S4090-0002-7
Features
Individual Addressable Relay Module (Relay
IAM):
IDNet addressable control for use with Simplex®fire
alarm control panel models 4100ES, 4100U, 4010ES
and 4010
A single addressable point provides control and status
tracking of a Form “C” contact
Low power latching relay design allows IDNet
communications to supply both data and module power
Compact, sealed construction:
Enclosed design minimizes dust infiltration
Mounts in standard 4” (102 mm) square electrical box
Screw terminals for wiring connections
Visible LED flashes to indicate communications
Optional covers are available to allow LED to be
viewed after installation
UL listed to Standard 864
Description
IDNet Relay IAMs allow fire alarm control panels to
control a remotely located Form “C” contact using IDNet
addressable communications for both data and module
power. Typical applications would be for switching local
power for control functions such as elevator capture, or
control of HVAC components, pressurization fans,
dampers, etc. Relay status is also communicated requiring
only one device address.
Product Selection
Model
Description
4090-9002
Relay IAM
Optional Trim Plates
Model
Description
4090-9801
For semi-flush
mounted box
Trim plate, galvanized
steel, with LED viewing
window; includes
mounting screws
4090-9802
For surface
mounted box
*This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing
7300-0026:223 for allowable values and/or conditions concerning material presented in this
document. It is subject to re-examination, revision, and possible cancellation. Accepted for
use –City of New York Department of Buildings –MEA35-93E. Additional listings may be
applicable; contact your local Simplex product supplier for the latest status. Listings and
approvals under Simplex Time Recorder Co. are the property of Tyco Safety Products
Westminster.
5
6
7
8
1
2
3
4
SIMPLEX TIME RECORDER CO .
4090-9002
RELAY IAM
INST. INSTR. 574-184
DATE CODE:
1
+IDNET
- IDNET
1
2
3
4
5
6
7
8
N.C.
N.O.
COM
-
-
-
4090 Series IDNet Relay IAM Package
(shown approximately 1/2 size)
Specifications
Communications
4100ES, 4100U, 4010ES or 4010
IDNet communications, 1 address per
device
Relay IAM Power
Supplied by IDNet communications
Contact Ratings* (not rated for incandescent switching)
Type
Form C, SPDT
Power-Limited
2 A @ 24 VDC, resistive
from listed
fire alarm
supply
1 A @ 24 VDC, inductive
Nonpower-Limited
0.5 A @ 120 VAC, resistive
* Provide circuit fusing and transient suppression as
required per application. DC inductive loads can typically
be diode suppressed; 120 VAC loads may require RC
networks or varistors, depending on device type. Refer to
Installation Instructions 574-184 for additional information.
Wire Connections
Screw terminals for in/out wiring,
18 to 14 AWG wire (0.82 to 2.08 mm2)
IDNet Wiring
Reference
Up to 2500 ft ( 762 m) from control
panel
Up to 10,000 ft ( 3048 m) total wiring
distance (including T-Taps)
Compatible with Simplex 2081-9044
Overvoltage Protectors
Dimensions
4-1/8” H x 4-1/8” W x 1-3/8” D
(105 mm x 105 mm x 35 mm)
Housing Material
Black thermoplastic
Mounting Plate
Sheet metal, galvanized
Temperature
Range
32° to 120° F (0° to 49° C),
intended for indoor operation
Humidity Range
Up to 93% RH at 100° F (38° C)
Multi-Application Peripherals
UL, ULC Listed; FM, CSFM, IDNet™ Communicating Devices
and MEA (NYC) Approved* Model 4090-9002 Relay IAM
Tyco is a registered trademark of Tyco International Services GmbH and is used under license. Simplex, the Simplex logo, and IDNet are trademarks of Tyco International Ltd. and
its affiliates and are used under license.
SimplexGrinnell LP Westminster • Westminster, MA • 01441-0001 • USA S4090-0002-7
www.simplexgrinnell.com
© 2011 Tyco. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.
4" (102 mm) square box, 2-1/8"
(54 mm) minimum depth, RACO
232 or equal (supplied by others)
Double gang blank cover plate and mounting screws, for
use when LED is not required to be externally viewed
(supplied by others)
4090-9002 Relay IAM
Address setting under
resealable label
Optional Trim Plates for Visible LED
4090-9802, Trim plate for
surface mounted box
4090-9801, Trim plate for
semi-flush mounted box
Mounting Reference, Double Gang Blank Cover Plate
4-9/16"
(116 mm)
4-9/16" (116 mm)
4-5/16"
(109 mm)
Light pipe for LED viewing
4-5/16" (109 mm)
Relay IAM Mounting Information

Popular Other manuals by other brands

Texas Instruments MSP430FG4616IPZ manual

Texas Instruments

Texas Instruments MSP430FG4616IPZ manual

Sony SAL18552 instruction & operation manual

Sony

Sony SAL18552 instruction & operation manual

Lutron Electronics DL-9602SD Operation manual

Lutron Electronics

Lutron Electronics DL-9602SD Operation manual

Duracable J-MAXX Machine manual

Duracable

Duracable J-MAXX Machine manual

Fichet-Bauche Complice Installation and use

Fichet-Bauche

Fichet-Bauche Complice Installation and use

3Com 3C433279 - SuperStack II RAS 1500 Access... manual

3Com

3Com 3C433279 - SuperStack II RAS 1500 Access... manual

Battery Tender Deltran Battery Tender 12V 800 Milliamp Important safety instructions

Battery Tender

Battery Tender Deltran Battery Tender 12V 800 Milliamp Important safety instructions

Meaco 12L-AH Dehumidifier instruction manual

Meaco

Meaco 12L-AH Dehumidifier instruction manual

Exo Terra Compact Top Series operating instructions

Exo Terra

Exo Terra Compact Top Series operating instructions

Extech Instruments RHT20 user guide

Extech Instruments

Extech Instruments RHT20 user guide

Proeco IO-2001 instruction manual

Proeco

Proeco IO-2001 instruction manual

Meaco MeacoWall 53B instruction manual

Meaco

Meaco MeacoWall 53B instruction manual

Delta Electronics EXIO28RAE reference guide

Delta Electronics

Delta Electronics EXIO28RAE reference guide

Motorvac Diff-Vac 1000 user manual

Motorvac

Motorvac Diff-Vac 1000 user manual

wtw 115 VAC operating manual

wtw

wtw 115 VAC operating manual

Pro-Ject Audio Systems Box Design Phono Box E BT Instructions for use

Pro-Ject Audio Systems

Pro-Ject Audio Systems Box Design Phono Box E BT Instructions for use

Future Motion ONEWHEEL+ owner's manual

Future Motion

Future Motion ONEWHEEL+ owner's manual

SWEEX CR150 quick guide

SWEEX

SWEEX CR150 quick guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.