socomec DIRIS A17 User manual

DIRIS A17
Multifunction meters - MFM
Multi-measurement meter - dimensions 72 x 72 mm
Operating instructions EN

2DIRIS A17 - Ref.: 541 984 A
Contents
1. DOCUMENTATION ...................................................................3
2. DANGER AND WARNING............................................................3
2.1. RISK OF ELECTROCUTION, BURNS OR EXPLOSION ..................................3
2.2. RISK OF DAMAGING DEVICE ........................................................3
3. PRELIMINARY OPERATIONS........................................................3
4. PRESENTATION ......................................................................4
4.1. MAIN FUNCTIONS ..................................................................4
4.2. DISPLAY VIEWS ....................................................................4
5. INSTALLATION .......................................................................5
5.1. RECOMMENDATION ................................................................5
5.2. CUT-OUT DIAGRAM ................................................................5
5.3. TERMINALS ........................................................................5
5.4. CONNECTIONS.....................................................................6
6. COMMUNICATION MODBUS®.......................................................7
6.1. GENERAL INFORMATION ...........................................................7
6.2. RECOMMENDATIONS...............................................................7
6.3. COMMUNICATION STRUCTURE .....................................................7
6.4. REGISTER TABLE...................................................................8
7. PROGRAMMING .....................................................................9
7.1. NAVIGATION PRINCIPLE ............................................................9
7.2. ACCESS TO PROGRAMMING MODE .................................................10
7.3. EXAMPLE: NETWORK SELECTION. ..................................................11
7.4. EXAMPLE: CHOICE OF CURRENT TRANSFORMER....................................12
7.5. PROGRAMMING MODE OVERVIEW ..................................................13
7.6. DETAILED VIEW OF THE PROGRAMMING MENU......................................14
8. USE ...................................................................................18
8.1. DETAILED VIEW OF THE "CURRENT" MENU ..........................................19
8.2. DETAILED VIEW OF THE "VOLTAGE" MENU...........................................20
8.3. DETAILED VIEW OF THE "POWER" MENU ............................................21
8.4. DETAILED VIEW OF THE "ENERGY" MENU ...........................................22
9. CONNECTION TEST FUNCTION ....................................................23
10. ASSISTANCE........................................................................26
11. ELECTRICAL AND TECHNICAL CHARACTERISTICS.............................27
12. ACCORDING TO IEC 61557-12 ....................................................28
13. GLOSSARY OF ABBREVIATIONS ..................................................29

3
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
1. Documentation
All DIRIS A17 documentations are available on the website at the
following address:
www.socomec.com/en/documentation-diris-a17
2. Danger and warning
This equipment must be mounted only by professionals.
The manufacturer shall not be held responsible for failure to comply with the instructions in this manual.
2.1. Risk of electrocution, burns or explosion
Prior to any work on or in the device, isolate the voltage inputs and auxiliary power supplies and short-circuit
the secondary winding of all current transfromers (PTI SOCOMEC).
Replace all devices, doors, and covers before turning on power to this equipment.
Always supply the device with the correct rated voltage.
Failure to take these precautions could cause serious injuries.
2.2. Risk of damaging device
Chek the following:
the voltage of the auxiliary power
the maximum voltage across the voltage-input terminals, (V1, V2, V3 and VN) 500 VAC phase-to-phase or
289 VAC phase-to-neutral
a maximum current of 6 A on the current-input terminals (I1, I2 and I3).
3. Preliminary operations
For personnel and product safety, please carefully read the contents of these operating instructions before installation.
Check the following points as soon as you receive the DIRISA17 package:
the packing is in good condition,
the product has not been damaged during transport,
the product reference number conforms to your order,

4DIRIS A17 - Ref.: 541 984 A
4. Presentation
The DIRIS A17 is a 72x72 mm compact multifunction meter for measuring electrical network parameters. The DIRIS
A17 provides measurements of voltage, current, power and energy. With display and push buttons, users can easily
access to all product functionalities. It includes an input and an output, and depending on the reference, it can
includes a communication bus as well as the measurement of the harmonic distorsion rate.
4.1. Main functions
Multifunction meters - PMD*
Measurement of electric variables: I, U, V, F
Power, Power Factor and Energy
1 input / 1 output
Alarms
RS 485 MODBUS communication (according to reference)
Description Reference
DIRIS A17 with pulse output 4825 0101
DIRIS A17 with RS485 Modbus communication 4825 0102
DIRIS A17 with RS485 Modbus communication and THD 4825 0103
*Performance Measuring and monitoring Device (IEC 61557-12)
4.2. Display views
54321
Zone 2Zone 1
Zone 3
1. Backlit LCD display.
2. Currents (instantaneous
and maximum) and current
3. Voltages, frequency and
4. Active, reactive, and
apparent power
(instantaneous and max.
values) and power factor.
5. Powers.
Zone 1 Geometric representation of active and reactive Power
Status of input/output
Bad phases order
Total power
Current or power max value
In communication
Programming mode selection
Alarm presence
Zone 2 Electrical values measurement with Phases and/or Neutral
indication
Zone 3 Total energy measurement

5
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
5. INSTALLATION
5.1. Recommendation
avoid proximity to systems which generate electromagnetic interference,
5.2. Cut-out diagram
Panel mount of the device can be done according
to the following cut-out diagram:
panel.
5/TEST 4 OK PROG
IV F P PF E
DIRIS A17
2.83 in
72 mm
2.68 in
68 mm
0.42 in
10,6 mm
1.94 in
49,4 mm
0.75 in
19 mm
2.83 in
72 mm
+ 0.03
- 0.0
+ 0,7
- 0,0
2.68 in
68 mm
max. 0.31 in
max. 8 mm
+ 0.03
- 0.0
+ 0,7
- 0,0
5.3. Terminals
Each CT’s secondary winding must be short-circuited when disconnecting the DIRIS. This can be done automatically
0521). Please contact us for further information.
0.29 in / 7.5 mm
Flat 3
2.5 mm² (AWG14)
4.42 lb-in / 0,5 Nm
0.31 in / 8 mm
Flat 2
1.5 mm² (AWG16)
2.12 lb-in / 0,25 Nm

6DIRIS A17 - Ref.: 541 984 A
5.4. Connections
5.4.1. Connection (input / output)
- +
DIRIS A17
OUT
- +
IN
diris_891_c_1_x_cat
Power supply between 8 and 30 VDC for the input /output.
5.4.2. Communication connection
RS485
+ - NC
LIYCY-CY
diris_892_a_1_x_cat
NC: not connected. can be used for shield continuity.
5.4.3. Network connections
5.4.3.1. Unbalanced three-phase network (4NBL)
1
2
2
N
S2 S1 S2 S1 S2S1
I2 I3I1
V1 V2 V3 VN AUX
L1 (R)
L2 (S)
L3 (T)
P1
S1
P1
S1
P1
S1
5.4.3.2. Unbalanced three-phase network (3NBL)
P1
S1
P1
S1
L1 (R)
L2 (S)
L3 (T)
P1
S1
S2 S1 S2 S1 S2S1
I2 I3I1
V1 V2 V3 VN AUX
2
1
2
L1 (R)
L2 (S)
L3 (T)
S2 S1 S2 S1 S2S1
I2 I3I1
V1 V2 V3 VN AUX
P1
S1
P1
S1
2
2
1
L1 (R)
L2 (S)
L3 (T)
S2 S1 S2 S1 S2S1
I2 I3I1
V1 V2 V3 VN AUX
P1
S1
P1
S1
2
1
2
The solution with 2 CTs with the 2nd and 3rd phase current calculated via vectoral
summation, results in an 0.5% reduction in phase accuracy.
5.4.3.3. Balanced three-phase network
(4NBL)
N
1
2
S2 S1 S2 S1 S2S1
I2 I3I1
V1 V2 V3 VN AUX
L1 (R)
L2 (S)
L3 (T)
2
P1
S1
5.4.3.4. Balanced three-phase network
(3NBL)
P1
S1
L1 (R)
L2 (S)
L3 (T)
S2 S1 S2 S1 S2S1
I2 I3I1
V1 V2 V3 VN AUX
2
1
2

7
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
6. Communication MODBUS®
6.1. General Information
The MODBUS®communication bus is available on DIRIS A17
It is achieved via an RS485 serial link (2 or 3 wires) for using products from a PC or an API.
a distance of 1200 meters.
DIRIS 109 F X
DIRIS 110 F X
Programmable PLC
Programmable PLC
Other systems
Other systems
Repeater
0 -> NC
0 -> NC
6.2. Recommendations
It is necessary to use a shielded twisted pair (LIYCY type). In a disturbed environnement or large network (in terms
of length) we recommend the use of a shielded twisted pair (type LIYCY-CY).
A repeater should be used if the distance of 1200 m and/or maximum number of 32 products are exceeded.
6.3. Communication structure
The MODBUS®used by the product involves a dialogue using a master-slave structure. The mode of communication
is the RTU (Remote Terminal Unit) using hexadecimal characters of at least 8 bits.
Structure of the MODBUS®sequence (question master -> slave):
Slave address Function code Address Number of words to be
read
CRC 16
1 byte 1 byte 2 bytes 2 bytes 2 bytes

8DIRIS A17 - Ref.: 541 984 A
According to the MODBUS®protocol, transmission time must be less than 3 silences,
i.e. the emission time of 3 characters so that the message is processed by the DIRIS A17.
To use this information correctly, it is necessary to use the MODBUS®functions according to the codes:
3: to read n words (maximum 128).
6: to write one word.
16: to write n words (maximum 128).
Note:
1 word<=> 2 octets <=> 16 bits
2 word<=> 4 octets <=> 32 bits
When selecting the slave address 0, a message is sent to all the devices present on the network (only for functions
6 and 16).
Note: The response time (time out question/answer) is 250 ms.
6.4. Register table
The communication tables and associated explanations are
available in the documentations page of DIRIS A17 on internet web
site at the following address:
www.socomec.com/en/documentation-diris-a17

9
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
7. Programming
DIRIS A17 display.
Refer to following paragraphs for programming from the display.
7.1. Navigation principle
The programming mode allows to modify parameters such as network type, integration time, input/output, alarms
or communication parameters. The process to navigate indide the programming mode is described in the following
steps:
Open programming mode
(pressing PROG button dor 3 sec)
Enter the code (factory default code is: 100).
For modifying the parameters displayed
Case of a value
to be modified Case of a digital value to be set
Change the value Change first digit
Select next digit to changed
Change first digit
Validate modification

10 DIRIS A17 - Ref.: 541 984 A
7.2. Access to programming mode
By pressing "E/PROG" button for 3 seconds, device will enter the programming mode. Default code is: 100.
x 1
3 sec
x 1
x 1
x 1
confirm
W
W
W
If the entered code is the right one, device will enter programming mode successfully and remains in this mode until
Attention: For a timeout of 60 seconds without activity on the pushbuttons the device leaves the programming mode
without saving possible changes.

11
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
7.3. Example: network selection.
In programming mode (see page 10), go to screen "Network type - nEt"
In this example, network change from 4NBL to 3NBL:
x 1
x2
x 1
confirm
x 1 (3BL)
x 2 (3NBL)
x 3 (4BL)
x 4 (4 NBL)
W
W

12 DIRIS A17 - Ref.: 541 984 A
7.4. Example: choice of current transformer
In programming mode (see page 10), access to screen "Current transformer - Ct"
Example: ratio change to 500/1.
x2
x 1
confirm
x 1
confirm
x 1
x5
x 1
W
W
W
W
W

13
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
7.5. Programming mode overview
By pressing "E/PROG" button for 3 seconds, device will enter the programming mode. Default code is: 100.
Different screens are accessed by pressing "PROG" :
Programming mode
Network type
Current transformer
Voltage transformer
Max. current and power integration period
Active and reactive energy, max power,
max current and pulse meter reset
Input type (IN)
Output type (OUT)
Alarm
Threshold
Alarm delay
Output (OUT)
activation in
case of alarm
Energy
Pulse output
energy value
Pulse output
duration value
Communication
Backlit
Program password
Serial number
Software version

14 DIRIS A17 - Ref.: 541 984 A
7.6. Detailed view of the programming menu
Programming mode
100 (factory code)
Network type
3BL, 3NBL, 4BL,
4NBL
Current transformer
Current transformer
Voltage transformer
Yes, No
Voltage transformer
Voltage transformer
60, 100, 110, 115,
120, 173,
x 1
3 sec
XX = default value

15
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
Max. current integration time
20, 30, 60, 2, 5, 8,
10, 15 min
Max. power integration time
20, 30, 60, 2, 5, 8,
10, 15 min
Active / reactive energy reset
Yes, No
Power max reset
Yes, No
Current max reset
Yes, No
Pulse meter reset
Yes, No
Input type (IN)
No: no activation
Puls: pulse
cd: status change
No, puls, cd
Output type (OUT)
Ea: active energy
Er: reactive energy
Alarm: status
change if alarm
, ER, Alarm
XX = default value

16 DIRIS A17 - Ref.: 541 984 A
Alarm type
Value alarm
I, In, P
Capacitive PF,
Inductive PF,
cd
Alarm high threshold
237
0 -> 9999
Alarm low threshold
223
0 -> 9999
Alarm hysteresis threshold
1%
0% -> 99%
Alarm delay
Output (OUT) activation in case of alarm
Yes, No
Pulse output energy value
0: 0.1 kWh/kvarh
1: 1 kWh/kvarh
2: 10 kWh/kvarh
3 : 100 kWh/kvarh
4 : 1000 kWh/kvarh
5 : 10000 kWh/
kvarh
Pulse output duration value
100 -> 900 msec
XX = default value

17
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
x 1
3 sec
Communication
Product address on
MODBUS network
1 -> 247
Communication
Baud Rate
1.2, 2.4, 4.8, 9.6,
19.2, 38.4 kbaud
Communication
Parity
No, Even, Odd
Communication
Stop bit
1, 2
Backlit
Standard: remains
ON
Auxiliary: switches
OFF after a few
seconds
Standard,
Program password
100
0 -> 999
Serial number
Software version
XX = default value

18 DIRIS A17 - Ref.: 541 984 A
8. Use
The measurement values are accessible via dedicated buttons: Current, Voltage, Power and Energy. By pressing
the appropriate button several times all the measurement relative to this button can be displayed. All the available
measurements are described in the following diagram:
Current Voltage Power Energy
Instantaneous phase
currents
Instantaneous phase-phase
voltages
Total powers
- imported/exported active,
- imported/exported
reactive
- apparent
Import active energy
______________ ______________ ______________ ______________
Instantaneous neutral
current
Instantaneous phase-
neutral voltages
Instantaneous active power
per phase Import reactive energy
______________ ______________ ______________ ______________
Max. phase currents Instantaneous frequency Instantaneous reactive
power per phase Apparent energy
______________ ______________ ______________ ______________
Max neutral current Instantaneous phase-phase
Instantaneous apparent
power per phase Export active energy
______________ ______________ ______________ ______________
Instantaneous phase-
Maximum active, reactive
and apparent power Export reactive energy
______________ ______________ ______________
Total power factor Pulse meter connected to
the input
______________
Instantaneous power factor
per phase

19
DIRIS A17 - Ref.: 541 984 A
DIRIS A17
8.1. Detailed view of the "Current" menu
Instantaneous phase currents
Instantaneous neutral current
Max. phase currents
Max neutral current
Max. phase currents THD
THD neutral current

20 DIRIS A17 - Ref.: 541 984 A
8.2. Detailed view of the "Voltage" menu
Instantaneous phase-phase
voltages
Instantaneous phase-neutral
voltages
Instantaneous frequency
Instantaneous phase-phase
voltages THD
Instantaneous phase-neutral
voltages THD