4 Installation (continued)
4.3 Environment Warning
•Do not use in an environment where corrosive gases, chemicals, salt
water or steam are present.
•Do not use in an explosive atmosphere.
•Do not expose to direct sunlight. Use a suitable protective cover.
•Do not install in a location subject to vibration or impact. Check the
product specifications.
•Do not mount in a location exposed to radiant heat.
•Do not use the Pressure switch in a place where electrical static charge
will be a problem. It can cause an error and damage to the system.
4.4 Piping Caution
•Before piping make sure to clean up chips, cutting oil, dust etc.
•When installing piping or fittings, ensure sealant material does not
enter inside the port. When using seal tape, leave 1 thread exposed
on the end of the pipe/fitting.
•Tighten fittings to the specified tightening torque.
•Connection using One-touch fitting
1. Cut the tube end perpendicular.
2. Hold the tube and insert it into the One-touch fitting slowly until it
bottoms out.
•Allow sufficient tube length to prevent twist and tensile or moment
loads from being applied to the fitting or tube.
•When using a tube manufactured by a company other than SMC,
check that its outside diameter tolerance satisfies the following values:
1) Nylon tube: ±0.1 mm maximum
2) Soft nylon tube: ±0.1 mm maximum
3) Polyurethane tube: +0.15 mm / -2 mm maximum
4.5 Lubrication Caution
•SMC products have been lubricated for life at manufacture, and do not
require lubrication in service.
•If a lubricant is used in the system, use turbine oil Class 1 (no additive),
ISO VG32. Once lubricant is used in the system, lubrication must be
continued because the original lubricant applied during manufacturing
will be washed away.
5 Wiring
5.1.1 Wiring connections
•Connections should be made with the power supply turned off.
•Use a separate route for the product wiring and any power or high
voltage wiring. Otherwise, malfunction may result due to noise.
•If a commercially available switching power supply is used, be sure to
ground the frame ground (FG) terminal. If the switching power supply is
connected for use, switching noise will be superimposed and it will not
be able to meet the product specifications. In that case, insert a noise
filter such as a line noise filter/ferrite between the switching power
supplies or change the switching power supply to a series power supply.
5 Wiring (continued)
5.2 Connector Connecting / Disconnecting
•When mounting the connector, insert it straight into the socket, holding
the lever and connector body, and push the connector until the lever
hooks into the housing, and locks.
•When removing the connector, press down the lever to release the
hook from the housing and pull the connector straight out.
Connector pin numbers
6 Pressure Setting
6.1 Measurement mode
The measurement mode is the condition where the pressure is detected
and displayed, and the switch function is operating.
This is the basic mode, and other modes should be selected for setting
changes and other function settings.
Setting the ON and OFF points of the Pressure switch.
•Operation
When the pressure exceeds the set point, the Pressure switch will be
turned ON.
When the pressure falls below the set point by the amount of hysteresis
or more, the Pressure switch will be turned OFF.
The default setting of the output set value is the central value between
the atmospheric pressure and the upper limit of the rated pressure
range.
If this condition, shown below, is acceptable, then keep these settings.
6 Pressure Setting (continued)
6.2 Operation
[Hysteresis mode]
1, Press the button once in measurement mode.
2, [P_1] or [n_1] and the set value are displayed in turn.
3, Press the or button to change the set value.
The button is to increase and the button is to decrease.
•Press the button once to increase by one digit, and press it
continuously to keep increasing the set value.
•Press the button once to decrease by one digit, and press it
continuously to keep decreasing the set value.
4, Press the button to finish the setting.
For models with 2 outputs, [P_2] or [n_2] will be displayed. Set as
above.
The Pressure switch operates within a set pressure range (from P1L to
P1H) during window comparator
mode. Set P1L (switch lower limit) and P1H (switch upper limit) with the
setting procedure above.
(When reversed output is selected, [n1L] and [n1H] are displayed.)
Zero clear of Display
The display is reset to zero when the and buttons are pressed
simultaneously for 1 second. For the first operation, always perform zero
clear with no pressure applied.
7 Function Setting
In measurement mode, press the button for 2 seconds or longer to
display [F 0]. Select to display the function to be changed, [F ## ].
Press the button for 2 seconds or longer in function selection mode
to return to measurement mode.
*: Some functions are not available depending on part number. All functions are
displayed with [F ##] followed by the function description. If a function is not
available, the function is displayed as [---].
7.1 Default Function settings
At the time of shipment, the following settings are provided.
If this condition is acceptable, then keep these settings.
To change the settings, enter function selection mode.
•[F 0] Unit selection function.