socomec DELPHYS MX User manual

Jbus/Modbus Serial Link
DELPHYS MX / MP / ELITE
Installation and operating manual GB

FOREWORD
We thank you for the trust you have in our Uninterruptible Power Systems.
This equipment is fitted with up to date technology. Rectifier and inverter subsets are provided with power semicon-
ductors (IGBT) including a digital micro-controller.
Our equipment complies with IEC EN 62040-2 standard.
CAUTION : “This is a product for restricted sales distribution to informed partners. Installation restrictions or addi-
tional measures may be needed to prevent disturbances”.
SOCOMEC UPS reserves the right to modify their specifications at any time as far as this con-
tributes to technical progress.
SAVETY REQUIREMNENT
Using conditions:
Do read carefully these operation instructions before using the JBUS/MODBUS interface.
Whatever the repairs, they must be made only by authorised staffs, which have been suitably trained. It is recom-
mended that the ambient temperature and humidity of the UPS environment are maintained below the values
specified by the manufacturer.
UPS operating reference
Respect the safety requirements.
Do read carefully the operation instructions of DELPHYS MX / MP.
For an optimal operation, it is recommended to maintain the ambient temperature and humidity of the UPS envi-
ronment below the values specified by the manufacturer.
This equipment meets the requirements of the European directives applied to this product. As a consequence it is
labelled as follows:
ENVIRONMENT
Recycling of electrical products and equipment.
Provision is made in European countries to break up and recycle materials making up the system. The various components
must be disposed of in accordance with the legal provisions in force in the country where the system is installed.
UPS/NTA GB/DMX-DMP JBUS.D
Page 1/22

UPS/NTA GB/DMX-DMP JBUS.D Page 2 / 22
INTRODUCTION
General purpose
This document provides required information of the J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S protocol serial link.
Before connecting a supervision equipment or BMS system (Building management system) to the UPS, it is
necessary to install and set up the serial interface.
This interface is located in the DELPHYS MX / MP « com-slot », and should be set through the control
panel or via the graphic touch screen (optional).
DELPHYS MX / MP is able to manage up to 2 independent J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S serial links.
JBUS/MODBUS protocol
This document does not explain the J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S
protocol management. Please refer on
www.modbus.org web site for more information.
The DELPHYS MX / MP
J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S uses the following functions :
- function 3 for reading Input Registers (16 bits),
- function 6 for writing single Registers (to control UPS).
The data field is composed of words, defined by a MSB (most significant byte) and a LSB (lowest
significant byte), and displayed in the following order on the serial link.
1 WORD DATA
b7MSB b0b7LSB b0
b15 b0
Data decoding
Status and alarms Information
This information are coding in bit. This means that 1 word defines 16 information. If the related bit is set to
1, this information is active or true.
Measurements and counters data
1 word defines a measurement or a counter. Some values are numeric decimal signed or unsigned (0 to
65535 or from -32767 to 32767), or in hexadecimal (0x0000 to 0xFFFF).
Compatibility with other SOCOMEC UPS products
In order to be fully compatible with other SOCOMEC UPSproducts such as MASTERYS, DELPHYS DS
and DELPHYS DS elite, DELPHYS MX / MP proposes the same J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S
tables.

UPS/NTA GB/DMX-DMP JBUS.D Page 3 / 22
JBUS/MODBUS SERIAL INTERFACE INSTALLATION INSIDE DELPHYS MX / MP
‘Com-Slots’ localisation
The « Com-Slots » integrates all communication interfaces, and it is located at the bottom of the UPS, on
the right side.
Slots 5 and 6 are dedicated to J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S
serial
interfaces.
Slots 1 to 4 are used for the alarm report boards, 3 inputs and 4 programmable relays (ADC).
JBUS/MODBUS serial interface plug in
The serial interface should be plugged in the corresponding slot, and fixed with 2 crews.
DELPHYS MX / MP is able to manage up to 2 independent J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S interfaces. Each interface can
be set differently, like the slave numbers.
JBUS interface in parallel system configuration
There is only one J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S serial link interface for a parallel system configuration. One serial
interface is used for the whole installation. The access to the data of the UPS module or unit is
managed by the table addressing1.
1See chapter 5

UPS/NTA GB/DMX-DMP JBUS.D Page 4 / 22
Connections and cablings
NOTE : there is only one connection per interface (RS232 or RS422 or RS485)
9
RS232 connection
)Standard PC connection
)Sub-D 9 pins connector
)Pin 2 : Rx
)Pin 3 : Tx
)Pin 5 : GND
9
Isolated RS485 connection
)2 wires connection
)« dip-switch c» allows connecting the terminal resistor
)Isolation via “opto-coupler”
)2 polarization resistors could be removed easily (if needed).
9
Isolated RS422 connection
)4 wires connection
)« dip-switch cand d» allows connecting the terminal resistors
)Isolation via “opto-coupler”
)4 polarization resistors could be removed easily (if needed).
RECOMMENDATIONS
Before making any connection, please check the cabling. A wrong connection or cabling can damage
the serial link interface.
RTX-
RTX+
TX-
TX+
RX+
RX-

UPS/NTA GB/DMX-DMP JBUS.D Page 5 / 22
JBUS/MODBUS LINK
Serial link 1 and 2 default settings
Baud rate: 9600 bauds
Parity: NONE
Data: 8 bits
Stop: 1 bit
Slave: 1
The serial link settings can be set from the control panel or from the graphic touch screen.
How to change the serial link settings ?
Available baud rate: 1200 - 2400 - 4800 - 9600 - 19200 bauds
Parity: EVEN - ODD - NONE
Slave number: 1 to 32
Settings screen of the control panel (last menu)
SETT ING 1
bauds : 9600
p
ari t
y
:NONE
slave : 001
JBUS L INK
Ð
Select the settings with
Change the value with and
Graphic touch screen:
J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S 1settings are linked to the interface located in slot 5.
J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S 2settings are linked to the interface located in slot 6.
The serial interface should be activated by the CIM or the factory during the UPS commissioning.

UPS/NTA GB/DMX-DMP JBUS.D Page 6 / 22
JBUS/MODBUS Protocol
Reminder:
The J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S protocol available on DELPHYS MX / MP is slave and in RTU mode.
It uses the function 3 as ‘read registers’ and the function 6 as ‘write register’.
The slave number is set via the control panel or via the graphic touch screen.
Conventions
The table addresses are written in hexadecimal, beginning with ‘0x’.
Some PLC systems request a relative address starting from 400 (0x0190) or 40001 (0x9C41), on this
address it’s necessary to add the first address of the J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S table.
Frame errors management:
In case of wrong data request, the UPS answers with the following frame error :
Error function code Error code Cause
80 + code function 1 Function error
80 + code function 2 Addresses error
80 + code function 3 Wrong data
80 + code function 6 busy
80 + code function 8 Write register error

UPS/NTA GB/DMX-DMP JBUS.D Page 7 / 22
SINGLE UNIT UPS JBUS/MODBUS TABLES
JBUS/MODBUS tables
§ TABLE Start
addresses Table length in
words JBUS/MODBUS
FUNCTION
1 UPS Identification 0x1000 12 3 READ
2 Date and hours 0x1360 4 3 READ
3 UPS Configurations 0x10E0 32 3 READ
4 Status (96 bits) 0x1020 6 3 READ
5 Alarms (64 bits) 0x1040 4 3 READ
6 Measurements 0x1060 48 3 READ
7 Controls permission 0x15C0 2 3 READ
8 UPS Controls 0x15B0 1 6 WRITE
How to read data:
The identification, status and alarms tables should be read completely (this means the number of word to
read is equal to the table length).
The measurements table could be read word by word or per group, without exceed the length of the table.
(from 0x1060 to 0x108F).
Incoming data structure:
Example of 6 words
1 2 3 4 5 6 7 8 9 10 11 12
MSB 0 LSB 0 MSB 1 LSB 1 MSB 2 LSB 2 MSB 3 LSB 3 MSB 4 LSB 4 MSB 5 LSB 5
WORD 0 WORD 1 WORD 2 WORD 3 WORD 4 WORD 5
b15 b0b
15 b0b
15 b0b
15 b0b
15 b0b
15 b0
S15 S00 S31 S16 S47 S32 S63 S48 S79 S64 S95 S80
A15 A00 A31 A16 A47 A32 A63 A48
M00 M01 M02 M03 M04 M05
‘Concentrator mode’ in parallel system configuration
The above
J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S
table can be used in case of a parallel system configuration. The TOR data
from all units or modules are managed in order to create a ‘virtual single unit’. The logic combination ‘OR’ is
used to create the single unit data base, except following states and alarms :
Information
Combination if redundant UPS Combination if not redundant UPS
S00 OR AND
S05 AND OR
S15 AND OR
A02 AND OR
A07 AND OR
A31 AND OR

UPS/NTA GB/DMX-DMP JBUS.D Page 8 / 22
1. UPS IDENTIFICATION: Address 0x1000, 12 words
CODE DESCRIPTION Number of
WORDS ADDRESS Type Remarks
I00 UPS CODE 1 WORD 0x1000 Numeric value 515 = DELPHYS MX
516 = DELPHYS MX elite
I01 UPS Power 1 WORD 0x1001 Numeric value In kVA * 10
5000 = 500kVA
I02 Module
number 1 WORD 0x1002 Numeric value 1
I03 Serial
number
5 WORDS 0x1003 1 word = 2 ASCII
codes LSB = 1. char
MSB = 2. char
UPS Code:CCCCCCAaYYYXXXXXXNNn
Code read :aXXXXXXXXn
I04 Reserved 1 WORD 0x1008 0
I05 Reserved 1 WORD 0x1009 0
I06 Reserved 1 WORD 0x100A 0
I07 Reserved 1 WORD 0x100B 0
2. DATE & HOURS: Address 0x1360, 4 words
CODE DESCRIPTION Number of
words Addresses Type Remarks
D00 Minutes /
seconds 1 0x1360 Byte value MSB = minutes
LSB = seconds
D01 Hours / day 1 0x1361 Byte value MSB = day
LSB = hours
D02 Month / day
of
week
1 0x1362 Byte value MSB = month
LSB = day of the week
1=Monday
7=Sunday
D03 year 1 0x1363 00 = 2000
3. UPS CONFIGURATION: Address 0x10E0, 32 words
Code Measurements Unit Address REMARKS
T00 Nominal start input voltage V 0x10E0
T01 Nominal start output
voltage V 0x10E1
T02 Nominal input frequency Hz 0x10E2
T03 Nominal output frequency Hz 0x10E3
T04 Version value * 100 0x10E4 100 = V1.00
T05 0x10E5
T06 0x10E6
TO7 0x10E7
T08 Nominal battery capacity Ah * 10 0x10E8 3000 = 300Ah
T09 Number of battery elements 0x10E9
T10 Reserved 0x10EA Set to 0xFFFF (-1)
T11 Reserved 0x10EB Set to 0xFFFF (-1)
T12 Reserved 0x10EC
T13 Working mode Bits field
0x10ED b0 not used
b1 = with battery
b2 = Gen Set present
b3 = ’energy saver’ enabled
T14 Redundancy level (only in
//) value 0x10EE 0 = without
1 = N+1
T15 Reserved 0x10EF 100
T16
..
T31
Reserved 0x10F0
0x10FF
Set to 0xFFFF (-1)

UPS/NTA GB/DMX-DMP JBUS.D Page 9 / 22
4. STATUS: Address 0x1020, 6 words
CODE DESCRIPTION BIT ADDRESS REMARKS
S00 Rectifier Input supply present 0 0x1020
S01 Inverter ON 1 0x1020
S02 Rectifier ON 2 0x1020
S03 Load protected by inverter 3 0x1020
S04 Load on automatic bypass 4 0x1020
S05 Load on battery 5 0x1020
S06 Remote controls disable 6 0x1020 0 = controls enabled
S07 Eco-mode ON 7 0x1020 If this function is available
S08 8 0x1020
S09 9 0x1020
S10 10 0x1020
S11 11 0x1020
S12 12 0x1020
S13 13 0x1020
S14 Battery test failed 14 0x1020
S15 Battery near end of backup time 15 0x1020 IMMINENT STOP and end of backup
time
S16 Battery discharged 0 0x1021
S17 Battery OK 1 0x1021 No alarm and battery circuit
closed
S18 2 0x1021
S19 3 0x1021
S20 4 0x1021
S21 5 0x1021
S22 6 0x1021
S23 7 0x1021
S24 8 0x1021
S25 9 0x1021
S26 Bypass input supply present 10 0x1021
S27 Battery charging 11 0x1021
S28 Bypass input frequency out of
tolerance 12 0x1021
S29 13 0x1021 Set to 1
S30 UPS on parallel system 14 0x1021 = 0 for single unit
S31 15 0x1021
S32 Unit operating (available or
coupled) 0 0x1022
S33 1 0x1022
S34 2 0x1022
S35 3 0x1022
S36 4 0x1022
S37 5 0x1022
S38 External Input 1 6 0x1022 IN1 ADC slot 1 or 2
S39 External Input 2 7 0x1022 IN2 ADC slot 1 or 2
S40 External Input 3 8 0x1022 IN3 ADC slot 1 or 2
S41 External Input 4 9 0x1022 IN1 ADC slot 3
S42 Controls permission table manage 10 0x1022 Set to 1
S43 11 0x1022
S44 12 0x1022
S45 13 0x1022
S46 Operating on Gen Set 14 0x1022
S47 15 0x1022
S48 Maintenance mode active 0 0x1023
S49 End of the fist maintenance period 1 0x1023
S50 2 0x1023
S51 3 0x1023
S52 4 0x1023
S53 5 0x1023
S54 6 0x1023
S55 7 0x1023
S56 8 0x1023
S57 9 0x1023
S58 10 0x1023
S59 11 0x1023
S60 12 0x1023
S61 13 0x1023
S62 14 0x1023
S63 15 0x1023
…/…

UPS/NTA GB/DMX-DMP JBUS.D Page 10 / 22
…/…
CODE DESCRIPTION BIT ADRESSE REMARQUES
S64 Boost charge ON 0 0x1024
S65 1 0x1024
S66 Inverter switch closed 2 0x1024
S67 Bypass breaker closed 3 0x1024
S68 Maintenance bypass breaker closed (Q5) 4 0x1024
S69 Remote maintenance bypass breaker closed 5 0x1024
S70 Output breaker closed (Q3) 6 0x1024
S71 Q21 closed 7 0x1024
S72 Q22 closed 8 0x1024
S73 Unit working 9 0x1024 On inverter or on bypass
S74 10 0x1024
S75 11 0x1024
S76 normal mode active 12 0x1024 No Eco-mode No ‘energy-
saver’ active
S77 13 0x1024
S78 14 0x1024
S79 15 0x1024
S80 0 0x1025
S81 1 0x1025
S82 2 0x1025
S83 3 0x1025
S84 4 0x1025
S85 5 0x1025
S86 6 0x1025
S87 7 0x1025
S88 8 0x1025
S89 9 0x1025
S90 10 0x1025
S91 11 0x1025
S92 12 0x1025
S93 13 0x1025
S94 14 0x1025
S95 15 0x1025
Status without description are not managed by DELPHYS MX / MP.

UPS/NTA GB/DMX-DMP JBUS.D Page 11 / 22
5. ALARMS: Address 0x1040, 4 words
CODE DESCRIPTION BIT ADRESSE REMARQUES
A00 General Alarm 0 0x1040 Activated if one alarm
active
A01 Battery failure 1 0x1040 Battery fault, room and
circuit open synthesis
A02 UPS overload 2 0x1040
A03
A04 Control failure (com, internal supply…) 4 0x1040 Ctrl board critical alarm
A05 Rectifier input supply out of tolerance 5 0x1040
A06 Bypass input supply out of tolerance 6 0x1040
A07 Over temperature alarm 7 0x1040
A08 Maintenance bypass closed 8 0x1040 Q5 closed
A09 9 0x1040
A10 Battery charger fault 10 0x1040
A11 11 0x1040
A12 12 0x1040
A13 13 0x1040
A14 14 0x1040
A15 15 0x1040
A16 0 0x1041
A17 Improper condition of use (Q3 and Q5
closed) 1 0x1041 Maintenance bypass alarm
A18 Inverter stopped for overload
(or bypass transfer) 2 0x1041 Imminent stop and
overload
A19 Microprocessor control system 3 0x1041 Ctrl board preventive Al.
A20 4 0x1041
A21 Synchronisation fault (PLL fault) 5 0x1041 ACS source fault
A22 Rectifier input supply fault 6 0x1041
A23 Rectifier preventive alarm 7 0x1041
A24 8 0x1041
A25 Inverter preventive alarm 9 0x1041
A26 Charger general alarm 10 0x1041
A27 11 0x1041
A28 12 0x1041
A29 Bypass preventive alarm 13 0x1041
A30 14 0x1041
A31 Imminent STOP 15 0x1041
A32 Unit 1 general alarm 0 0x1042
A33 1 0x1042
A34 2 0x1042
A35 3 0x1042
A36 4 0x1042
A37 5 0x1042
A38 External alarm 6 0x1042 To configure
A39 7 0x1042
A40 8 0x1042
A41 9 0x1042
A42 e-Service 10 0x1042 NOT AVAILABLE
A43 11 0x1042
A44 Servicing alarm 12 0x1042
A45 Automatic and manual transfer disable 13 0x1042
A46 Automatic transfer disable 14 0x1042
A47 Battery room alarm 15 0x1042
A48 Maintenance bypass alarm 0 0x1043
A49 Battery discharged 1 0x1043
A50 2 0x1043
A51 Synoptic alarm 3 0x1043
A52 Rectifier fault 4 0x1043 Critical alarm
A53 5 0x1043
A54 Inverter fault 6 0x1043 Critical alarm
A55 7 0x1043
A56 8 0x1043
A57 9 0x1043
A58 ESD activated 10 0x1043
A59 Battery circuit open 11 0x1043
A60 12 0x1043
A61 13 0x1043
A62 Bypass critical alarm 14 0x1043
A63 15 0x1043
Alarms without description are not managed by DELPHYS MX / MP.

UPS/NTA GB/DMX-DMP JBUS.D Page 12 / 22
6. MEASUREMENTS: Address 0x1060, up to 48 words
Code Description Unit ADDRESSES REMARKS
M00 Load rate phase1 % 0x1060
M01 Load rate phase 2 % 0x1061 Set to 0xFFFF if one phase
M02 Load rate phase 3 % 0x1062 Set to 0xFFFF if one phase
M03 UPS load rate % 0x1063
M04 Battery Capacity % 0x1064
M05 Battery Capacity Ah*10 0x1065
M06 Input bypass voltage phase 1 V 0x1066
M07 Input bypass voltage phase 2 V 0x1067 Set to 0xFFFF if one phase
M08 Input bypass voltage phase 3 V 0x1068 Set to 0xFFFF if one phase
M09 Output voltage phase 1 V 0x1069
M10 Output voltage phase 2 V 0x106A Set to 0xFFFF if one phase
M11 Output voltage phase 3 V 0x106B Set to 0xFFFF if one phase
M12 0x106C Set to 0xFFFF (-1)
M13 0x106D Set to 0xFFFF (-1)
M14 0x106E Set to 0xFFFF (-1)
M15 Output current phase 1 A*10 0x106F
M16 Output current phase 2 A*10 0x1070 Set to 0xFFFF if one phase
M17 Output current phase 3 A*10 0x1071 Set to 0xFFFF if one phase
M18 Input bypass frequency Hz*10 0x1072
M19 Output frequency Hz*10 0x1073
M20 Battery voltage (+) V*10 0x1074
M21 Battery voltage (-) V*10 0x1075 Set to 0
M22 Ambient Temperature °C 0x1076
M23 Remaining backup time Minutes 0x1077 Set when the load is on
battery
M24 Battery current A*10 0x1078
M25 0x1079 Set to 0xFFFF (-1)
M26 0x107A Set to 0xFFFF (-1)
M27 0x107B Set to 0xFFFF (-1)
M28 Rectifier voltage (+) V 0x107C
M29 Rectifier voltage (-) V 0x107D Set to 0
M30 0x107E Set to 0xFFFF (-1)
M31 0x107F Set to 0xFFFF (-1)
M32 0x1080 Set to 0xFFFF (-1)
M33 Rectifier input voltage phase 1 V 0x1081
M34 Rectifier input voltage phase 2 V 0x1082
M35 Rectifier input voltage phase 3 V 0x1083
M36 UPS output power kW*10 0x1084
M37 Output power phase 1 kVA*10 0x1085
M38 Output power phase 2 kVA*10 0x1086 Set to 0xFFFF if one phase
M39 Output power phase 3 kVA*10 0x1087 Set to 0xFFFF if one phase
M40 0x1088 Set to 0xFFFF (-1)
M41 0x1089 Set to 0xFFFF (-1)
M42 0x108A Set to 0xFFFF (-1)
M43 0x108B
M44 0x108C
M45 0x108D
M46 0x108E
M47 0x108F

UPS/NTA GB/DMX-DMP JBUS.D Page 13 / 22
7. ENABLED CONTROLS TABLE: Address 0x15C0, 2 words
CODE DESCRIPTION BIT ADDRESSES REMARKS
C00 0
C01 1
C02 2
C03 Eco-mode enabled 3 0x15C0
C04 normal Mode enabled 4 0x15C0
C05 5
C06 6
C07 7
C08 8
C09 9
C10 Automatic Bypass transfer enabled 10 0x15C0
C11 Inverter transfer enabled 11 0x15C0
C12 12
C13 13
C14 14
C15 15
C16 Battery test enabled 0 0x15C1
C17 1
C18 2
C19 3
C20 4
C21 5
C22 6
C23 7
C24 8
C25 9
C26 10
C27 11
C28 12
C29 13
C30 14
C31 15
8. CONTROLS SEND TO UPS: Address 0x15B0, write 1 words
For a remote UPS control, it is necessary to set the serial interface in “remote” mode using the Human
Machine Interface.
Local controls of the control panel or graphic touch screen are no more available.
The control table below shows if the selected control is allowed or not. If the control sent to the UPS is not
allowed, the function will be ignored.
Controls available by JBUS/MODBUS connection:
Code Controls Value to write ADDRESS REMARKS
C03 Eco-mode 0x0003 0x15B0
C04 Normal mode 0x0004 0x15B0
C10 Automatic bypass transfer 0x000A 0x15B0
C11 Inverter transfer 0x000B 0x15B0
C16 Battery test 0x0010 0x15B0

UPS/NTA GB/DMX-DMP JBUS.D Page 14 / 22
JBUS/MODBUS TABLES IN PARALLEL SYSTEM CONFIGURATION
Reminder
In UPS parallel system configuration, there is only one J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S interface. The addresses mapping
gives the possibility to read data from each module and common bypass. There is no link between the
J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S
salve number and the UPS unit or module one.
The interface is plugged in the ‘com-slots’ of the common cabinet is case of central bypass installation or in
the UPS unit 1 “com slots” in case of modular system (see bellow).
How to read data:
The identifications, status and alarms tables should be read completely in one JBUS/MODBUS frame; this
means the number of word to read is equal to the table length.
The measurements table could be read word by word, without exceed the length of the table. (from 0x1060
to 0x108F).
Incoming data structure:
Example of 6 words
1 2 3 4 5 6 7 8 9 10 11 12
MSB 0 LSB 0 MSB 1 LSB 1 MSB 2 LSB 2 MSB 3 LSB 3 MSB 4 LSB 4 MSB 5 LSB 5
WORD 0 WORD 1 WORD 2 WORD 3 WORD 4 WORD 5
b15 b0b
15 b0b
15 b0b15 b0b15 b0b
15 b0
S15 S00 S31 S16 S47 S32 S63 S48 S79 S64 S95 S80
A15 A00 A31 A16 A47 A32 A63 A48
M00 M01 M02 M03 M04 M05
J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S link setting
The setting of the link is made from the control panel or from the graphic touch screen of the common
cabinet or of the UPS unit 1.

UPS/NTA GB/DMX-DMP JBUS.D Page 15 / 22
JBUS/MODBUS tables in parallel system configuration with central bypass (AC)
TABLE Start addresses Table length in words JBUS/MODBUS
FUNCTION
Identification 0x8000 12 3 READ
Configurations 0x80E0 32 3 READ
Date and hours 0x8360 4 3 READ
States CC ( 96 bits) 0x8020 6 3 READ
Alarms CC ( 64 bits) 0x8040 4 3 READ
Measurements CC 0x8060 48 3 READ
States module 1 ( 96 bits) 0x2020 6 3 READ
Alarms module 1 ( 64 bits) 0x2040 4 3 READ
Measurements module 1 0x2060 48 3 READ
States module 2 ( 96 bits) 0x3020 6 3 READ
Alarms module 2 ( 64 bits) 0x3040 4 3 READ
Measurements module 2 0x3060 48 3 READ
States module 3 ( 96 bits) 0x4020 6 3 READ
Alarms module 3 ( 64 bits) 0x4040 4 3 READ
Measurements module 3 0x4060 48 3 READ
States module 4 ( 96 bits) 0x5020 6 3 READ
Alarms module 4 ( 64 bits) 0x5040 4 3 READ
Measurements module 4 0x5060 48 3 READ
States module 5 ( 96 bits) 0x6020 6 3 READ
Alarms module 5 ( 64 bits) 0x6040 4 3 READ
Measurements module 5 0x6060 48 3 READ
States module 6 ( 96 bits) 0x7020 6 3 READ
Alarms module 6 ( 64 bits) 0x7040 4 3 READ
Measurements module 6 0x7060 48 3 READ
Controls permission 0x15C0 2 3 READ
UPS Controls 0x15B0 1 6 WRITE
JBUS/MODBUS table in modular parallel system
TABLE
Start addresses
Table length in words JBUS/MODBUS
FUNCTION
Identification 0x1000 12 3 READ
Configurations UPS 0x10E0 32 3 READ
Date and hours 0x1360 4 3 READ
Output UPS Measurements 0x8060 48 3 READ
States unit 1 ( 96 bits) 0x2020 6 3 READ
Alarms unit 1 ( 64 bits) 0x2040 4 3 READ
Measurements unit 1 0x2060 48 3 READ
States unit 2 ( 96 bits) 0x3020 6 3 READ
Alarms unit 2 ( 64 bits) 0x3040 4 3 READ
Measurements unit 2 0x3060 48 3 READ
States unit 3 ( 96 bits) 0x4020 6 3 READ
Alarms unit 3 ( 64 bits) 0x4040 4 3 READ
Measurements unit 3 0x4060 48 3 READ
States unit 4 ( 96 bits) 0x5020 6 3 READ
Alarms unit 4 ( 64 bits) 0x5040 4 3 READ
Measurements unit 4 0x5060 48 3 READ
States unit 5 ( 96 bits) 0x6020 6 3 READ
Alarms unit 5 ( 64 bits) 0x6040 4 3 READ
Measurements unit 5 0x6060 48 3 READ
States unit 6 ( 96 bits) 0x7020 6 3 READ
Alarms unit 6 ( 64 bits) 0x7040 4 3 READ
Measurements unit 6 0x7060 48 3 READ

UPS/NTA GB/DMX-DMP JBUS.D Page 16 / 22
1. UPS IDENTIFICATION: Address 0x1000 or 0x8000, 12 words
CODE DESCRIPTION Number of
WORDS ADDRESS Type Remarks
I00 UPS CODE 1 WORD 0x1000 Numeric value 1018 = DELPHYS MX MODULAIRE
1019 = DELPHYS MX // common by-pass
1020 = DELPHYS MX elite modular
1021 = DELPHYS MX elite // by-pass
I01 UPS Power 1 WORD 0x1001 Numeric value In kVA * 10
5000 = 500kVA
I02 Module
number 1 WORD 0x1002 Numeric value 1
I03 Serial
number
5 WORDS 0x1003 1 word = 2 ASCII
codes LSB = 1. char
MSB = 2. char
UPS Code:CCCCCCAaYXXXXXXXXNNn
Code read :aXXXXXXXXn
I04 Reserved 1 WORD 0x1008 0
I05 Reserved 1 WORD 0x1009 0
I06 Reserved 1 WORD 0x100A 0
I07 Reserved 1 WORD 0x100B 0
2. DATE & HOURS: Address 0x1360 or 0x8360, 4 words
CODE DESCRIPTION Number of
words Addresses Type Remarks
D00 Minutes /
seconds 1 0x1360 Byte value MSB = minutes
LSB = seconds
D01 Hours / day 1 0x1361 Byte value MSB = day
LSB = hours
D02 Month / day of
week 1 0x1362 Byte value MSB = month
LSB = day of the week
1=Monday
7=Sunday
D03 year 1 0x1363 00 = 2000
3. USP CONFIGURATION: Address 0x10E0 or 0x80E0, 32 words
Code Measurements Unit Address REMARKS
T00 Nominal start input voltage V 0x10E0
T01 Nominal start output voltage V 0x10E1
T02 Nominal input frequency Hz 0x10E2
T03 Nominal output frequency Hz 0x10E3
T04 Version value * 100 0x10E4 100 = V1.00
T05 0x10E5
T06 0x10E6
TO7 0x10E7
T08 Nominal battery capacity Ah * 10 0x10E8 3000 = 300Ah
T09 Number of battery elements 0x10E9
T10 Reserved 0x10EA Set to 0xFFFF (-1)
T11 Reserved 0x10EB Set to 0xFFFF (-1)
T12 Reserved 0x10EC
T13 Working mode Bits field
0x10ED b0 not used
b1 = with battery
b2 = Gen Set present
b3 = ’energy saver’ enabled
T14 Redundancy level value 0x10EE 0 = without
1 = N+1
T15 Reserved 0x10EF 100
T16
..
T31
Reserved 0x10F0
0x10FF
Set to 0xFFFF (-1)

UPS/NTA GB/DMX-DMP JBUS.D Page 17 / 22
Preliminary remarks
The following J
JB
BU
US
S/
/M
MO
OD
DB
BU
US
S addresses tables only indicate the LSB byte, the MSB depends of the
module number requested.
An ‘X’ in the ‘CC’ (central bypass), ‘Module’ or ‘Unit’ column means that this information is available on
this equipment.
Please refer to § 4.4 for more details.
4. STATUS : Address 0x20, 6 words
CODE DESCRIPTION BIT ADDRESS LSB
byte CC Module Unit
S00 Rectifier Input supply present 0 0x20 X X
S01 Inverter ON 1 0x20 X X
S02 Rectifier ON 2 0x20 X X
S03 Load protected by inverter 3 0x20 X X X
S04 Load on automatic bypass 4 0x20 X X
S05 Load on battery / Battery discharging 5 0x20 X X
S06 Remote controls disable 6 0x20 X
S07 Eco-mode ON 7 0x20 X X X
S08 8 0x20
S09 9 0x20
S10 10 0x20 X X
S11 11 0x20
S12 12 0x20
S13 13 0x20
S14 Battery test failed 14 0x20 X X
S15 Battery near end of backup time 15 0x20 X X
S16 Battery discharged 0 0x21 X X
S17 Battery OK 1 0x21 X X
S18 2 0x21
S19 3 0x21
S20 4 0x21
S21 5 0x21
S22 6 0x21
S23 7 0x21 X X
S24 8 0x21 X X
S25 9 0x21
S26 Bypass input supply present 10 0x21 X X
S27 Battery charging 11 0x21 X X
S28 Bypass input frequency out of
tolerance 12 0x21 X X
S29 13 0x21
S30 UPS on parallel system 14 0x21 X X X
S31 15 0x21
S32 Unit 1 operating 0 0x22 X X
S33 Unit 2 operating 1 0x22 X X
S34 Unit 3 operating 2 0x22 X X
S35 Unit 4 operating 3 0x22 X X
S36 Unit 5 operating 4 0x22 X X
S37 Unit 6 operating 5 0x22 X X
S38 External Input 1 6 0x22 X X X
S39 External Input 2 7 0x22 X X X
S40 External Input 3 8 0x22 X X X
S41 External Input 4 9 0x22
S42 Controls permission table manage 10 0x22 X X X
S43 11 0x22
S44 12 0x22
S45 13 0x22
S46 Operating on Gen Set 14 0x22 X X X
S47 15 0x22
…/…

UPS/NTA GB/DMX-DMP JBUS.D Page 18 / 22
…/…
CODE DESCRIPTION BIT ADDRESS
LSB byte CC Module Unit
S48 Maintenance mode active 0 0x23 X X X
S49 End of the fist maintenance period 1 0x23
S50 2 0x23
S51 3 0x23
S52 4 0x23
S53 5 0x23
S54 6 0x23
S55 7 0x23
S56 8 0x23
S57 9 0x23
S58 10 0x23
S59 11 0x23
S60 12 0x23
S61 13 0x23
S62 14 0x23
S63 15 0x23
S64 Boost charge ON 0 0x24 X X
S65 1 0x24 X X
S66 Inverter switch closed 2 0x24 X X
S67 Bypass breaker closed 3 0x24
S68 Maintenance bypass breaker closed (Q5) 4 0x24 X X
S69 Remote maintenance bypass breaker closed 5 0x24 X X
S70 Output breaker closed (Q3) 6 0x24 X X X
S71 Q21 closed 7 0x24 X X
S72 Q22 closed 8 0x24 X X
S73 Unit working 9 0x24 X X
S74 Energy saver activated 10 0x24 X X X
S75 11 0x24
S76 normal mode active 12 0x24 X X X
S77 13 0x24
S78 14 0x24
S79 15 0x24
S80 0 0x25
S81 1 0x25
S82 2 0x25
S83 3 0x25
S84 4 0x25
S85 5 0x25
S86 6 0x25
S87 7 0x25
S88 8 0x25
S89 9 0x25
S90 10 0x25
S91 11 0x25
S92 12 0x25
S93 13 0x25
S94 14 0x25
S95 15 0x25

UPS/NTA GB/DMX-DMP JBUS.D Page 19 / 22
5. ALARMS: Address 0x40, 4 words
CODE DESCRIPTION BIT ADRESSE
basse AC Module Unite
A00 General Alarm 0 0x40 X X X
A01 Battery failure 1 0x40 X X
A02 UPS overload 2 0x40 X X X
A03
A04 Control failure - critical alarm 4 0x40
A05 Rectifier input supply out of tolerance 5 0x40 X X X
A06 Bypass input supply out of tolerance 6 0x40 X X
A07 Over temperature alarm 7 0x40 X X X
A08 Maintenance bypass closed 8 0x40 X X
A09
A10 Battery charger fault X X
A11
A12
A13
A14
A15
A16
A17 Improper condition of use (Q3 and Q5 closed) 1 0x41 X X
A18 Inverter stopped for overload
(or bypass transfer) 2 0x41
X X
A19 Microprocessor control system - preventive al. 3 0x41 X X X
A20
A21 PLL fault 5 0x41 X X
A22 Rectifier input supply fault 6 0x41 X X
A23 Rectifier preventive alarm 7 0x41 X X
A24
A25 Inverter preventive alarm 9 0x41 X X
A26 Charger general alarm 10 0x41 X X
A27
A28
A29 Bypass preventive alarm 13 0x41 X X X
A30
A31 Imminent STOP 15 0x41 X X X
A32 Unit 1 general alarm 0 0x42 X X
A33 Unit 2 general alarm 1 0x42 X X
A34 Unit 3 general alarm 2 0x42 X X
A35 Unit 4 general alarm 3 0x42 X X
A36 Unit 5 general alarm 4 0x42 X X
A37 Unit 6 general alarm 5 0x42 X X
A38 External alarm 6 0x42 X X X
A39
A40
A41
A42 e-Service 10 0x42
A43 redundancy loss 11 0x42 X X
A44 Servicing alarm 12 0x42 X
A45 Automatic and manual transfer disable 13 0x42 X X
A45 Automatic transfer disable 14 0x42 X X
A47 Battery room alarm 15 0x42 X X
A48 Maintenance bypass alarm 0 0x43 X X
A49 Battery discharged 1 0x43 X X
A50 2 0x43 X X
A51 Synoptic alarm 3 0x43
A52 Rectifier fault - critical alarm 4 0x43 X X
A53
A54 Inverter fault - critical alarm 6 0x43 X X
A55
A56
A57
A58 ESD activated 10 0x43 X X X
A59 Battery circuit open 11 0x43 X X
A62 Bypass critical alarm 14 0x43 X X X
For more detail, please refer to the single unit UPS table §1.5
Other manuals for DELPHYS MX
2
This manual suits for next models
2
Table of contents
Popular Computer Hardware manuals by other brands

Intel
Intel Xeon Guidelines

VIA Technologies
VIA Technologies VAB-820 quick start guide

König Electronic
König Electronic CMP-WNUSB50 manual

ICP vortex Corporation
ICP vortex Corporation 32-Bit 66MHz low profile PCI Wide/Ultra160... specification

WBS
WBS M6205A-3G user manual

Phytec
Phytec phyCORE-AM335 Series Hardware manual

Vantec
Vantec UGT-CR945 installation guide

Sony
Sony PCWA-C800S Read This First Software guide

MikroTik
MikroTik RouterBOARD 500 Series Quick setup guide and warranty information

Targus
Targus USB 3.0 ExpressCard 410-2207-001A user guide

Alphacool
Alphacool GPX PRO - N 2080 M04 manual

Avago
Avago LSI STORAGE SAS 9302-16e Quick installation guide