Spirotech SpiroVent Superior S6 Series User manual


User manual - version 1.1 English 21
TABLE OF CONTENTS
/i
All rights reserved. No part of this manual may be
duplicated and/or made public through the Internet, by
means of printing, photocopying, microfilm or in any
other way without prior written permission from
Spirotech bv.
This manual has been composed with the utmost care.
Should, however, this manual contain any inaccuracies,
Spirotech bv cannot be held responsible for this.
1PREFACE
This user manual involves the installation, commissioning
and operation of the SpiroVent Superior of the types S6A,
S6A-R and S6A-R 2P.
Always carefully read the instructions before installation,
commissioning and operation. Keep the instructions for
future reference.
1.1 Symbols
Throughout the instructions the following symbols are
used:
1 Preface 21
2 Introduction 22
3 Technical specifications 24
4Safety 26
5 Installation and commissioning 27
6Use 32
7Failures 33
8Maintenance 36
9 Guarantee 38
10 CE statement 38 Warning or important note
Note
Risk of electric shock
Risk of burning
OBJ_DOKU-75-001.fm Page 21 Thursday, January 29, 2009 1:34 PM

22 English User manual - version 1.1
2INTRODUCTION
2.1 Overview of the unit
A Automatic air vent
B Deaeration vessel
C Inlet hose
D Refill connection (types S6A-R and S6A-R 2P)
E Valve behind pressure gauge
F Notch in the cover
GWaterflowmeter
H Level switch (in bottom of vessel)
I Adjustable inlet valve
J Temperature sensor
K Back-up pump (for type S6A-R 2P)
LScrew
M Drain connection (under the vessel)
N Solenoid valve
OMainpump
P Adjustable outlet valve
Q Pressure sensor
R SmartSwitch (in bottom of control unit)
S Pressure switch
T Pressure gauge
U Control unit
V Outlet hose
WCover
W
A
V
U
T
S
R
Q
M
L
P
O
N
F
G
I
J
B
C
D
S
Superior S6A-R 2P Superior S6A-R
Superior S6A
E
H
K
OBJ_DOKU-75-001.fm Page 22 Thursday, January 29, 2009 1:34 PM

User manual - version 1.1 English 23
2.2 Operation
The figure below schematically shows the operation of
the unit. The letter indications comply with the main
figure on the previous page.
/i
S6A
CJ I
N
R
T
E
S
A
B
H
MO
P
V
M
TT
PS
PS
LS
PI
S6A-R
CJ I
N
N
G
R
T
E
S
A
B
H
M
D
O
P
Q
V
M
TT
PS
PS
LS
PT
PI
FT
S6A-R 2P
K
CJI
N
N
G
R
T
A
B
E
S
H
M
O
P
Q
V
M
M
TT
PS
PS
LS
PI
FT
PT
OBJ_DOKU-75-001.fm Page 23 Thursday, January 29, 2009 1:34 PM

24 English User manual - version 1.1
2.2.1 General
The Superior is a fully automatic vacuum degasser for
installations filled with fluid. The fluid contains dissolved
and undissolved gases. The function of the unit is to
remove these gases from the installation until the
concentration of undissolved gases has reached an
absolute minimum. Problems caused by gases in the
installation are thus eliminated.
The types S6A-R and S6A-R 2P have an integrated refill
automat. The refill automat maintains continuous
pressure in the installation. For this the unit adds
degassed fluid, if necessary. The unit can also fill the
entire installation with degassed fluid.
The type S6A-R 2P also has a back-up pump. In case of a
break-down of the main pump, the back-up pump takes
over the refill function of the main pump, thus
guaranteeing the system pressure.
2.2.2 Degassing
The unit starts up daily with the degassing process at a
time indicated by the user. The process has two phases:
1 The flushing phase: The fluid flows from the
installation through the solenoid valve (N) into the
vessel (B). The pump (O) continuously pumps the
(degassed) fluid from the vessel into the
installation. Here the degassed fluid absorbs gases
again.
2 The vacuum phase: The solenoid valve (N) regularly
closes, starting the vacuum phase. The continuously
running pump (O) provides underpressure in the
vessel (B). The underpressure causes the release of
the gases dissolved in the fluid, which are collected
at the top of the vessel. The solenoid valve (N)
opens again, starting a new flushing phase. The
gases collected in the vessel are removed from the
installation through the automatic air vent (A). The
SmartSwitch (R) in the control unit makes sure that
the degassing is stopped as soon as the content of
dissolved gases has reached the minimum level.
2.2.3 (Re)fill
The types S6A-R and S6A-R 2P of the unit constantly
check the installation pressure. The refill process starts
and stops automatically at the set values. The unit can
also be used to automatically fill the installation with
degassed fluid.
2.3 Operating conditions
The unit is suitable for use in systems filled with clean
water or mixtures of water with a maximum of 40%
glycol. Use in combination with other fluids may result in
irreparable damage.
The unit should be used within the limits of the technical
specifications as given in chapter 3.
2.4 Scope of delivery
•1x SpiroVent Superior
•1x User manual
•1x Non-return protection (optional)
3 TECHNICAL SPECIFICATIONS
3.1 Dimensions
/i
WARNING
•In case of doubt, always contact the
supplier.
•In case of a heavily contaminated system
fluid, a dirt separator is to be installed in
the main return line of the installation.
Height [mm] Width [mm] Depth [mm]
880 590 350
590350
880
OBJ_DOKU-75-001.fm Page 24 Thursday, January 29, 2009 1:34 PM

User manual - version 1.1 English 25
3.2 General specifications
/i
3.3 Electrical specifications
/i
3.4 Other specifications
/i
S6A S6A-R S6A-R 2P
Max. system volume 150 m3150 m3150 m3
Empty weight 57 kg 59 kg 67 kg
Volume of degassing vessel 8 l 8 l 8 l
Inlet connection Swivel G¾” f.t. Swivel G¾” f.t. Swivel G¾” f.t.
Outlet connection Swivel G¾” f.t. Swivel G¾” f.t. Swivel G¾” f.t.
Drain connection Swivel G¾” m.t. Swivel G¾” m.t. Swivel G¾” m.t.
Noise level Approx. 57 dB(a) Approx. 57 dB(a) Approx. 57 dB(a)
Refill connection n/a Swivel G¾” f.t. Swivel G¾” f.t.
S6A S6A-R S6A-R 2P
Supply voltage 230 V ± 10% / 50 or 60 Hz 230 V ± 10% / 50 or 60 Hz 230 V ± 10% / 50 or 60 Hz
Absorbed power 800 W 800 W 1300 W
Nominal power
consumption
3.5 A 3.5 A 5.5 A
Starting current 2.6*nominal current 2.6*nominal current 2.6*nominal current
Protection 10 A / 3.15 A(T) 10 A / 3.15 A(T) 10 A / 3.15 A(T)
Protection class IP 44 IP 44 IP 44
Max. load of potential-free
contacts
24 V / 1 A 24 V / 1 A 24 V / 1 A
Supply voltage for BMS
control
(voltage of BMS)
24 Vac 24 Vac 24 Vac
Supply voltage of external
refill signal
(supplied voltage)
n/a 5 Vdc 5 Vdc
S6A S6A-R S6A-R 2P
System pressure 1 - 6 bar 1 - 6 bar 1 - 6 bar
Ambient temperature 0 - 40 °C 0 - 40 °C 0 - 40 °C
Maximum compression
pressure
(with closed valve behind
pressure gauge)
10 bar 10 bar 10 bar
Refill flow n/a See graph in § 6.1 See graph in § 6.1
System fluid temperature 0 - 90 °C. 0 - 90 °C 0 - 90 °C
Refill pressure 0 - 6 bar 0 - 6 bar 0 - 6 bar
Refill fluid temperature n/a 0 - 70 °C 0 - 70 °C
OBJ_DOKU-75-001.fm Page 25 Thursday, January 29, 2009 1:34 PM

26 English User manual - version 1.1
3.5 Building Management System
(BMS)
The unit has been provided with auxiliary contacts for
communication with a BMS. The BMS has to offer the 24
Vac voltage.
/i
4SAFETY
4.1 CE marking
The unit has a CE marking. This means that the unit has
been designed, constructed and tested in compliance
with the current safety and health regulations.
Provided that the user manual is adhered to, the unit can
be safely used and maintained.
4.2 Type plate
A Type of the unit
B Absorbed power
C Supply voltage
D Protection class
ESystempressure
FSystemtemperature
G Serial number
H Year of construction
The type plate has been applied on the inside of the unit.
Remove the cover to read the data on the type plate.
Signal S6A S6A-R S6A-R 2P
Unit in operation Potential-free Potential-free Potential-free
Unit failure Potential-free Potential-free Potential-free
Unit release/stop 24 Vac 24 Vac 24 Vac
Refill by BMS n/a 24 Vac 24 Vac
WARNING
•Installation and maintenance of the unit
should only be carried out by authorised
personnel.
•Remove the voltage and pressure from
the unit before starting the activities.
WARNING
There are hot parts below the cover. Let the
unit cool down before starting the activities.
SPIROVENT SUPERIOR
Type
Power input
Voltage
IP class
Pressure
Temperature
Serial number
Year of manufacture
SPIROTECH bv – Helmond – The Netherlands
A
B
C
D
E
F
G
H
OBJ_DOKU-75-001.fm Page 26 Thursday, January 29, 2009 1:34 PM

User manual - version 1.1 English 27
5 INSTALLATION AND
COMMISSIONING
5.1 Installation conditions
•Install the unit on a frost-free, well-ventilated place.
•Electrically connect the unit to a 230 V / 50 -60 Hz
socket.
•Make sure the expansion system has the proper
dimensions. The water displacement in the unit can
cause pressure variations in the installation.
•There must be overpressure in the installation. This
prevents spontaneous aeration.
5.2 Unpack
The unit is delivered on a pallet.
1. Remove the packaging.
2. Loosen the screw (A) half a turn.
3. Remove the cover (B) from the unit.
4. Move the unit with two persons to the place of
installation. Lift the unit using the handles (C).
5.3 Installation and mounting
5.3.1 Mounting
•Wall mounting: Mount the unit on the wall using
the holes (A). Make sure that the mounting can
carry the filled unit (empty weight + 10 kg).
•Floor mounting: Place the unit on a flat surface.
Mount the unit on the floor using the holes (B).
WARNING
Do not hoist the unit when unpacked. The use
of webbing slings, chains and hooks can
cause irreparable damage.
A C
B
CAUTION
•Install the unit in accordance with the
local guidelines and rules.
•Install the unit as bypass on the main
transport line of the installation.
NOTE
•Preferably install the unit at the point in
the installation with the lowest
temperature. Here the most dissolved
gases are found in the fluid.
•Make sure when installing that the
operating panel is always easily
accessible.
B
A Ø10
Ø10
OBJ_DOKU-75-001.fm Page 27 Thursday, January 29, 2009 1:34 PM

28 English User manual - version 1.1
5.3.2 Installation
Mechanical
1. Make two branch lines ¾” (A) on the side of the
main transport line. The distance between them
should be at least 500 mm.
2. Insert a valve (B) in each branch. With this the unit
can be depressurised.
3. Connect the line (A) to the flexible outlet hose (D).
4. Connect the line (B) to the flexible inlet hose (C).
With the types S6A-R and S6A-R 2P:
1. Insert a valve (F) and a non-return protection (E) in
the refill fluid supply line.
2. Connect the supply line to the refill connection (G)
of the unit.
Electrical
1. Loosen the screws (A) of the control cabinet.
2. Fold down the operating panel (B) to the front.
CAUTION
Make sure that the valves are opened before
putting the unit into operation.
NOTE
As seen from the direction of the volume flow,
the first branch is the inlet into the unit.
A
500mm
A
B
B
>
A
D
B
C
F
E
G
CAUTION
•Use a locally approved non-return
protection. A non-return protection can
be optionally delivered.
•Make sure that the pressure in the refill
line is below the system pressure. This
prevents undesired refilling in case of
failure of the refill line.
•Make sure that the lines leave the unit at
the rear.
CAUTION
•Preferably use a wall socket for the
power supply to the unit. This should
always be accessible.
•Mount an all-pole main switch (contact
opening >= 3mm) if the unit is directly
connected to the power supply.
•Use supply cables with the correct
dimensions.
•Always replace a defect fuse by a fuse of
the same value. See § 3.3.
A
C D E
B
OBJ_DOKU-75-001.fm Page 28 Thursday, January 29, 2009 1:34 PM

User manual - version 1.1 English 29
/i
3. Feed a 3-core supply cable through swivel (C) and
connect this to connector J16.
4. If a BMS is used, feed in the BMS cable through
swivel (E) and connect this to connector J20.
With the types S6A-R and S6A-R 2P:
1. If an external device controls the refill, feed in a
cable through swivel (D) and connect this to
connector J21.
5.4 Commissioning
5.4.1 Preparation
1. Set the adjustment valves (A and B) from the
position "fully open" with the following table.
2. Open the valve (C) behind the pressure gauge (D).
3. Open the valves (E and F) in the inlet and outlet
lines.
4. Open the valve (G) in the refill line.
/i
5.4.2 Start up
A On/off
BDisplay
C Status report in operation / OK
DUp
E Confirm / Enter
FMenu
GDown
H Cancel / Exit
I Status report failure
connector contact connection
J20 1 and 2 Refill*)
*) applies to types S6A-R and S6A-R 2P.
3 and 4 Release/off
5 and 6 Failure
7 and 8 In operation
J21 1 and 2 Refill*)
J20J16
PE
N
L1
J21
1
2
3
5
4
6
8
7
2
1
6
4
5
3
2
1
F5
F8
J16 J20
J21
F1
F6 F7
F2
1
2
3
5
4
6
8
7
2
1
6
4
5
3
2
1
FE
C
D
B
G
A
System
pressure
[bar]
Medium:
water
System
pressure
[bar]
Medium:
water/glycol
Position
adjustment
valve inlet
(B)
Position
adjustment
valve
outlet (A)
1 - 2 3 2
2 - 3 2.5 2.5
3 - 4 2.25 6
4 - 5 2 6
5 - 6 1.75 6
1 - 2 6 2
2 - 3 6 2.5
3 - 6 6 6
CAUTION
•The start-up routine starts automatically
when the unit is switched on for the first
time.
•Press EXIT to go back one step in the
menu while programming.
H
I
G
B
C
D
E
F
A
OBJ_DOKU-75-001.fm Page 29 Thursday, January 29, 2009 1:34 PM

30 English User manual - version 1.1
Follow the procedures given below for entering the
required parameters.
Set date en time
1. Press ON/OFF.
2. Select a language using Sand T. Press ENTER.
3. Set the date using Sand T. Press ENTER.
4. Set the day using Sand T. Press ENTER.
5. Set the time using Sand T. Press ENTER.
Filling the unit
1. Press ENTER two times. The unit starts filling.
2. Wait for 20 seconds until Initial fill busy
disappears.
3. Loosen the air vent screw (A) a few turns and
tighten it again when air has stopped coming out.
4. Repeat steps 1 - 3 until water starts coming out of
the air vent screw at step 3.
5. Also deaerate the back-up pump with type S6A-R
2P.
6. Press EXIT two times. The status menu shows the
message Err 7 when the test of the run dry
protection has been completed successfully.
7. Press MENU. Select Manual operation using S
and T. Press ENTER.
8. Select Reset using Sand T. Press ENTER.
Check operation
1. Manually start the unit, see § 5.5.2.
2. Check the indication of the pressure gauge (B). This
should alternately display overpressure and
underpressure.
3. Close the valve (A) behind the pressure gauge (B).
4. Put back the cover (C) on the unit and fasten it with
the screw (D).
5.5 Install and operate
5.5.1 Install
Set the user parameters
1. Press MENU. Select Settings using Sand T.
Press ENTER.
2. Select the parameter to be changed using Sand
T. Press ENTER.
3. Change the setting using Sand T. Press ENTER.
4. Repeat steps 2 and 3, if necessary.
5. Repeatedly press EXIT to return to the status report.
/i
NOTE
The green LED "OK" indicates that the unit is
ready for use. The degassing starts by default
daily at 08:00 hours.
A
NOTE
The SmartSwitch will automatically turn
off the unit when the concentration of
dissolved gases has reached the minimum
level.
Parameter Description
Language Language for the display texts.
Date The current date.
Weekday The current weekday.
Time The current time.
Auto start 1 Time 1 for starting the degassing
process.
Auto start 2 See Auto start 1.
Block.time day 1 Time for stopping the degassing
process.
D
B
A
C
OBJ_DOKU-75-001.fm Page 30 Thursday, January 29, 2009 1:34 PM

User manual - version 1.1 English 31
5.5.2 Manual operation
1. Press MENU. Select User menu > Manual
operation using Sand T. Press ENTER.
2. Select Manual operation start or Manual
operation stop using Sand T. Press ENTER.
5.5.3 Filling the installation
Applies to types S6A-R and S6A-R 2P.
1. Press MENU. Select User menu > Manual
operation using Sand T. Press ENTER.
2. Select Manual operation > system fill
using Sand T. Press ENTER.
3. Select Degassed or Non degassed. Press ENTER.
5.5.4 Switch on again
Follow the procedure described below after the unit has
been switched off.
1. Set the adjustment valves from the position "fully
open" in accordance with the table in § 5.4.1.
2. Press ON/OFF.
3. Press ENTER two times. The unit starts filling.
4. Wait for 20 seconds until Initial fill busy
disappears.
5. Loosen the air vent screw (A, see figure on the
previous page) a few turns and tighten the screw
again when air has stopped coming out.
6. Repeat steps 3 - 5 until water starts coming out of
the air vent screw at step 5.
7. Also deaerate the back-up pump with type S6A-R
2P.
8. Press EXIT two times. The status menu shows the
message Err 7 when the test of the run dry
protection has been completed successfully.
9. Press MENU. Select Manual operation using S
and T. Press ENTER.
10. Select Reset using Sand T. Press ENTER.
5.5.5 Reading the memory
During operation the following data are stored in the
memory:
•Accumulative running hours
•Degassing history
•Fault history
•Refilling history (only with types S6A-R and
S6A-R 2P).
The memory can be read in the following way:
1. Press MENU. Select User menu > History using S
and T. Press ENTER.
2. Select Fault history or Operation history
using Sand T. Press ENTER.
3. Select an item using Sand T. Press ENTER.
4. Repeatedly press EXIT to return to the status report.
5.5.6 Reading data
The following general data have been stored in the
memory of the unit:
•Unit type
•Software version
•Installation date.
The general data can be read in the following way:
Block.time day 2 See Block.time day 1.
Block.time week Days of the week on which the unit
is not working.
Selected days are marked with an *.
After having changed this
parameter, select Save using Sor
T. Press ENTER.
Block.time year 1 Period per year during which the
unit is not working.
Block.time year 2
- 5
See Block.time year 1.
Max. syst.
pressure *)
Pressure at which the unit stops.
Psystem desired*) Pressure at which the refilling
stops. Set this as low as possible if
the refilling is controled by the BMS
or external devices.
Refillpressure*) Pressure at which the refilling
starts.
Set this as low as possible when the
refilling is controled by the BMS or
external devices.
Refill alarm*) Maximum amount of fluid that may
be refilled per time (0 - 2500 l; 0 =
switched off).
Refill alarm after*) Continuous refilling time (0 - 255
min.; 0 = switched off).
Max. refill freq.*) Maximum number of times per day
that refilling is allowed
(0 - 10 times; 0 = switched off).
*) applies to types S6A-R and S6A-R 2P.
NOTE
If manually switched off, the process must be
manually switched on again.
NOTE
The unit also fills the installation with
(degassed or not degassed) fluid. When the
desired system pressure is reached, the unit
automatically goes to the standby status.
Parameter Description
NOTE
The green LED "OK" indicates that the unit is
ready for use.
OBJ_DOKU-75-001.fm Page 31 Thursday, January 29, 2009 1:34 PM

32 English User manual - version 1.1
1. Press MENU. Select User menu > General info
using Sand T. Press ENTER.
2. Select an item using Sand T. Press ENTER.
3. Repeatedly press EXIT to return to the status report.
6USE
6.1 General
•The display lighting automatically dims after no key
has been pressed for 5 minutes. Press a key to
activate the lighting.
•While stopping the process a stop procedure is
started, making sure that the unit stops in a safe
situation (overpressure).
•When a pump has not run for 96 hours, an
automatic pump test is run at the first next Auto
start.
•Press ON/OFF to switch off the unit. Press ON/OFF
again to switch on the unit again.
•At low fluid temperatures condensation may occur
at certain parts. The condensation is drained
through the openings in the frame.
•With the types S6A-R and S6A-R 2P:
The amount of fluid that is added (B) depends on
the difference (A) between the system pressure and
the refill water pressure.
A System pressure - water pipe pressure (bar)
BFlow(l/hour)
6.2 Status reports
/i
0
100
200
300
400
500
600
B
01
A
2345
Report Description LED indication
Auto pump test The unit runs a pump test. Green
End degassing
End refilling
End systemfill
The stop procedure is in process. Green
Degassing The degassing process is in process. Green
Process stopped The unit has been stopped manually. None
Standby The unit is waiting for a starting signal. Green
Stop by BMS The BMS has stopped the unit. After release by the BMS the
unit must be started manually.
None
Failure The unit has stopped because of a failure. Remedy the failure
before resetting the unit, see § 7.3.1. The unit is switched to
one of the above statuses.
Red
Refill (only with S6A-R
and S6A-R 2P)
The unit is refilling fluid. Green
Filling system
(only with S6A-R and
S6A-R 2P)
The installation is filled with fluid. Green
OBJ_DOKU-75-001.fm Page 32 Thursday, January 29, 2009 1:34 PM

User manual - version 1.1 English 33
7FAILURES
7.1 Remedy failures
1. Localise the failure using the failure table,
see § 7.3.
2. If necessary, put the unit out of operation,
see § 7.2.
3. Remedy the failure.
4. Reset the unit, see § 7.3.1 or put the unit into
operation again, see § 5.5.4.
7.2 Putting out of operation
1. Take the plug out of the wall socket or switch off
the main switch. Make sure that switching on the
voltage unintentionally is not possible.
2. Close the valves (A) and/or (C) in the inlet line and
(B) and/or (D) in the outlet line.
3. Close, if applicable, the valve (E) in the refill supply
line as well.
4. Connect a drain line (H) to the drain connection (G).
5. Drain the unit through the drain connection (G).
6. Open the air vent screw on the main pump to
completely empty the unit. See the figure in §
5.4.2.
WARNING
•In case of failure always warn the
installer.
•Remove the voltage and pressure from
the unit before starting the activities see
§7.2.
•Pressing ON/OFF does not remove the
voltage from the unit.
WARNING
There are hot parts below the cover. Let the
unit cool down before starting the activities.
NOTE
In case of a failure the red LED is lit. The
failure report appears in the display.
NOTE
With the types S6A-R and S6A-R 2P the
seriousness of the failure determines whether
the whole unit or a part of the unit switches
off. With partly switching off the refilling
process remains active. In this case both the
red and the green LEDs are lit.
G
C
E
B
A
F
DH
OBJ_DOKU-75-001.fm Page 33 Thursday, January 29, 2009 1:34 PM

34 English User manual - version 1.1
7.3 Failure table
General
The letter indications comply with the main figure in §
2.1. An overview of the replacement parts has been
included in § 8.2.
Problem Possible cause Correction
Err 3 Syst.temp. too low
There is a risk of freezing.
The temperature of the system fluid is
< 0 °C.
Provide a temperature of > 0 °C.
Err 4 Syst.temp. too high
There is a risk of boiling.
The temperature of the system fluid is
> 90 °C.
Provide a temperature of < 90 °C.
Err 5 Entrance flow
The flow in the inlet line has been
blocked *).
The solenoid valve (N) in the inlet line
does not open.
Replace (a part of) the solenoid valve.
A valve in the inlet line is closed. Open the valve.
The inlet line has been blocked. Remove the blocking.
The pressure switch (S) is defect. Replace the pressure switch.
Err 6 Flow
The flow in the outlet line has been
blocked *).
One of the solenoid valves (N) is not
closing.
Replace (a part of) the solenoid valve.
The valve in the outlet line is closed. Open the valve.
The outlet line has been blocked. Remove the blocking.
The pump (O) does not run. Check the pump. Check and replace
the pump fuse in the control unit.
The unit sucks in air during the
vacuum phase.
Replace the automatic air vent.
The pressure switch (S) is defect. Replace the pressure switch.
Err 7 Fluid lack vessel
There is a risk of running dry, the fluid
level in the vessel is at the minimum.
The automatic air vent (A) is defect or
blocked.
Replace the automatic air vent.
The vessel has not been filled. Fill the vessel (see § 5.5.4).
The level switch (H) is defect. Replace the level switch.
The unit runs continuously and does
not switch off automatically.
The SmartSwitch does not seem to
work*).
The content of dissolved gases has
not reached the minimum yet.
Check whether there is a possibility of
gases entering.
The SmartSwitch (R) is defect. Disconnect the hose on the
automatic air vent. Replace the
SmartSwitch if the unit does not
switch off after 10 minutes.
The automatic air vent (A) is defect. Check whether gas is released
through the valve. Replace the
automatic air vent when no gas is
released.
The unit runs maximally 10 min. per
degassing period. Gases remain in
the installation.
The SmartSwitch does not seem to
work*).
The SmartSwitch (R) is defect. Check whether gas is released
through the valve. Replace the
SmartSwitch if gas is released.
The automatic air vent (A) is defect. Replace the automatic air vent.
*) The refill mode remains active, this applies to types S6A-R and S6A-R 2P.
OBJ_DOKU-75-001.fm Page 34 Thursday, January 29, 2009 1:34 PM

User manual - version 1.1 English 35
Specific for types S6A-R and S6A-R 2P
7.3.1 Resetting the unit
1. Press MENU. Select User menu > Manual
operation using Sand T. Press ENTER.
2. Select Manual operation reset using Sand
T. Press ENTER.
Problem Possible cause Correction
Err 1 Psystem too low
The system pressure is below 1 bar.
A failure in the installation. Provide a system pressure of > 1 bar.
There is a leak in the installation. Repair the leak.
The pressure sensor (Q) is defect. Replace the pressure sensor.
Err 2 Psystem too high
The system pressure exceeds the set
maximum.
A failure in the installation. Provide a system pressure that is
below the set value.
The set value is too low. Increase the set value.
The pressure sensor (Q) is defect. Replace the pressure sensor.
Err 10 Refill flow too low
There is no or little supply of refill
fluid*).
A valve in the refill line is (partly)
closed.
Open the valve.
The solenoid valve (N) in the refill line
does not open.
Replace (a part of) the solenoid valve.
The refill line has been blocked. Remove the blocking.
The water flow meter (G) is defect. Replace the water flow meter.
Err 11 Refill valve
Undesired supply of refill fluid. The
refilling does not stop.
The solenoid valve (N) in the refill line
does not close.
Replace (a part of) the solenoid valve.
Err 13 Refill freq. too high
Refilling takes place too frequently.
There is a leak in the installation. Repair the leak.
Check the setting Max. refill
freq.
Err 14 Refill time too high
Refilling takes too long.
There is a leak in the installation. Repair the leak.
Check the setting Alarm refill
after:
Err 15 Refill quantity
Too much is added.
There is a leak in the installation. Repair the leak.
Check the setting Alarm refill.
*) The refill mode remains active, this applies to types S6A-R and S6A-R 2P.
OBJ_DOKU-75-001.fm Page 35 Thursday, January 29, 2009 1:34 PM

36 English User manual - version 1.1
8 MAINTENANCE
8.1 Periodic maintenance
1. Annually replace the interior of the solenoid valves
(N).
8.2 Replacement parts
The letter indications comply with the main figure in
§2.1.
/i
Article number Letter Description
15.552 O Shaft sealing for pump type CR1-13/1-9 AAA HQQE
15.553 O Gasket set for pump type CR1-9 and CR1-13
15.554 O Condensator for pump type CR1-13
15.790 O Condensator for pump type CR1-9
15.510 O Pump type CR1-13 AAA HQQE (50 Hz)
15.511 O Pump type CR1-9 AAA HQQE (60 Hz)
15.512 W Cover
12.023 N Solenoid valve (excluding coil)
12.022 N Coil for solenoid valve
12.018 N Interior for solenoid valve
12.021 T Pressure gauge
15.513 - Non-return valve
15.514 A Automatic air vent
13.468 S Pressure switch
15.515 U Control unit (cover incl print) (S6A)
15.784 U Control unit (cover incl print) (S6A-R)
15.785 U Control unit (cover incl print) (S6A-R 2P)
15.516 J Temperature sensor
15.517 R SmartSwitch
15.518 I, P Adjustment valve
13.466 H Level switch
15.519 G Water flow meter (S6A-R and S6A-R 2P)
15.520 Q Pressure sensor (S6A-R and S6A-R 2P)
15.521 K Pump type PSAM70/A (S6A-R 2P) (50 Hz)
15.522 K Pump type PSAM706/A (S6A-R 2P) (60 Hz)
OBJ_DOKU-75-001.fm Page 36 Thursday, January 29, 2009 1:34 PM

User manual - version 1.1 English 37
8.3 Maintenance card /i
Type :
Serial number:
Installation date:
Installed by firm:
Installed by technician:
Inspection date: Technician: Initials:
Nature of the maintenance:
Inspection date: Technician: Initials:
Nature of the maintenance:
Inspection date: Technician: Initials:
Nature of the maintenance:
Inspection date: Technician: Initials:
Nature of the maintenance:
Inspection date: Technician: Initials:
Nature of the maintenance:
Inspection date: Technician: Initials:
Nature of the maintenance:
OBJ_DOKU-75-001.fm Page 37 Thursday, January 29, 2009 1:34 PM

38 English User manual - version 1.1
9GUARANTEE
9.1 Terms of guarantee
•The guarantee for Spirotech products is valid until 2
years following the purchasing date.
•The guarantee lapses in cases of faulty installation,
incompetent use and/or non-authorised personnel
trying to make repairs.
•Consequential damage is not covered by the
guarantee.
10 CE STATEMENT
10.1 Declaration of conformity /i
EU declaration of conformity
We, Spirotech bv, Churchilllaan 52, Helmond NL, declare entirely on our own responsibility that the products
SpiroVent Superior S6A / S6A-R / S6A-R 2P
to which this declaration applies, comply with the standards:
EN 292-1, EN 292-2, EN 809, EN 60204-1, EN60335-1,
EN 55014-1 and EN 55014-2, EN 61000-3-2, EN 61000-3-3, EN 61000-6-2 and EN 61000-6-4.
in accordance with the stipulations of:
* the Machine Directive 89/392/EEC, amended by directives 91/368/EEC, 93/44/EEC, and 93/68/EEC
* the Low Voltage Directive 2006/95/EC
* The EMC Directive 89/336/EEC, amended by directives 92/31/EEC and 93/68/EEC.
Helmond, January 2009,
Daphne Scholten
General Manager
OBJ_DOKU-75-001.fm Page 38 Thursday, January 29, 2009 1:34 PM

The manufacturer reserves the right to make changes without prior notification.
© Copyright Spirotech bv
Information given in this brochure may not be reproduced complete or in part without the prior written consent of Spirotech bv.
Spirotech bv The Netherlands www.spirotech.com
This manual suits for next models
3
Table of contents
Other Spirotech Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Baileigh Industrial
Baileigh Industrial BB-12010H Operator's manual

VEMAG
VEMAG ROBOT HP7C operating instructions

SMC Networks
SMC Networks EX260-VIL1 Operation manual

Lennox
Lennox SYSTEMA EOLO LXC 50 manual

STABILUS
STABILUS ACE MC33-V4A Operating and mounting instructions

Festo
Festo EAMM-A-T42-55A Assembly instructions

Kval
Kval EFX Service manual

Emerson
Emerson Yarway Installation, operation and maintenance instructions

ABB
ABB A130-M66 Operation manual

DOGA
DOGA BA PC Series instruction manual

Zimmer
Zimmer MATCH LWR50L-27 Series Installation and operating instructions

Laars
Laars MV2 Installation & operation instructions