
4099-9032 through 4099-9037
IDNet Manual Call Point
Installation Instructions
1998 Simplex Time Recorder Co., Gardner, MA 01441-0001 USA
All specifications and other information shown were current as of publication, and are subject to change without notice. 574-787
Rev. A
Cautions and Warnings
ELECTRICAL HAZARD - Disconnect electrical power when installing or servicing.
STATIC HAZARD - Static electricity can damage components. Ground yourself before opening or installing
components.
Introduction
The 4099-9032 through 4099-9037 Series Manual Call Points provide a means to manually initiate a fire alarm
condition to the 4010 Fire Alarm Control Panel (FACP), via the IDNet™ channel. The IDNet channel provides the
communication link between a call point and 4010 FACP and powers the entire circuitry.
Installation
Addressable call point installation consists of the following steps.
1. Setting the call point address.
2. Making electrical connections to the call point.
3. Mechanically installing the call point.
4. Replacing the glass substitute element with the break glass.
5. Testing the call point.
1. Setting the Call Point Address
Each call point has a unique address (1 through 250). The address of the call point is set via an eight position DIP
switch (Figure 2), DIP switch position 1is the least significant bit (LSB) and position 8is the most significant bit
(MSB). Set the call point address using Figure 2 as a reference. Use a small screwdriver or pen to set the switches.
Configure the call point to the 4010 panel using the 4010 Fire Alarm Panel Programming Instructions (574-054) and
the 4010 Fire Alarm Installation and Operation Instructions (574-052). Use device type KACPUL. Refer to the
4010 Panel Label (526-444) for the appropriate revision of the instructions to be used.
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000 0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240
1000 1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241
0100 2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242
1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243
0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244
1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245
0110 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
1110 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247
0001 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
1001 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249
0101 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
1101 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235
0011 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236
1011 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237
0111 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238
15 31 47 63 79 95 111 127 143 159 175 191 207 223 239
LSB MSB
12345678
1111
DIP SWITCHES 5 THRU 8
ON
OFF 1 = ON 0 = OFF
251
252
253
254
255
DIPSWITCH IS SHOWN SET AT ADDRESS 7. Note:
DIP switch in “1” position is
“ON” while DIP switch in “0”
position is “OFF.”
Figure 3. Call Point Addressing ChartFigure 2. Rear View of Call Point
Figure 1. Front View of Call Point
(English Version with Glass Installed)
Red IDNet +
Black IDNet -
DIP Switches