Service Manual
Under-voltage protection
The mains supply voltage has dropped below the minimum allowable
level. The cabinet has temporarily shut down to prevent damage and
will restart once the supply voltage increases.
1, 2, 3, 4 Should be a one off; if continues:
- power supply overloaded / multi-box
- line voltage / rural.
- voltage setting parameter
- controller
High condensing temperature protection
The system was operating at an elevated temperature and has
temporarily shut down to prevent damage. Extended operation in this
condition may result in ALARM 15, increased energy consumption
and a reduction in cabinet life. This alarm may be caused by very
high ambient temperature.
2, 3, 4
NO swap cartridge required
- condenser not clean
- poor installation / ventilation
- condenser fan motor / blade
- controller
Excessive compressor cycling protection
The system has been turning on and off too frequently. 2, 3, 4
Take a spare cartridge in case refrigeration system fault.
- condenser blocked
- poor installation / ventilation
- cabinet / cartridge gasket seals leaking
- door not self closing / gasket leaking
- product; hot / blocking cabinet airflow
- overloaded from excess door openings / ambient
- fan motor / blade (condenser / evaporator)
- controller
- compressor / gas leak = SWAP cartridge
Table 4: Faults (continued)
Description Service tech
type
Possible root cause
Table 5: Alarms
Code Description Service tech
type
Possible root cause
dor Door left open.
The door has been open for several minutes. Will revert
to door left open FAULT after 10 minutes (see faults
table on previous page).
1, 2, 3, 4 - door not self closing (torsion fault)
- door switch / circuit
- controller
8 Estimated product temperature below allowable range
The estimated product temperature has been below the
allowable range for longer than the permissible time.
Potential causes are: an empty or partially filled
cabinet, or low ambient temperature.
1, 2, 3, 4 - low ambient
- App settings
- controller
9 Estimated product temperature above allowable range
The estimated product temperature has been above
the allowable range for longer than the permissible
time. Potential causes are: excessive door openings,
door being left open, or warm product loaded into
cabinet.
2, 3, 4 NO spare cartridge required to be taken (but may be required as
fault could still be with sealed refrigeration system)
- Condenser blocked
- Poor installation / ventilation
- Frozen blocked evaporator coil
- Cartridge gasket leaking (to cabinet seal / lid seal)
- Door leaking air (bad gasket / door not self closing)
- Product hot / blocking cabinet airflow
- Overloaded from excess door openings / ambient
- Fan motor / blade (condenser / evaporator)
- App settings
- Controller
- Compressor / gas leak = arrange SWAP cartridge
15
Excessive condensing temperature protection
The system was operating at an excessive temperature
and has shut down to prevent permanent damage. This
alarm may occur due to very high ambient temperature.
2, 3, 4
NO swap cartridge required
- Condenser not clean
- Poor installation / ventilation
- Condenser fan motor / blade
- Controller
17
Control probe failure
A critical system sensor has failed and the cabinet can
no longer operate.
2, 3, 4
NO swap cartridge required
- Control probe / circuit
- Controller