20
Modbus
address
Variable description
Type
Read /Write
U.M.
Min
value
Max
value
Function
Di
ital variables
1Boiler CH Enable/Re
uestDR/W- 01
2Boiler DHW Enable DR/W -0 1
3Boiler Water Fillin
Function DR/W -0 1
32 Boiler CH Mode DR -0 1
33 Boiler DHW Mode DR -0 1
34 Boiler Flame Status DR -0 1
35 Boiler Alarm Status DR -0 1
Analo
variables
1Boiler CH Primary Setpoint A R/W 0,1°C 20,0 80,0
2Boiler DHW Primary Setpoint A R/W 0,1°C 20,0 80,0
3Boiler DHW Setpoint A R/W 0,1°C 10,0 80,0
4Outside Temperature MB A R/W 0,1°C-55,0 95,0
5Boiler CH Curve Slope A R/W 0,13,0 40,0
6Boiler CH Curve Displacement A R/W 0,1-5,05,0
64 Boiler DHW Water Tem
eratureAR0,1°C 0,0 100,0
65 Boiler Primar
Water Tem
eratureAR0,1°C 0,0 100,0
66 Boiler Return Water Tem
eratureAR0,1°C 0,0 100,0
67 Boiler Flue Gas Tem
eratureAR0,1°C 0,0 200,0
68 Boiler Relative Modulation Level AR0,1% 0,0 100,0
69 Boiler Primar
Water Pressure AR0,1 bar 0,06,0
70 Boiler Outside TemperatureAR0,1°C -100,0 100,0
Inte
er variables
129Boiler Current MinuteI
R/W -0 59
130Boiler Current Hour I R/W -0 23
131Boiler Current Da
of the Week I R/W -1= Lun 7 = Dom
132Boiler Current Da
of the MonthI
R/W -1 31
133Boiler Current MonthI
R/W -1 12
134Boiler Current Year I R/W - 2000 2200
192Boiler Alarm Code IR -0100
193Boiler Slave 1 Alarm Code IR -0100
194Boiler Slave 2 Alarm Code IR -0100
195Boiler Slave 3 Alarm Code IR -0100
196Boiler Slave 4 Alarm Code IR -0100
197Boiler Slave 5 Alarm Code IR -0100
198Boiler Slave 6 Alarm Code IR -0100
199Boiler Slave 7 Alarm Code IR -0100
200Boiler Combustion Parameter
Par1
IR -0199
Request CH zone 1
Enable DHW preparation
Not used
State CH zone 1
State preparation DHW
State presence flame
State presence alarm
Setpoint CH zone 1.
If you receive a value out of range
so the value isn’t received and
the boiler temperature control is
maintained of fixed point or a
temperature curve.
Setpoint CH during ACS preparation
(for PAR 66 installer parameters)
If you receive a value out of range
the value isn’t received and it is used
the boiler value regulation .
Setpoint ACS.
If you receive a value out of range
the value isn’t received and it is used
the boiler value regulation.
External value of temperature by MobBus.
If you receive a value out of range
the value isn’t received. In case of
conflict the boiler will give priority to the value
of the probe connected to it.
Slope of heating curve of zone 1
(it is used instead of the curve set in the boiler).
If you receive a value out of range
the value isn’t received and it is used
the boiler heating curve.
If you receive a value out of range
the value isn’t received and it is used
the boiler heating curve.
Shift value of room zone 1 set
(it is used instead of the shift set in the boiler).
DHW temperature sensor
CH temperature sensor (Delivery)
CH temperature sensor (Return)
Smoke temperature sensor
Modulation level: (0%= minimum boiler power
100%= maximum boiler power)
Pressure value water CH
Outside temperature read from the boiler
through the probe connected to it
Not used
Not used
Not used
Not used
Not used
Not used
Numeric code shown during boiler error
(If Master is in cascade)
Numeric code shown during slave 01 error
Numeric code shown during slave 02 error
Numeric code shown during slave 03 error
Numeric code shown during slave 04 error
Numeric code shown during slave 05 error
Numeric code shown during slave 06 error
Numeric code shown during slave 07 error
PAR 1 value
PAR 2 value
MODBUS BOILER VARIABLES LIST