4 Setpoints
Set _______________
Reset _____________
• Analog Output Scale 1:
Display = ___________
Output = ___________
• Analog Output Scale 2:
Display = ___________
Output = ___________
• Setup:
Trend Speed __________

All Sigma Controls, Inc. products are warranted to be free from
defective materials and workmanship for one (1) year from date of
shipment. Sigma reserves the right to repair or replace at its
option any product found to be defective. In no event shall Sigma
Controls, Inc. be liable for any consequential, incidental, or
special damages and the limit of its liability shall not exceed the
purchase price of the supplied equipment.
*****IM PORTANT*****
SENSO RS AND CABLE THAT H AVE BEE N USED IN W ASTE W ATER
OR HAZARDO US LIQUIDS M UST BE THOROUG HLY CLEANED
BEFORE RETURNING. UNITS RETURNED UNCLEANED W ILL BE
CONSIDERED UNREPAIRABLE AND RETURNED TO SENDER OR
DISCARDED. NOTE: DO NOT SUBM ERG E UNITS FO R CLEANING
W ITH CABLE CUT OR REMOVED. TH IS W ILL ALLOW CLEANING
FLUID TO ENTER HOUSING, DAMAG ING ELECTRONICS AND
VOIDING THE W ARRANTY.
RETURN FOR REPAIR POLICY (WARRANTY/NON-WARRANTY
REPAIR)
Return status can be determined upon factory inspection of returned
equipment.
A completed Return Authorization form must accompany all items
returned for repair.
Repairs will be evaluated as quickly as possible. Cost for
non-
warranty repairs will be provided before repairs are
initiated and repairs will be completed only after approval
by customer.
217 S. Fifth Street, Perkasie, PA 18944 H: 215
-
257
-
3412 FAX: 215
-
257
-
3416
WARRANTY