SOR 1550 Instruction manual

Form 865 (01.13) ©SOR Inc.
1/8
Do not exceed catalog stated electrical ratings. Improper current input to
detector will cause permanent damage to contacts.
Electrical Connection
The SOR
®
1550 Electric Level Detector mounts into the top of a vessel.
Electric detecting action is provided by the float moving a magnet into the
field of a hermetically sealed reed detector.
NOTE: If you suspect that a product is defective, contact the factory or the
SOR Representative in your area for a return authorization number (RMA).
This product should only be installed by trained and competent personnel.
1550 Top Mounted
Level Detector
General Instructions
Registered Quality System to ISO 9001
Design and
specifications are
subject to change
without notice.
For latest revision, go to
www.sorinc.net
Table of Contents
Electrical Connections ........................ 1
SIL Installation ................................. 2
Wiring ........................................... 2
Float Attachment............................... 3
Special Conditions............................. 3
Dimensions ..................................... 4
ATEX and IECEx Marking Details ............ 4
Declaration of Conformity .................... 6
Troubleshooting ................................ 7
Replacement Parts ............................ 7
Before Installng the Level Detector
Inspect the unit for any shipment damage.
Check for mechanical clearance of the float. Float must move freely
without binding throughout its stroke.
Use an acceptable thread compound when installing unit to ensure
a leak-free fit and avoid thread galling.
Electrical connection is free wire leads with a 1/2” NPT(F) conduit
connection. Use two wrenches - one to hold hex conduit connection,
the other to tighten conduit fitting. Detecting element is a hermetically
sealed reed detector.
Wiring schematics shown on page 2.
Ensure that all wiring conforms to all applicable local and national electrical
codes and install unit(s) according to relevant national and local safety codes.
al
t
he
.
.
ral
Instructions
rica
al

2/8
Form 865 (01.13) ©SOR Inc.
NC 2
NO 2
NC 1
NO 1
5
6
4
3
7
2
1
8
Detector Capsule
Black Lead
White Lead
C2
C1
Power
Supply Relay Coil
SPST Reed
Detector Capsule
SPDT Reed
Detector Capsule
Common Black Lead
Common Black Lead Normally Open Blue Lead
Normally Closed White Lead
Normally Open White Lead
For Type 1550 Level Detectors equipped with DPDT relays, a wiring schematic and pin
position schematic is shown below. When the 1550 is actuated, the coil will energize and
“make” both NO1 and NO2 while it will “break” NC1 and NC2. This provides a DPDT circuit.
Wiring for DPDT Relay
DPDT Relay Schematic
3
NO1
2187
C2C1
4
NC1 5
NC2 6
NO2
Wiring for SPST and SPDT Detector Operation
Safety Integrity Level (SIL) Installation Requirements
The SOR pressure detectors have been evaluated as Type-A safety related hardware.
To meet the necessary installation requirements for the SIL system, the following
information must be utilized:
Proof Test Interval shall be one year.
Units may only be installed for use in Low Demand Mode.
Products have a HFT (Hardware Fault Tolerance) of 0, and were evaluated in a
1oo1 (one out of one) configuration. Form 1538 (03.12) ©2012 SOR Inc.

Form 865 (01.13) ©SOR Inc.
3/8
Special Conditions of Safe Use
The permanently attached leads must be suitably protected against mechanical damage and
terminated in a suitable junction or terminal facility with a minimum degree of protection of
at least IP20.0
Linear = mm/inches
Drawing 0390747
APPLY TWO DROPS
LOCTITE 271 INSIDE
THREADED HOLE
OF FLOAT
FLOAT
SET SCREW
Place two drops of Loctite 271
inside the threaded hole of the float.
Thread the float onto the set
screw and hand-tighten.
NOTE: Do not remove the set screw as
it secures the pivot arm to the shaft.
Float Attachment (Series 1500 with Flange)

4/8
Form 865 (01.13) ©SOR Inc.
Dimensions
Linear = mm/inches
Drawing 0390428
Dimensions are for
reference only.
Contact the factory
for certified drawings
for a particular model
number.

Form 865 (01.13) ©SOR Inc.
5/8
For ATEX and IECEx Certied Models
Standards Assessed To: ATEX Certification: EN 60079-0: 2009 & EN 60079-11:2007
IECEx Certification: IEC 60079-0:2004 & IEC 60079-11: 1999
ATEX and IECEx Marking Details
Drawing 0720531
Manufacturer’s
Registered Trademark
ATEX Listing
Information
Product Type
Identification
Product Model
Identification

6/8
Form 865 (01.13) ©SOR Inc.
Declaration of Conformity
For ATEX Certied Models
EC Declaration
of Conformity
14685 West 105th Street, Lenexa, KS 66215-2003
s53!s&!8
Engineered to Order with Off-the-Shelf Speed
Form 1385 (11.12) SOR Inc.
Product
Manufacturer
Date of Issue
We declare that the above
products conform to
the following specifications
and directives
Carries the marking
Reference document
ATEX Notified Body
Persons responsible
Type 1500 Electric Detectors
SOR Inc.
14685 West 105
th
Street
Lenexa, Kansas 66215-2003
5NITED3TATESOF!MERICA
November 12, 2012
!4%8$IRECTIVE%#%QUIPMENT)NTENDEDFORUSE
IN0OTENTIALLY%XPLOSIVE!TMOSPHERES
%.%.
)%#)%#
II 1 G Ex ia IIC T3
²#4A ²#OR²#4A ²#
%XIA))#4²#4A²#
EC-Type Examination Certificate
Baseefa06ATEX0271X
IECEx BAS06.0063X
)SSUED*ANUARY
Baseefa Ltd..OTIlED"ODY.O
2OCKHEAD"USINESS0ARK3TADEN,ANE
"UXTON$ERBYSHIRE3+2:
5NITED+INGDOM
"ASEEFA#USTOMER2EFERENCE.O
*OHN*&ORTINO60OF%NGINEERING
*OHN*&ORTINO

Form 865 (01.13) ©SOR Inc.
7/8
Troubleshooting
Symptom Probable Cause
Float in actuated position but no
output signal.
a. No power supply.
b. Detector damaged. (Replace.)
Float in de-actuated positon but
still receiving an output signal.
a. Detector damaged. (Replace.)
Liquid in vessel at the actuation
level but unit does not respond.
a. Leaky or collapsed float. (Replace.)
b. Liquid specific gravity too low.
c. Float stem bound up or dirty. (Clean.)
d. Float travel is obstructed. Verify float
can move freely and is not obstructed
when installed.
Part Number Description
3130-091 W9 - SPST Hermetically Sealed Detector Capsule
3130-245 W1 - SPDT Hermetically Sealed Detector Capsule
3130-107 L9 - SPST Hermetically Sealed Detector Capsule
3130-244 L1 - SPDT Hermetically Sealed Detector Capsule
3101-122 316SS Float. (Consult factory for other materials.)
3130-396 Actuator Arm Replacement Kit
Replacement Parts

8/8
Form 865 (01.13) ©SOR Inc.
14685 West 105th Street, Lenexa, KS 66215
913-888-2630
800-676-6794 USA
Fax 913-888-0767
Registered Quality System to ISO 9001
Printed in USA www.sorinc.net