Mechanically installing the 2-Stage Station
After all electrical connections have been made, install the 2-Stage Station IAM into a electrical box (not
supplied) behind the Manual Station using Figure 4 as a reference. Refer to the 2099-Series Non-Coded
Fire Alarm Stations Installation and Operating Instructions (574-656) for information on other mounting
configurations. Mount the 2-Stage Station IAM to the electrical box as follows:
For surface mounting, use a 2975-9178 red steel back box or a 2975-9022 aluminum back box. Do not
substitute a box with a depth less than 2-3/16 inches (5.55 centimeters).
For semi-flush mounting, use a standard 4-inch (10.16 centimeters) square back box with a minimum depth
of 2-1/8 inches (5.39 centimeters). Fit the back box with a 3/4 inch (1.9 centimeters) deep single gang
switch cover set flush (DO NOT RECESS) or protruding 1/16 inch (.16 centimeter) from the wall surface.
1. Install the 2-Stage Station IAM inside the electrical box in a position that allows the manual station
adequate room to be mounted onto the electrical box. The attached field wiring holds the 2-Stage
Station IAM in place inside the electrical box.
2. Secure the manual station to the back box.
Figure 4. 2-Stage Station IAM Back Box Installation
4099-9801C IDNet2-Stage Station IAM
Installation Instructions
574-179
Rev. D
574-179
Rev. D
2000 Simplex Time Recorder Co., Westminster, MA 01441-0001 USA
2000 Simplex International Time Equipment Co., Ltd., Mississauga, Ontario L4V 1H3 Canada.
All specifications and other information shown were current as of publication, and are subject to change without notice.
IDNetis a trademark of Simplex Time Recorder Company.
Suffix “C” following an 8-digit Product ID number denotes ULC-listed product.
IAM Assembly
Label
DIP Switch
(Under Re-sealable Label)
Terminal
Front View Rear View
LED
Note: The LED flashes approximately once every three
seconds to indicate valid communications with the FACP.
Cautions and Warnings
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED. Upon unpacking
your Simplex product, inspect the contents of the carton for shipping damage. If damage is apparent,
immediately file a claim with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any internal adjustments or repairs.
Servicing should be performed by qualified Simplex Representatives.
STATIC HAZARD - Static electricity can damage components. Ground yourself before opening or
installing components.
Introduction
The 4099-9801C 2-Stage Station Individual Addressable Module (IAM) provides addressability to
pre-signal type hardwired stations. The four device states (NORMAL, OPEN, CURRENT-LIMITED
and SHORT) are communicated to the 4010 Fire Alarm Control Panel (FACP) via the IDNetchannel.
Contacts for both General Alarm and Pre-Signal Alarm are supervised by the IAM. The IDNet channel
provides the communication link between the IAM and the 4010 FACP and powers the entire IAM circuitry
.
Installation
2-Stage Station IAM installation consists of
the following:
• Setting the 2-Stage Station IAMs address
• Making electrical connections to the 2-Stage
Station IAM and to the IDNet channel
• Mechanically installing the 2-Stage Station IAM
Figure 1. 2-Stage Station IAM Installation
firealarmresources.com
Making Electrical Connections to the 2-Stage Station IAM
The IDNet channel connects to the 2-Stage Station IAM via terminals 1 and 2. The manual station connects
to the 2-Stage Station IAM via terminals 3 and 4. Terminal connections are illustrated in Figure 3.
CAUTION: Do not loop wire under terminals. Break wire runs to provide supervision.
6
5
4
3
2
1
IDNet IDNet to
next device
1.8 K 1/2 W
733-984
(4081-9005)
2-STAGE
STATION
IAM
PRE-SIGNAL STATION
TYPE 2099-9107C, -9108C, -9759C
-
+
-
+
4.7 K 1/2 W
733-896
(4081-9003)
Notes:
1. When connecting two wires to one terminal, position one wire on each side of the terminal screw.
Maximum allowable run from 4010 FACP to farthest device not to exceed 2500 feet. Maximum
total wire (including all T-Taps) from 4010 FACP is 10000 feet. IDNet wiring is supervised and
power-limited.
2. Maximum wire length is 500 feet, #18 AWG.
3. Refer to Field Wiring Diagram 842-073 for further information. Refer to 4010 panel label 526-444
for appropriate revision of the Field Wiring Diagram to be used.
Figure 3. 2-Stage Station IAM Connections
32
Setting the 2-Stage Station IAMs Address
Each 2-Stage Station IAM has a unique address (1 through 250). The address of the IAM is set by an eight
position dip switch (Figure 1), DIP switch position 1 is the least significant bit (LSB) and position 8 is the most
significant bit (MSB). Set the IAMs address using Figure 2 as reference. Use a small screwdriver or pen to set
the switches. The device address for the 2-Stage Station IAM should be written on the re-sealable label; this
information provides an aid in troubleshooting the system.
Note: DIP switch in “1”position is “ON”while DIP switch in “0”position is “OFF”.
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000 0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240
1000 1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241
0100 2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242
1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243
0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244
1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245
0110 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
1110 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247
0001 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
1001 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249
0101 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
1101 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235
0011 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236
1011 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237
0111 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238
15 31 47 63 79 95 111 127 143 159 175 191 207 223 239
LSB MSB
12345678
1111
DIP SWITCHES 5 THRU 8
ON
OFF 1 = ON 0 = OFF
251
252
253
254
255
DIPSWITCH IS SHOWN SET AT ADDRESS 7.
Figure 2. 2-Stage Station IAM Address Chart
Configure the 2-Stage Station IAM to the 4010 panel using the 4010 Fire Alarm – PC Programmer Installation
and Programming Instructions (574-187) and 4010 Fire Alarm – Front Panel Installing, Operating, and
Programming Instructions (574-052). Refer to 4010 panel label 526-444 for appropriate revision of the
instructions to be used.
firealarmresources.com

Other Simplex Fire Alarm manuals

Simplex MINIPLEX 4100ES Series User manual

Simplex

Simplex MINIPLEX 4100ES Series User manual

Simplex 4099-9032 User manual

Simplex

Simplex 4099-9032 User manual

Simplex SafeLINC 4020 User manual

Simplex

Simplex SafeLINC 4020 User manual

Simplex 4007ES Panels User manual

Simplex

Simplex 4007ES Panels User manual

Simplex 2004 Series User manual

Simplex

Simplex 2004 Series User manual

Simplex 49SVC-CWFIRE User manual

Simplex

Simplex 49SVC-CWFIRE User manual

Simplex 4098 Instructions for use

Simplex

Simplex 4098 Instructions for use

Simplex SafeLINC 4100U User manual

Simplex

Simplex SafeLINC 4100U User manual

Simplex SafeLINC 4100 Instruction Manual

Simplex

Simplex SafeLINC 4100 Instruction Manual

Simplex SafeLINC 4020 Quick guide

Simplex

Simplex SafeLINC 4020 Quick guide

Simplex 4010 User manual

Simplex

Simplex 4010 User manual

Simplex SafeLINC 4100U User manual

Simplex

Simplex SafeLINC 4100U User manual

Simplex InfoAlarm 4100U User manual

Simplex

Simplex InfoAlarm 4100U User manual

Simplex 4010ES User manual

Simplex

Simplex 4010ES User manual

Simplex SafeLINC 4100 User manual

Simplex

Simplex SafeLINC 4100 User manual

Simplex 4007ES Panels Guide

Simplex

Simplex 4007ES Panels Guide

Simplex 4100-1265 User manual

Simplex

Simplex 4100-1265 User manual

Simplex 4010 User manual

Simplex

Simplex 4010 User manual

Simplex SafeLINC 4100U User guide

Simplex

Simplex SafeLINC 4100U User guide

Simplex 4100ES-S1 Maintenance and service guide

Simplex

Simplex 4100ES-S1 Maintenance and service guide

Simplex 2606-9101 Series User manual

Simplex

Simplex 2606-9101 Series User manual

Simplex SafeLINC 4100 User manual

Simplex

Simplex SafeLINC 4100 User manual

Simplex SafeLINC 4100 User manual

Simplex

Simplex SafeLINC 4100 User manual

Simplex 4002 User manual

Simplex

Simplex 4002 User manual

Popular Fire Alarm manuals by other brands

GST DI-9204 Installation

GST

GST DI-9204 Installation

Panasonic MEW01091 operating instructions

Panasonic

Panasonic MEW01091 operating instructions

Siemens MH-5 Series Installation instructions manual

Siemens

Siemens MH-5 Series Installation instructions manual

Mircom MPS-800MP Series manual

Mircom

Mircom MPS-800MP Series manual

E2S BExCP3D-PB instruction manual

E2S

E2S BExCP3D-PB instruction manual

Mircom MPS-800 Series manual

Mircom

Mircom MPS-800 Series manual

Ampac Warning Sign 4210-011 installation guide

Ampac

Ampac Warning Sign 4210-011 installation guide

Kentec Electronics Sigma A-CP Installation and operation manual

Kentec Electronics

Kentec Electronics Sigma A-CP Installation and operation manual

Honeywell SILENT KNIGHT 5860 Product installation document

Honeywell

Honeywell SILENT KNIGHT 5860 Product installation document

AVOTEC DOA V installation manual

AVOTEC

AVOTEC DOA V installation manual

Cooper Notification Wheelock MPS Series installation instructions

Cooper Notification

Cooper Notification Wheelock MPS Series installation instructions

Wheelock MB Series installation instructions

Wheelock

Wheelock MB Series installation instructions

Radionics D7024 operating instructions

Radionics

Radionics D7024 operating instructions

Notifier UniNet 2000 Simplex 4010 NION Installation and operation manual

Notifier

Notifier UniNet 2000 Simplex 4010 NION Installation and operation manual

SILENT KNIGHT INTELLIKNIGHT 5808 Installation and operation manual

SILENT KNIGHT

SILENT KNIGHT INTELLIKNIGHT 5808 Installation and operation manual

Honeywell NOTIFIER FireWarden-100-2 instruction manual

Honeywell

Honeywell NOTIFIER FireWarden-100-2 instruction manual

Global JUNO-NET Operation & maintenance manual

Global

Global JUNO-NET Operation & maintenance manual

Faraday MPC-6000 Programming manual

Faraday

Faraday MPC-6000 Programming manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.