socomec ATI 250 A Owner's manual

Transfer Panel ATI
Technical Instruction Manual

2SOCOMEC - Réf.: 678 623 G GB
GENERAL SAFETY INSTRUCTIONS
a. This leaflet provides indispensable
instructions in terms of the safety,
the connection and the operation of
the automatic transfer switch.
b. This system must exclusively be
installed by specialised, qualified
personnel.
c. Before making the connections, it is
essential that the earth cable be con-
nected.
d. Keep the cabinet clean using a dry
cloth.
e. It is recommended that this leaflet
be kept in a place easily accessible
to all those who may need it.
f. The maintenance operations must
be carried out exclusively by autho-
rised and appropriately trained per-
sonnel.
g. This system complies with the com-
munity directives applicable to this
product. Thus, it bears the CE mark.
h. Compliance with IEC 60947-6-1.
i. Information available in this instruc-
tion manual are not contractual.

SOCOMEC - Réf.: 678 623 G GB 3
ENGLISH
INTRODUCTION________________________________________________ 4 - 6
GENERAL INTRODUCTION ____________________________________ 4
ATI TRANSFER PANEL RANGE_________________________________ 4
NEW MOTORIZED CHANGEOVER SWITCH _____________________ 4
OPTIONS AVAILABILITY_______________________________________ 5
ENVIRONMENT ______________________________________________ 6
TECHNICAL CARACTERISTICS_____________________________________ 6
ENCLOSURES INSTALLATION_________________________________ 7 - 37
FIRST OPERATIONS______________________________________ 7 - 10
BOTTOM CABLE ENTRY ENCLOSURES___________________ 11 - 16
TOP CABLE ENTRY ENCLOSURES _______________________ 17 - 22
OPTIONAL CONNECTIONS ______________________________ 23 - 34
GENERAL POINTS___________________________________________ 34
VOLTAGE CONFIGURATIONS _________________________________ 35 - 42
VOLTAGE OPTIONS__________________________________________ 35
CABLE CONNECTIONS BETWEEN SWITCH
AND ELECTRONIC MODULE _________________________________ 35
ELECTRONIC MODULE CONNECTIONS _______________________ 36
INPUTS AND OUTPUT CONTACTS ________________________________ 40
CURRENT INPUTS (for metering)__________________________________ 40
BASIC PRODUCT USE________________________________________ 42 - 62
GENERAL INTRODUCTION___________________________________ 42
ELECTRONIC MODULE USAGE __________________________ 42 - 43
PROGRAMMING ACCESS____________________________________ 43
PROGRAMMING EXIT________________________________________ 43
PROGRAMMING MENUS_____________________________________ 44
SETUP MENU___________________________________________ 45 - 46
VOLTAGE MENU ________________________________________ 47 - 48
FREQUENCY MENU_____________________________________ 48 - 49
TIMERS MENU__________________________________________ 49 - 50
COMMUNICATION MENU________________________________ 50 - 52
MANUAL MODE_____________________________________________ 53
AUTOMATIC MODE__________________________________________ 54
LOSS OF MAINS AUTOMATIC SEQUENCE_____________________ 55
MAINS RETURN AUTOMATIC SEQUENCE _________________ 56 - 57
TEST MODE ACCESS________________________________________ 58
TEST MODE EXIT____________________________________________ 58
OFF LOAD TESTING _________________________________________ 59
ON LOAD TESTING__________________________________________ 60
METERING PRODUCT USE _______________________________________ 61
GENERAL INTRODUCTION___________________________________ 61
ELECTRONIC MODULE USAGE __________________________ 61 - 62
PROGRAMMING ACCESS____________________________________ 62
PROGRAMMING EXIT________________________________________ 62
PROGRAMMING MENUS_____________________________________ 63
SETUP MENU___________________________________________ 64 - 65
VOLTAGE MENU ________________________________________ 66 - 67
FREQUENCY MENU_____________________________________ 67 - 68
TIMERS MENU__________________________________________ 68 - 69
COMMUNICATION MENU ____________________________________ 69
PRODUCT METERING ___________________________________ 70 - 71
MANUAL MODE_____________________________________________ 72
MAINS RETURN AUTOMATIC SEQUENCE _____________________ 72
TEST MODE ACCESS________________________________________ 73
TEST MODE EXIT____________________________________________ 73
COMMUNICATION ___________________________________________ 74 - 77
LIST OF PARAMETERS TO BE DISPLAYED_________________ 74 - 77
SAVED COMMAND __________________________________________ 77
MAINTENANCE ______________________________________________ 78 - 81
FAULT FINDING GUIDE ___________________________________________ 82

4SOCOMEC - Réf.: 678 623 G GB
INTRODUCTION
GENERAL INTRODUCTION
NEW ATI enclosure integrates a new
4-pole changeover switch including
electronic’s control to meet standard
IEC 60947-6-1. Thanks to the chan-
geover switch technology, it is always
possible to manually operate the sys-
tem to guarantee the changeover panel
operation in any situation.
The new enclosure design allows
switch front panel access to:
• Avoid opening of the enclosure for
manual operation
• Allow electronic module access for
programming and monitoring
•Simplify connections between the
mechanical switch and the electronic
module.
With the mode switch in manual posi-
tion, Padlocking, as well as handle
insertion operations are then directly
accessible from the front panel.
The electronic module, also accessible
from the front panel, includes:
• Sources monitoring
• Metering display (V and f as standard)
• Test operations and Sequences pro-
gramming using keypad.
• ATI 1000 A
• ATI 1250 A
• ATI 1600 A
New ATI range models
MODEL
• ATI 250 A
• ATI 400 A
• ATI 630 A
• ATI 800 A
ATI TRANSFER PANEL RANGE
The new ATI panel range will be available from 250 A to 1600 A.
1. A mechanical switch.
2. A motorized block to operate the switch electrically.
3. An electronic module on the top of the motorized block, driving loss of mains
and main’s return sequence.
4. A reset button.
NEW MOTORIZED CHANGEOVER SWITCH
The new switch included in the enclosure is made of 3 different parts:
Standard offer includes Bottom cable entry. Top cable entry is offered as an
option.
Features and benefits:
• The new Motorisation block is inclu-
ded in a moulded case
• It is possible to remove the motorized
block and the electronic module
without being obliged to disconnect
the power cables
• Manual operation directly acts on the
shaft of the mechanical switch for
better reliability
• The complete enclosure meets stan-
dard IEC 60947-6-1 (ATS applications)
• The enclosure is self-powered (from
Main and Gen sources). There is no
need for an external power source to
allow automatic sequence after loss
of power
• All thresholds and timers can be set
using the display and the keypad, or
via modbus (optional)
•The standard product integrates
voltage and frequency control for
better diagnostic
• Main sensing circuit is 3 phases and
Gen sensing circuit is single phase
• Standard product includes, phase to
phase + phase to neutral voltage
measurement and displays system
frequency (phase 1) and switch num-
ber of operations.
• The product including metering allows
current measurement as well as power
metering (kW, kVar, kVA and PF).
12
3
4
ATI 035 A

SOCOMEC - Réf.: 678 623 G GB 5
ENGLISH
Option 9:
•Top Cable Entry. For cables to be
routed through the top rather than
bottom. Option code is TICT.
Option 6:
• Auxiliary contacts for switch posi-
tion information, padlocking and
Auto/Manual mode information are
optionally available. Option code is
TAUX.
INTRODUCTION (continued)
OPTIONS AVAILABILITY
Factory options are delivered pre-installed in the enclosures
Option 5:
• A switch allowing 277Vac specific
voltage option for customers requi-
ring voltage code V601 (480/277 Vac).
Option code is THVM.
Option 1:
• Ametering module allowing standard
features + current and power meter-
ing facilities on a larger backlit display.
This option also integrates option 6
(TAUX). Option code is TMET & TAUX.
Option 7:
•2IN/2OUT.1 plug in module allowing
auxiliary contacts for Main and
Generator available information is also
available as an option. Option code is
TIO2.
Option 8:
• 1 plug in communication module,
JBUS/MODBUS protocole, can
optionally be ordered allowing remote
communication of the changeover
system. Option code is TCOM.
Option 2:
•IP54 protection rating is available as
an option. A specific protection win-
dow must be installed on the front
panel of the enclosure to avoid water
infiltration in the enclosure. Option
code is TIP5.
Option 3:
•Solid neutral link is available as an
option on the switch itself, when
switching of the neutral cable is not
required. Option code is TLNK.
Option 4:
•Lightning protection is also available
as an option to avoid ATS damage in
case of a strike on the power cables.
This option is highly recommended
in stormy areas. Option code is TLPR
and TI02 is included.
Loose options are available, for customer mounting in the enclosures
Option 2
IP54 Protection Kit
Option 7
2In / 2Out
Option 3
Solid Neutral
Option 6
Auxiliary contacts
Option 4
Lightning Protection
Option 1
Metering Option
Option 5
Voltage 277 VAC
Option 8
Communication
Option 9
Top Cable Entry
ATI 036 A GB

6SOCOMEC - Réf.: 678 623 G GB
ENVIRONMENT
• Ingress protection of IP41 with overall
rating of IP21
• Operating temperature of – 10 °C to
40 °C without de-rating
• Operating temperature of 40 °C to
65 °C with de-rating
The complete enclosure meets following environmental requirements:
INTRODUCTION (continued)
TECHNICAL CARACTERISTICS
Characteristics
Thermal Current Ith (40 °C) 250 A 400 A 630 A 800A 1000A 1250 A 1600 A
Assigned isolement voltage Ui (V) 800 800 1000 1000 1000 1000 1000
Assigned voltage to chocks Uimp (kV) 8 8 12 12 12 12 12
IEC 60947-6-1 Characteristics
Assigned current Ie (A) (B categorie)
415 Vac AC31B 250 400 630 800 1000 1250 1600
Operating Class
Material class PC PC PC PC PC PC PC
Maximum short circuit current using gG DIN fuse
Max short circuit (kA eff) 50 18 70 50 100 100 100
Fuse size (A) 250 400 630 800 1000 1250 2 x 800
Peak current value: withstand and closing operation (kA peak) 23 23 45 48 75 75 75
Short circuit Operation
Rated short time withstand current (kA eff) 10 10 12.6 16 20 25 32
Rated short circuit making capacity (kA max) 17 17 25.2 27.2 40 52.5 67
Other Characteristics
Commutation duration
I-II ou II-I (s) (1) 1.3 1.3 1.3 2.6 2.6 2.8 2.8
I-o ou II-0 (s) (1) 0.85 0.85 0.85 1.6 1.6 1.7 1.7
Black time durating during commutation under Un (ms) 600 600 600 1 500 1500 1700 1700
Power input
230 Vac mini/maxi (V) 184/276 184/276 184/276 184/276 184/276 210/310 210/310
277 Vac mini/maxi (V) - Option 5 221/332 221/332 221/332 221/332 221/332 240/380 240/380
Consumption during switching operation
230 Vac maxi/average (VA) 400/100 400/100 420/110 450/120 450/120 470/128 470/128
277 Vac maxi/average (VA) - Option 5 400/110 400/110 420/115 450/125 450/125 470/128 470/128
Mechanical characteristics
Number of commutation (durability) 8000 8000 5000 4000 4000 3000 3000
Weight (complete std enclosure) kg 39 44 66 125 130 230 330
All these characteristics are given as information and are not contractual
(1): Between order sent and final position (under nominal conditions)
Temperature Derating
Nominal Rating Cable Size De rate IEC 947-3
(40 °C Max) 50 °C 60 °C 65 °C 40 °C 415 V 60 °C 415 V
(A) (mm2) (A) (A) (A) AC 22 AC 23 AC 22 AC 23
250 120 250 220 200 AC23A 250A AC23A 200A
400 240 360 300 250 AC22A 400A AC23A 250A AC23A 250A
630 2 x 185 550 500 400 AC22A 630A AC23A 500A AC23A 400A
800 2 x 240 720 640 540 AC22A 800A AC23A 800A AC23A 540A
1000 4 x 150 880 800 680 AC22A 1000A AC23A 1000A AC23A 680A
1250 4 x 240 1150 1000 820 AC22A 1250A AC22A 1000A
1600 5 x 240 1300 1100 930 AC22A 1600A AC22A 1100A
Single phase configuration
Table available for single phase configurations using a 4 poles switch and connecting 2 poles in parrallel
Max ambiant Temperature = 40 °C
Nominal Rating 3 phase configuration Nominal Rating 1phase configuration
(A) (2 poles in //) (A)
250 400 (1) Short circuit level required for 630A
400 630(1) not acceptable for 400A version
630 800(2) (2) Short circuit level required for 800A
800 1250 not acceptable for 630A version
1000 1600(3) (3) Short circuit level required for 1600A
1250 1800 not acceptable for 1000A version
1600 2500(4) (4) Short circuit level required for 2500A
not acceptable for 1600A version
Metering accuracy
Voltage and frequency: 1% on power input range.
• 95% humidity non condensing at
40 °C
• Maximum operating altitude without
switch de-rating is 2000 m above
sea level.
• Maximum storage is one year at:
- Maximum temperature +55°C
- 95% humidity non condensing
• 80% humidity non condensing at
55 °C

SOCOMEC - Réf.: 678 623 G GB 7
ENGLISH
ENCLOSURES INSTALLATION
FIRST OPERATIONS
400A / 630A
• The system is delivered in position 0 in
manual mode, start generator contact
closed.
• Remove the shroud to allow terminals
access.
Remove the plastic protection of the
plexiglas cover.
Shroud
ATI 037 A
For a correct use in hard
environmental conditions, it is
essential to use the cable
gland plate, in order to
protect the product.

8SOCOMEC - Réf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
x1
• Fix the handle + chain on the enclo-
sure itself.
Handle with chain
ATI 038 A

SOCOMEC - Réf.: 678 623 G GB 9
ENGLISH
ENCLOSURES INSTALLATION (continued)
M6
x4
x4
x4 x4
• Use the mounting brackets delivered
in a bag inside the enclosure to fix the
enclosure on a wall.
Wall mounting brackets
ATI 039 A

10 SOCOMEC - Réf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
1
2
3
• Cut the voltage sensing kit clips to
allow cables connections using
screws/nuts/contact washers delive-
red in a bag inside the enclosure.
Voltage sensing kit
ATI 040 A

SOCOMEC - Réf.: 678 623 G GB 11
ENGLISH
ENCLOSURES INSTALLATION (continued)
BOTTOM CABLE ENTRY ENCLOSURES
250 A rating
Phase and neutral cable
150 mm2or 2 x 70 mm2(Max)
Earth cable 120 mm2
or 2 x 50 mm2(Max)
A
A
Generator Main
Load
A-A
Torque : M8
M10 13 Nm (Max)
26 Nm (Max)
600
435
648
495
82.5
858
641
655
348
12.5
900
185
245
60
323
39 15
7
9
7.5
39
17
Power Cables Connection
123N
Power Cables Connection
ATI 042 A GB

12 SOCOMEC - Réf.: 678 623 G GB
400A rating
Phase and neutral cable
240 mm2or 2 x 120 mm2(Max)
Earth cable 120 mm2
or 2 x 70 mm2(Max)
Generator
Main
Load
Torque : M10
M12 26 Nm (Max)
45 Nm (Max)
A
A
435
648
600
495
82.5
858
641
655
348
12.5
900
185
245
60
323
39 15
7
9
7.5
39
17
Power Cables Connection
123N
Power Cables Connection
ENCLOSURES INSTALLATION (continued)
ATI 043 A GB

SOCOMEC - Réf.: 678 623 G GB 13
ENGLISH
ENCLOSURES INSTALLATION (continued)
600
605
545
328
320
200
288
495
455 30
30
46
72.5
14
423
398
900
Torque : M10
M12 26 Nm (Max)
45 Nm (Max)
Phase and neutral cable
2 x 240 mm2(Max) Earth cable
240 mm2(Max)
Generator
Main
Load
A
A
A-A
123N
630 A rating
Power Cables Connection
ATI 044 A

A
A
623
600
1175
200
775
720
520
30
28
80
50
50
80
536
480 50
120
14
14
536
480
1375
Torque: M10 26Nm (Max)
M12 45Nm (Max)
Phase and neutral cable
800A:3x240mm2or 2x300mm2(Max)
1000A:4x240mm2or 2x300mm2(Max)
Earth cable:
-800A:2x120mm2or 1x300mm2(Max)
-1000A:2x240mm2or 1x300mm2(Max)
A-A
Main
Load
Generator
14 SOCOMEC - Réf. : 678 623 G GB
800A/1000 A ratings
Power Cables Connection
ATYS 127 A GB
ENCLOSURES INSTALLATION (continued)

SOCOMEC - Réf. : 678 623 G GB 15
ENGLISH
ENCLOSURES INSTALLATION (continued)
1250 A rating
Power Cables Connection
A
A-A
Main
Load
Generator
Torque: M12 45Nm (Max)
A
A
798
775
1600
1800
800
555
100
100
100
100
100
555
100
800
100
200
100
803
1800
1000
58
81
79
58
Earth cable
2 x 240 mm2
or 1 x 300 mm2(Max)
Phase and neutral cable
2 x 300 mm2or 4 x 240 mm2(Max)
ATYS 131 B GB

ENCLOSURES INSTALLATION (continued)
1600 A rating
Power Cables Connection
ATYS 132 B GB
798
775
1600
1800
800
555
100
100
100
100
100
555
100
800
100
200
100
803
1800
1000
58
81
79
58
Earth cable
2 x 300 mm2
or 3 x 240 mm2(Max)
Phase and neutral cable
6 x 240 mm2or 4 x 300 mm2(Max)
A-A
Main
Load
Generator
Torque: M12 45Nm (Max)
A
A
A
A
16 SOCOMEC - Réf. : 678 623 G GB

SOCOMEC - Réf. : 678 623 G GB 17
ENGLISH
ENCLOSURES INSTALLATION (continued)
TOP CABLE ENTRY ENCLOSURES
250A ratings - Top cable entry
648
858
641
655
348
12.5
900
323
39 15
7
9
7.5
39
17
600
435
495
82.5
185
245
60
Phase and neutral cable
150 mm2or 2 x 70 mm2(Max)
Earth cable 120 mm2
or 2 x 50 mm2(Max)
A
A
Generator
Main
Load
A-A
Torque : M8
M10 13 Nm (Max)
26 Nm (Max)
123N
ATI 046 A GB
Power Cables Connection

18 SOCOMEC - Réf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
400A ratings - Top cable entry
648
858
641
655
348
12.5
900
323
39 15
7
9
7.5
39
17
600
435
495
82.5
185
245
60
Earth cable 120 mm2
or 2 x 70 mm2(Max)
Torque : M10
M12 26 Nm (Max)
45 Nm (Max)
Phase and neutral cable
240 mm2or 2 x 120 mm2(Max)
A
A
Generator
Main
Load
A-A
123N
ATI 047 A GB
Power Cables Connection

SOCOMEC - Réf.: 678 623 G GB 19
ENGLISH
ENCLOSURES INSTALLATION (continued)
630A ratings - Top cable entry
600
600
540
328
280
288
495
455
30
50
46
72.5
13
423
398
1150
Torque : M10
M12 26 Nm (Max)
45 Nm (Max)
Phase and neutral cable
2x240 mm2(Max)
Earth cable 240 mm2(Max)
Load
A
Generator
Main
AA-A
1 2 3 N
200
ATI 048 A
Power Cables Connection

20 SOCOMEC - Réf.: 678 623 G GB
ENCLOSURES INSTALLATION (continued)
800 A/1000 A ratings Top cable entry
A
A
536
480
520
720
28
30
14
200
775
1175
600
623
1375
80
50
50
80
536
480
120
50
14
12
13
13
Torque: M10 26Nm (Max)
M12 45Nm (Max)
Phase and neutral cable:
800A:3x240mm2or 2x300mm2(Max)
1000A:4x240mm22 or 2x300mm2(Max)
Earth cable:
-800A:2x120mm2or 1x300mm2(Max)
-1000A:2x240mm2or 1x300mm2(Max)
A-A
Main
Load
Generator
ATI 048 C GB
Power Cables Connection
This manual suits for next models
6
Table of contents
Popular Control Panel manuals by other brands

Bosch
Bosch D7024 operating instructions

Allen-Bradley
Allen-Bradley RediPANEL installation instructions

ETHINK
ETHINK KL8-3A Installation & user manual

Siemens
Siemens Synco RMZ792 installation instructions

EOS
EOS InfraTec Premium Installation and operating instruction

Teletek electronics
Teletek electronics iRIS4 installation manual