SJE Rhombus VFDC-4100 User manual

This manual explains the features and operations of the VFDC-
4100 controller which is specifically designed for Pressure Booster
Pump Systems. The VFDC-4100 controller is capable of maintaining
a constant discharge pressure by adjusting the speed of up to 4
Variable Frequency Drives (VFDs), one VFD and up to 3 across the
line (ATL) starters, or one Jockey pump and up to 3 main pumps.

WARNINGS
Failure to read and understand the information provided in this manual may result in personal injury or death, damage to
the product or product failure. Please read each section in its entirety and be sure you understand the information provided
in the section and related sections before attempting any of the procedures or operations given.
Failure to follow these precautions could result in serious injury or death.
Keep these instructions with warranty after installation. This product must be
installed in accordance with National Electrical Code, ANSI/NFPA 70 so as to
prevent moisture from entering or accumulating within the controller housing.
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing this product.
A qualified service person must install and service this product
according to applicable electrical codes and electrical schematics.
EXPLOSION OR FIRE HAZARD
Do not use this product with flammable liquids. Do not install in
hazardous locations as defined by National Electrical Code,
ANSI/NFPA 70.
• Do not install in area with: excessive or conductive dust, corrosive or
flammable gas, moisture or rain, excessive heat, regular impact shocks
or excessive vibration.
• Do not place in water or let water leak onto the controller.
• Do not allow debris to fall inside the unit during installation.
• Double-check all the wiring before turning on the power supply.
• Do not touch live wires.
• Stay as far as possible from high-voltage cables and power equipment.
• Leave a minimum of 10 mm space for ventilation between the top and
bottom edges of the controller and enclosure walls.

SJE-Rhombus VFDC-4100 Controller User Manual 1
Table of Contents
Chapter 1
1.1 Controller Description........................................................................ 2
1.2 Controller Outline Dimension ............................................................ 3
Chapter 2
2.1 Description of Functions.................................................................... 4
2.2 Security.............................................................................................. 5
2.3 Default Values ................................................................................... 6
2.4 Function Keys & Icon Descriptions ................................................... 8
2.5 Description of LCD Screen................................................................ 9
Chapter 3
3.1 Security............................................................................................ 10
3.2 Details of Setup Menus ................................................................... 10
3.3 Setup Menu Display & Input Method............................................... 14
Chapter 4
4.1 Triplex VFD Power Circuit Schematic (VFD) .................................. 16
4.2 Triplex Controller Circuit Schematic (VFD) ..................................... 17
4.3 Triplex VFD Power Circuit Schematic (1VFD+ATL)........................ 18
4.4 Triplex Controller Circuit Schematic (1VFD+ATL)........................... 19
Chapter 5
5.1 Troubleshooting............................................................................... 20
Chapter 6
6.1 Fault Alarm Display & Corrective Actions ....................................... 21
6.2 Alarm Data Screen.......................................................................... 22
6.3 Operation Data Log Screen & Run Times ...................................... 22
ModBus Communication Functions & Adress Code........................ 24

2SJE-Rhombus VFDC-4100 Controller User Manual
Chapter 1
1.1 Controller Description
<Front View>
<Rear View>
LCD Screen
LED Indicators
Push Buttons
CN2 Sensor Terminal
CN10 COMM Port
CN7 Fault Inputs
CN8 Low Suction/Set
Pressure 2
CN1 Annalog Speed
Refs.
CN3 Transistor outputs
CN5 Relay outputs
CN4 DC Input Power

SJE-Rhombus VFDC-4100 Controller User Manual 3
1.2 Controller Outline Dimensions in inches.

Chapter 2
2.1 Description of Functions
LCD Display
The LCD Display is a user friendly operator interface with 240 x 64 pixels resolution; it allows the user to quickly view the
system status and log.
Multiple Pumps Parallel Operation
The controller is able to control up to four (4) pumps utilizing all VFD’s, or one VFD with up to 3 ATL (across the line)
starters for the lag pumps.
Lead/Lag Operation
A fully automatic lead/lag operation based on the variation of the system discharge flow allows you to significantly reduce
your energy cost and consistently maintain the system pressure. While the lead pump is operating, the system will
sequentially start and stop lag pump(s) based on variation of the system pressure.
Across The Line (ATL) Pump Operation
When enabled and utilized, this function allows for multiple pumps to be controlled in a true PID pressure control system,
while only needing one VFD. When the output of the lead pump (VFD) is at 100%, the controller changes that pump over
to direct (ATL) operation and switches on the first lag pump using the VFD. In the same way, lag pump 2 and 3 can be
added as needed for heavy flow conditions. The pump being controlled by the VFD will always be varying its speed as
needed to maintain the set pressure.
Automatic Re-Start
Should the system shutdown by a sudden power loss, it will automatically restart when the power is restored. No manual
reset is required. The system automatically returns to the running condition programmed and stored in the system memory.
Lead Pump Alternation
When selected as set time based, the alternation will occur when the total operating time of the lead pump reaches to
the alternation time; the system automatically selects the next pump in sequence to be the lead pump. This function is
designed to reduce the system life cycle cost. The system make all pump operate for equal period of time as to prevent
the over-use of a particular pump resulting in high parts wear of the pump. The alternation may also be cycle based
rather than time based.
Faulty Pump(s) Skip Function
The system automatically skips any pump sending a fault signal to the controller, and immediately changes the operating
sequence to the functioning pumps. The faulty VFD/Pump will continue to report its fault until maintenance personnel can
diagnose and repair the fault condition. A fault can be any of the following: VFD fault, starter overload trip (when using
starters) or HAND/OFF/AUTP (HOA) selector switch is not in the AUTO position.
Dry Run Prevention
The system automatically stops the running pump(s) upon the detecting a Low pressure signal (Low Water). This
function prevents the pump(s) from dry running that may result in damage to the pump(s).
Program
Used to program the set pressure to change based on a time/day/month basis.
Dual Set Pressures
An additional SET PRESSURE is available in the PRESSURE menu and can become the active set pressure by
activating input 018 on CN8. This function can be useful for systems with large fluctuations in suction pressure or large
variations in demand flow.
Alarm Display and Logging
The system displays alarm conditions on the LCD monitor, and records the condition in a log that is date and timed
stamped.
Operating Data Display and Storage
The semi-permanent operating data recording and storage for each pump allows efficient pump maintenance.
4SJE-Rhombus VFDC-4100 Controller User Manual

Freeze Prevention
When this function is enabled the lead pump will automatically start at the VFD minimum output for 30 seconds and then
shift to the next pump when the temperature is under 32 deg. This will occur when all pumps are stopped for more than
30 seconds at the same time.
Idle Prevention
If the lead pump does not run for the set time, corrosion of some parts may occur. In order to prevent this, the system
will automatically run the lead pump at the minimum operating speed for 60 seconds and then starts the next pump in
sequence. The same process will be repeated if the succeeding lead pump does not run during the set time.
Password
If the password function is enabled, a pop-up window will appear when you press the MENU button. You must enter your
password to access the setup screens. This is to prevent access to the input values by an unauthorized person. You can
change or disable the user password if you wish, however once enabled you must remember the value to gain access to
the setup menu.
Communication
It is possible to monitor the system remotely when connected via the RS-485 port. See page 24 for details.
PID Control
The microprocessor based controller is programmed to perform adjustable Proportional, Integral and Derivative control to
provide consistent and reliable pressure control.
LCD Screen Saver
The back light of the LCD display is programmed to automatically fade out if the keypad is not used for a set time. This
function allows for maximum life span of the LCD monitor. This function can be disabled if desired.
Jockey Pump Function
The role of the Jockey pump is to maintain constant pressure during low flow conditions. When utilized, the jockey pump
is typically much smaller than the main pumps and is well suited to handle variations in flow at a low flow rate. When flow
demand exceeds the capacity of the Jockey pump and the main pumps are called to run, the Jockey will turn off after a
programmable delay time, minimizing wear on the small pump.
Pre-Charge Function
In systems that drain out when not running, the pre-charge function allows for filling the piping system without causing
damage. This function allows for the lead pump to run at a low preset speed for a preset time prior to switching over to
full automatic operation. This greatly reduces water hammer to the piping system.
SJE-Rhombus VFDC-4100 Controller User Manual 5
2.2 Security
The security system is designed to prevent access by unauthorized persons to the setup menu without entering a user
password. If this function is turned on in the protect menu you will be required to enter the password to gain access to
the setup screens. When you press the [Menu] button, the password pop-up window will appear. You must enter your
user password to access the setup menu screens.
Set the password in the password function under the protect menu item by using the up/down & right/left key and press
the enter button. The password must consist of 4 numbers.
After entering the password, and exiting the setup menu, access to the setup screens will be locked. The password will
then need to be re-entered to access the setup screens.

6SJE-Rhombus VFDC-4100 Controller User Manual
2.3 Default Values
Menus Setup Menus Default Input Range
YEAR 2004 0000 ~ 9999
MONTH 1 1 ~ 12
DATE 1 1 ~ 31
DATE WEEKDAY 0 MONDAY ~ SUNDAY
TIME HOUR 0 0 ~ 23
MINUTE 0 0 ~ 59
SECOND 0 0 ~ 59
LEAD PUMP PUMP 1 1 ~ 4
PUMP 1 USED USED, NOT USED, JOCKEY
PUMP PUMP 2 USED USED, NOT USED
SET UP PUMP 3 NOT USED USED, NOT USED
PUMP 4 NOT USED USED, NOT USED
SET PRESSURE 60 PSI 2 PSI ~ 650 PSI
SET PRESSURE 2 60 PSI 2 PSI ~ 650 PSI
HIGH PRESSURE LIMIT 95 PSI 3 PSI ~ 719 PSI
PRESSURE LOW PRESSURE LIMIT 15 PSI 1 PSI ~ 649 PSI
SET UP START LEAD PRESSURE -3 PSI -65 PSI ~ 65 PSI
START LAG PRESSURE -7 PSI -65 PSI ~ 65 PSI
STOP LAG PRESSURE 3 PSI -0 PSI ~ 65 PSI
P VALUE 60 0 ~ 200
I VALUE 30 0 ~ 200
D VALUE 1 0 ~ 200
CYCLE TIME 120 Msec. 50 ~ 999 M.SEC.
ALTERNATION 24 HOURS 0 ~ 999 HOURS
FRICTION 0.0 PSI 0 ~ 650 PSI
CONTROL RUN DELAY 1 SECONDS 0 ~ 10 SECONDS
SET UP STOP DELAY 1 SECONDS 0 ~ 999 SECONDS
JOCKEY STOP DELAY 5 SECONDS 0 ~ 999 SECONDS
OPERATION TYPE VFD VFD, 1VFD+ATL
LOW SUCTION TMR 30 SECONDS 10 ~ 999 SECONDS
LOW SUCTION RST AUTO AUTO, MANUAL
LOW SUCTION RST TMR 30 SECONDS 10 ~ 9999 SECONDS (2.78 HOURS)
LOW PRESSURE STOP TIME 10 SECONDS 10 ~ 999 SECONDS
INITIALIZE YES, NO
SENSOR SENSOR VALUE 200 PSI 29 PSI ~ 720 PSI
SET UP SENSOR OFFSET 0 PSI -72 PSI ~ 72 PSI
VFD STOP TIME 30 SECONDS 0 ~ 60 SECONDS
VFD MINIMUM RATE 40% 10 ~ 90 % (of VFD DISP. TYPE)
VFD STOP RATE 60% 20 ~ 90 (of VDF DISP. TYPE)
VFD VFD DISP. TYPE 100% 100%, 60Hz, 50Hz
VFD AUTO RESET 5 0 ~ 20
PIPE FILL OFF ON, OFF
PIPE FULL RATE 45% 10 ~ 90% of VFD DISP. TYPE or VFD
PIPE FILL TIMER 30 SECONDS 5 ~ 600 SECONDS

SJE-Rhombus VFDC-4100 Controller User Manual 7
2.3 Default Values con’t.
Menus Setup Menus Default Input Range
IDLE PREVENTION NOT USED USED, NOT USED
PROTECT FREEZE PREVENTION NOT USED USED, NOT USED
PASSWORD USE NOT USED USED, NOT USED
PASSWORD 1234 0000 ~ 9999
RETURN TO MAIN SCREEN 120 SECONDS 10 ~ 300 SECONDS
LCD BACK LIGHT TIME 120 SECONDS 10 ~ 998 SECONDS (999 TO DISABLE)
DATA LOG 60 SECONDS 0 ~ 999 SECONDS (16.65 MIN)
TEST CODE 0 0 ~ 9999 (NOT USED)
RELAY OUTPUT 1 STOP AVAILABLE SETTINGS FOR OUTPUTS:
RELAY OUTPUT 2 RUNNING NOT USED, PUMPS STOPPED, PUMPING,
SYSTEM RELAY OUTPUT 3 ALARM GENERAL ALARM, LOW SUCTION, P1-P4
RELAY OUTPUT 4 NOT USED VFD RUN, P1-P4 ALT RUN, BUZZER,
RELAY OUTPUT 5 NOT USED LOW PRESSURE, HIGH PRESSURE,
DIGITAL OUTPUT 6~13 NOT USED VFD1-4 FLT/HOA, SENSOR FAULT
LANGUAGE ENGLISH ENGLISH, ESPANOL
PRESSURE UNIT PSI PSI, BAR
SCHEDULE OPERATION NOT USED NOT USED, TIMELY, WEEKLY, MONTHLY
PROGRAM 00:00:00~00:00:00 NOT USED 0 PSI ~ 650 PSI
TUESDAY NOT USED 0 PSI ~ 650 PSI
FEBRUARY NOT USED 0 PSI ~ 650 PSI
PARITY NONE EVEN, ODD, NONE
BAUDRATE 9600 9600, 14400, 19200
COMM NODE 1 1~31
SET DATA BITS 8
STOP BIT 1 1,2
ALARM DATA 32 MOST RECONT ALARMS SAVED SEE CHAPTER 6
OPERA DA OPERATION DATA SELECTION RUN LOG RUN LOG, PUMP RUN TIMES
Total 2000 lines of data saved.
(Refer to Chapter 6)

8SJE-Rhombus VFDC-4100 Controller User Manual
J
“Pump Setting” - “Pump 1”
When you set “Jockey Pump”
The VFD faulted while operating
the pump.
“Pump Setting” - “Pump 1 ~ 4”
Set to “USED” when the pump is
available for use.
“Pump Setting” - “Pump 1 ~ 4”
Set to “NOT USED” when the pump is
NOT available for use.
2.4 Function Keys & Icon Description
2.4.1 Function Description
LCD Screen/LED Indicators/Keypad
1. LCD: Displays on the screen the operating status and setting.
2. LED: Displays the operation, alarm, operating pump, etc.
Four PUMP LED displays the operation of each pump.
LED Off: PUMP stopped
LED On: PUMP running
3. Function Keys
2.4.2 Description of Icon
Menu Navigation and Data Entry
Pressing the menu button will enter the main setup menu items. The system will ask for a password if enabled. Using
the arrow buttons, navigate to the item desired, and press enter. Navigate with the arrows and enter the item of choice to
display its value. Enter to change the value using the arrow buttons and again press the enter button to accept the new
value, or press esc. to exit without saving. Press the esc., enter and arrow buttons as desired to move up, drill down,
and navigate the screen as needed.
WARNING:
Certain settings will not change when system is in “AUTO” mode. For these, set the HOA switches to “OFF” to make changes.
RESET
Used to clear faul codes
after the fault condition is
removed. (Some Faults may
require you to cycle power.)
ESC
Press to move up in
the menu structure or
cancel an entry without
saving.
ENTER
Press to accept a value
or navigate down within a
menu item.
Navigation Buttons
MENU
Used to access the main setup screen.
System may ask for a password
if enabled.

SJE-Rhombus VFDC-4100 Controller User Manual 9
2.5 Description of LCD Screen
2.5.1 Opening Screen
Opening Screen: when the controller power is turned on, the opening screen will be displayed for 3 seconds.
2.5.2 Main Screen
1. Opr. Pre = current discharge pressure & Set Pre = set pressure (Target pressure)
2. Alarm & Time Display: Display of the current time and alarm list if an alarm is active.
3. Auto/Stop Display: Display of the operating condition of the system.
“AUTO” – Is in AUTO if any of the HAND/OFF/AUTO selector switches in AUTO position (Input CN7)
“STOP” - is displayed if none of the HAND/OFF/AUTO selector switches are in AUTO position
4. VFD Output Frequency Display: Display of the output value of the VFD running.
The VFD output display can be configured in percentage (%) or in frequency (50Hz or 60Hz).
5. Pump Status Display: Idle, Running, VFD Fault, or Jockey.
6. Pump Number: Display of the total pumps and Lead pump and numbers.
The Lead pump is labeled “L”, the other pumps are labeled “P”.
PRESSURE BOOSTER
CONTROLLER
PCB-4000 VER 1.05
1. Current & Set Pressure Display
2. Alarm & Time Display
6. Pump Number Display
5. Pump Status Display
4. VFD Output Frequency Display (0-100% = 0-60Hz)
3. Auto/Stop Display
L = Lead Pump

10 SJE-Rhombus VFDC-4100 Controller User Manual
Chapter 3
3.1 Security
The security system is programmed to prevent access by unauthorized persons to control setup without User Password.
<PASSWORD INPUT>
<Password Input Screen>
When you press the [MENU] button, the password pop-up window will appear as shown in the figure above. You must
enter your user password “1234” to access the menu items screen.
• Set the password by using the Up/Down & Right/Left Key and press the Enter button.
• The password must consist of 4 numbers.
• The default User Password is 1234.
NOTE: After entering the password, access to the setup screen will be granted until the LCD backlight timer times
out. The password will then need to be re-entered to access the setup screens. If you don’t give any controls on the
Setup Menu Screen, it will automatically return to the Main Screen. It is strongly recommended to change the password
after the initial access. If you set the system control to factory default setting, the password is initialized to the default
password “1234”. NOTE: The password feature is disabled by default.
INPUT PASSWORD !
0 0 0 0
04. 12. 01 Ver 1.03
3.2 Details of Setup Menus
3.2.1 Date/Time Setup: Current Time Setup
Menus Setup Menu Contents Input Range
YEAR Current Year Display 0000 ~ 9999
MONTH Current Month Display 1 ~ 12
DATE Current Date Display 1 ~ 31
DATE/TIME DAY Current Day Display MONDAY ~ SUNDAY
HOUR Current Hour Display 0 ~ 23
MINUTE Current Minute Display 0 ~ 59
SECOND Current Second Display 0 ~ 59
The time and date does not change should you set the set system to factory default.
3.2.2 Pump Setup
Menus Setup Menu Contents Input Range
LEAD PUMP Lead Pump Selection 1 ~ 4
PUMP 1 Used, Not used or Jockey Used, Not Used, Jockey
PUMP PUMP 2 Used or Not Used Used, Not Used
SETUP PUMP 3 Used or Not Used Used, Not Used
PUMP 4 Used or Not Used Used, Not Used
The lead pump must be set to a pump that is USED and not the Jockey pump.
If PUMP1 is set to JOCKEY, the Jockey pump will always start first and cannot be the LEAD PUMP. The jockey pump
is not included in the lead lag sequencing. The jockey pump will operate alone unless the set pressure cannot be
maintained. Then the lead pump and subsequent pumps will start based on lead/lag sequencing. The jockey pump will
stop after the lead pump starts and a preset delay times out (JOCKEY STOP DELAY).

SJE-Rhombus VFDC-4100 Controller User Manual 11
3.2.3 Pressure Setup
Menus Setup Menu Contents Input Range
SET PRESSURE Target pressure for the pump system discharge 2 PSI ~ 650 PSI
SET PRESSURE 2 To change the set pressure to this alternate 2 PSI ~ 650 PSI
value, a dry contact must close between G-COM
and 018 on the CN8 terminals.
HIGH LIMIT ALARM If the discharge pressure exceeds this value, the 3 PSI ~ 719 PSI
controller will shutdown the pumps after a delay.
LOW LIMIT ALARM If the discharge pressure drops below this value, 1 PSI ~ 649 PSI
PRESSURE the contoller will shutdown the pumps after a
delay.
SETUP START LEAD PRESSURE If the set pressure is 60 PSI and start lead -65 PSI ~ 65 PSI
pressure at -3 PSI, the lead pump will start
when the operating pressure drops below 57 PSI.
START LAG PRESSURE If the set pressure is 60 PSI and start lag -65 PSI ~ 65 PSI
pressure is -7 PSI the lag pump(s) will start when
if lead pump is operating full speed (100% and
the system pressure drops below 53 PSI.
STOP LAG PRESSURE If the set pressure is 60 PSI and the stop lag 0 PSI ~ 65 PSI
pressure is 3 PSI the lag pump will stop if it is
operating at minimum speed (example 50%)
and the current pressure is over 63 PSI.
3.2.4 Control Setup
Menus Setup Menu Contents Input Range
P P Value Setup of PID (Proportional) 0 ~ 200
I I Value Setup of PID (Integral) 0 ~ 200
D D Value Setup of PID (Derivative) 0 ~ 200
CYCLE TIME Sampling time of PID Control 0 ~ 999 m.sec
ALTERNATION Shifts the lead to the next available pump in the 0 ~ 999 HOURS (set to 0 for
sequence.
lead. Change every cycle, set
to 999 for no alternation)
FRICTION PSI offset allowance for friction loss 0 PSI ~ 900 PSI
RUN DELAY Delay time for pumping output to start 0 ~ 999 SECONDS
STOP DELAY Delay time for pumping output to stop 0 ~ 999 SECONDS
CONTROL JOCKEY STOP DELAY TIME Delay time after the main pump starts 0 ~ 999 SECONDS
SET UP OPERATION TYPE Sets the operation type. VFD = multiple VFD VFD, 1VFD+ATL
control system (1 VFD for each pump.)
1VFD+ATL = Single VFD control system
(combination of 1 VFD and starters)
LOW SUCTION TMR Delay time before stipping the pump due to low 10 ~ 999 SECONDS
suction pressure
LOW SUCTION RST Method used to reset the low suction shut AUTO, MANUAL
down valve
LOW SUCT RST TMR When low scution rest is set to auto, this is the 10 ~ 999 SECS (2.78 hrs)
time the controller will wait before attempting
to reset.
LOW PRESS STOP TIME Delay time before stopping the pump due to low 10 ~ 999 SECONDS
pressure fault.
INITIALIZE All parameters are set to factory defaults YES, NO
(except data setup)

12 SJE-Rhombus VFDC-4100 Controller User Manual
3.2.6 VFD Setup
Menus Setup Menu Contents Input Range
VFD STOP TIME Time delay for when the last pump stops after 0 ~ 60 SECONDS
the speed drops to the VFD minimum rate.
VFD MINIMUM RATE VFD minimum speed output 10 ~ 90%
VFD STOP RATE The last pump stops when its speed is less than 20 ~ 90%
this set value and the VFD STOP TIME is done.
VFD DISP. TYPE Display the VFD output value on the main screen. 100%, 60Hz, 50Hz
VFD VFD AUTO RESET Reset times after an alarm happened while the 0 ~ 20
VFD was operating.
PIPE FILL Enable or disable the pipe fill function. ON, OFF
PIPE FILL RATE The preset speed the pump will run on start up 10- 90% or VFD min speed
slowly fill the pipes. Runs for the PIPE FILL
TIMER or the SET PRESSURE is reached.
PIPE FILL TIMER The length of time the pump will run. If the set 5 ~ 600 SECONDS
pressure is reached during this time, the
system will switch to PID immediately.
3.2.7 Protect Setup
Menus Setup Menu Contents Input Range
IDLE PREVENTION When set to USED, if the lead pump has not ran USED, NOT USED
for 10 days, the system will automatically run the
lead pump at the minimum operating speed for 60
seconds. Then it will switch lead pump. The same
process will be repeated if the succeeding lead
pump does not run for 10 days etc.
PROTECT FREEZE PREVENTION When set to USED, the lead pump will automatically USED, NOT USED
start the VFD minimum output for 30 seconds and
then shift to the next pump when the temperature
is under 32 deg. This will occur when all pumps are
stopped for more than 30 seconds at the same time
PASSWORD USE See password section for description USED, NOT USED
PASSWORD 0000 ~ 9999
3.2.5 Sensor Setup
Menus Setup Menu Contents Input Range
SENSOR TRANSDUCER TYPE Range Setup of Sensor 29 PSI ~ 720 PSI
SETUP SENSOR ADJUST Sensor Offset Value -72 PSI ~ 72 PSI

SJE-Rhombus VFDC-4100 Controller User Manual 13
3.2.8 System Setup
Menus Setup Menu Contents Input Range
RETURN MAIN SCREEN Returns to the main screen after set time if user 10 ~ 300
does not use any key controls
LCD BACK LIGHT TIME After the set time, LCD back light automatically turns 10 ~ 999
off. This can be disabled by setting value to 999.
DATA LOG Sets the sampling rate for the Operation data log 10 ~ 999
SYSTEM TEST CODE Internal code to check the system. 0 ~ 9999
SET UP RELAY OUTPUT 1-5 Relay output 1-5 allows for up to 5A @ 250V
DIGITAL OUTPUT 6-13 Digital output is transistor out. High = 5V Low = 0V
Available settings for outputs are: NOT USED,
PUMPS STOPPED, PUMPING, GENERAL ALARM,
LOW SUCTION, P1-P4 VFD RUN, P1-P4 ATL RUN,
BUZZER, LOW PRESSURE, HIGH PRESSURE,
VFD 1-4 FLT/HOA, SENSOR FAULT
LANGUAGE Language selection English/Espanol
PRESS UNIT Unit of measure for analog input PSI/BAR
3.2.9 Communication Setup (RS-485)
Menus Setup Menu Contents Input Range
PARITY Select parity mode EVEN, ODD, NONE
COMM BAUDRATE Transmission speed 9600, 14400, 19200
SETUP NODE Network node address 1~31
DATA BITS 8
STOP BIT 1,2
3.2.10 Communication Setup
Menus Setup Menu Contents Input Range
SCHEDULE OPERATION This function allows the set pressure to be NOT USED, TIMELY, WEEKLY,
00:00:00 ~ 00:00:00 adusted based on a schedle. If on certain days MONTHLY
PROGRAM of the week, you wanted the set pressure to be
TUESDAY different, you would set schedule operation to
FEBRUARY WEEKLY then set the pressures for the days of
the week.

14 SJE-Rhombus VFDC-4100 Controller User Manual
3.3 Setup Menu Display & Input Method
Example for the Data Setup Change
<Fig 1> Menu Setup Screen
<Fig 2> Data Setup Change Screen
<Fig 3> Date Setup Change Screen
1. The display will change to <Fig 2> if you press the enter button after selecting the Date/Time on the Menu Setup
<Fig 1>.
2. Moved to the set position which needs to be changed: Year/Month/Day/Week by Right & Left key. Press the Enter
key and edit when flashing.
3. Change the value by using the Up/Down keys.
4. Save the changed value by pressing the Enter key.
5. Exit to the main screen by pressing the ESC key.
DATE/TIME PUMP SET PRESSURE
CONTROL SENSOR VFD
PROTECT SYSTEM PROGRAM
COMM SET ALARMS DATA LOG
DATE & TIME SETUP (4.0/RUN)
2005 / 12 / 22 [WED]
11 : 00 : 00
DATE & TIME SETUP (4.0/RUN)
2005 / 12 / 22 [WED]
11 : 00 : 00

SJE-Rhombus VFDC-4100 Controller User Manual 15
Example for the Pressure Setup Change
<Fig 1> Main Screen
<Fig 2> Menu Setup Screen
<Fig 3> Pressure Setup Change Screen
<Fig 4> Pressure Setup Change Screen
<Fig 5> Pressure Setup Change Screen
<Fig 6> Pressure Setup Change Screen
DATE/TIME PUMP SET PRESSURE
CONTROL SENSOR VFD
PROTECT SYSTEM PROGRAM
COMM SET ALARMS DATA LOG
DATE/TIME PUMP SET PRESSURE
CONTROL SENSOR VFD
PROTECT SYSTEM PROGRAM
COMM SET ALARMS DATA LOG
PRESSURE SETUP (60.0/RUN)
SET PRESSURE 60 PSI
HIGH PRE. LIMIT 150 PSI
LOW PRE. LIMIT 20 PSI
Press the “MENU” button.
Use the UP/DOWN and RIGHT/LEFT keys to go to the Pressure
Menu.
Press “ENTER” button to open the Pressure Menu.
Moved to the set position which needs to be changed using the UP/
DOWN key. Press “ENTER” key.
Use the UP/DOWN and RIGHT/LEFT keys to edit.
Save the changed value by pressing the Enter key.
Exit to the main screen by pressing the ESC key.
PRESSURE SETUP (60.0/RUN)
SET PRESSURE 60PSI
HIGH PRE. LIMIT 150 PSI
LOW PRE. LIMIT 20 PSI
PRESSURE SETUP (60.0/RUN)
SET PRESSURE 65PSI
HIGH PRE. LIMIT 150 PSI
LOW PRE. LIMIT 20 PSI

16 SJE-Rhombus VFDC-4100 Controller User Manual
Chapter 4
4.1 Typical Triplex VFD Power Circuit Schematic (OPER TYPE =VFD)

SJE-Rhombus VFDC-4100 Controller User Manual 17
RS-485
CN10
+-
4.2 Typical Triplex Controller Circuit Schematic (OPER TYPE = VFD)

4.3 Typical Triplex VFD Power Circuit Schematic (OPER TYPE = 1VFD+ATL)
18 SJE-Rhombus VFDC-4100 Controller User Manual
Table of contents
Languages:
Other SJE Rhombus Controllers manuals
Popular Controllers manuals by other brands

Tecnoplastic
Tecnoplastic TAURUS instructions

Emerson
Emerson Dixell XR60CHC Installing and operating instructions

Oase
Oase ProfiLux Garden LED Controller operating instructions

Delta Electronics
Delta Electronics Program Copy Card TP-PCC01 instruction sheet

United Automation
United Automation INFRESCO P user manual

Omron
Omron Sysmac NX-PD1000 user manual