S+S Regeltechnik Rymaskon 600 User manual

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
Room control unit with colour touch screen,
with BACnet or Modbus connection
Controller for controlling and regulating
temperature, fan, light (1 zone) and
blind (2 zones)
G
MOD2.160 |Rev. 2022 - V12 DE | 22. 04. 2022

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
2
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
INSTALLATION AND
COMMISSIONING
IMPORTANT NOTES
Only the valid edition of our conditions and the valid “General Conditions for the Supply of
Products and Services of the Electrical and Electronics Industry” (ZVEI conditions) and
the supplementary clause “Extended Retention of Title” apply as the terms and conditions
regulating this purchase.
The following points must also be complied with:
- These instructions must be read before installation and commissioning,
and all of the specifications that they contain must be complied with.
- The units must only be connected to an extra-low safety voltage in a de-energised condition.
Use shielded cables to avoid damage to the unit and faults (e.g. resulting from voltage induction),
avoid parallel routing with live lines, and comply with the EMC directives.
- This unit must only be used for its intended purpose, whereby the applicable VDE safety regulations and
all regulations issued by the regional and national regulatory authorities, TÜV and local energy providers
must be complied with. The purchaser must ensure that the relevant building and safety regulations are
complied with, and must avoid hazards of all kinds.
- No warranty or liability whatsoever will be accepted for defects and damage arising from improper
use of this unit.
- The warranty and liability excludes consequential damage caused by a fault in this unit.
- The units must only be installed and commissioned by qualified personnel.
- Only the technical data and connecting conditions specified by the installation and operating instructions
which are included in the scope of delivery of the unit apply. Deviations from the depictions contained in
the catalogue are not additionally listed, and are possible as a result of technical progress and the
continuous improvement of our products.
- Any alterations made to the unit by the user will void the warranty.
- This unit must not be installed close to sources of heat (e.g. radiators) or their heat flow. Avoid direct
solar irradiation or heat radiation from similar sources (powerful lamps, halogen spotlights).
- Operating this unit close to other devices that do not comply with EMC directives may influence the
functionality thereof.
- This unit must not be used for monitoring purposes which serve the purpose of protecting persons
against hazards or injury, as an Emergency Stop switch on systems or machinery, or for any other
similar safety-related purposes.
- The housing dimensions and the dimensions of accessories may differ slightly from the specifications
of these instructions.
- Changes to these documents are not permitted
- In cases of complaint, we will only accept complete units returned in their original packaging.
Commissioning is mandatory and may only be performed by qualified personnel! Please read these instruc-
tions prior to installation and commissioning, and comply with the specifications that they contain!
Mounting shall take place while observing all relevant regulations and standards applicable for the place of
measurement (e.g. such as welding instructions, etc.). It is particularly important to comply with the
following:
- VDE ⁄ VDI technical temperature measurements, directives, measurement set-ups for
temperature measurements.
- EMC directives
- It is imperative to avoid parallel routing of current-carrying lines
- We recommend the use of shielded cables with the shielding attached to the DDC/PLC at one side.
Before mounting, make sure that the existing technical parameters of the measuring instrument comply
with the actual conditions at the place of utilization, particularly with regard to:
- the measuring range
- the maximum permissible temperature and humidity
- the protection type and protection class
- oscillation, vibration and impacts must be avoided (< 0.5 g)
Devices with integrated CO2-Sensor
Devices with integrated CO2-Sensor have
an automatic calibration of the carbon dioxide measurement –
ABC logic.
The Automatic Background Logic is a self-calibrating mechanism that is suitable for use in
applications in which the CO2 concentration regularly drops to fresh air level (350 - 500 ppm).
This should typically happen at times during which the rooms are unoccupied.
The sensor reaches its normal accuracy after 24 hours of continuous operation in an environment which
has been exposed to a fresh air supply of 400 ppm CO2. The deviation error remains minimal with at least
4 cases of sensor exposure to fresh air within 21 days. The ABC logic requires continuous operating
cycles of longer than 24 hours in order to function properly.

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
3
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
INSTALLATION
CONFIGURATION
Terminating resistors may only be installed at the ends of the bus line.
No more than two line terminators are permitted in networks without repeaters.
The bias resistors for bus level definition in the idle state are usually activated at the
Modbus master / repeater.
The maximum number of subscribers per Modbus segment is 32 devices.
With a greater number of subscribers, the bus must be subdivided into several
segments separated by repeaters. The subscriber address can be set from 1 to 247.
A cable with a twisted-pair data line / power supply line and copper shielding braid must be
used for the bus line. The line capacitance should be less than 100 pF/m (e.g. Profibus cable).
The communication interface must be configured from the unit (see parameter table - System page 42).
All other parameters can also be changed via the Modbus master.
Changed communication parameters are activated when Setting Mode is exited; the unit performs a
soft reset. Alternatively, the new settings can also be activated by switching the unit off and on again
(deactivate and reactivate supply voltage).
The configuration parameters are stored in the non-volatile memory of the controller.
After changing the configuration via the display, the new parameters are saved when the controller
returns to Normal Display Mode.
If the changes were made via the bus (Modbus), the parameter for updating the non-volatile memory is
required in order to force saving. If configuration takes place via the display, the parameters are saved
after an expiry time or when the settings menu is closed.
An
existing configuration
can be
transferred
to other units using the
RYMASKON USB-CT
configuration tool (see next page).
General layout of bus structure
Slave n
MODBUS
RTU-Master
RS-485
Line
termination
Line
termination
Active
branch
Passive
branch
Stub line
Trunk line
Stub line:
shorter 20m
Multiple branch n:
shorter 40m/n
General layout of bus structure
Slave 1 Slave 2
LA LA
Bus topology with terminating
and bias resistors
Bus topology with terminating and bias resistors
A (D1) D+
B (D0) D–
MODBUS
RTU-Master
Slave 1 Slave 2
5 V
Common
(GND)
Line
termination
Pull-down /
bias resistor
Pull-up /
bias resistor
RBIAS
RBIAS
RAB
Line
termination
RAB

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
4
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
PC/Laptop
System
USB
RYMASKON
USB CT
RYMASKON
500/600/700
KEY FEATURES
Basic model Typ 610 • 24 V AC/DC voltage supply
• 3.5 inch touch display
with background lighting
• Modbus or BACnet
• Wall mounting on standard in-wall flush boxes
• Integrated temperature sensor (basic equipment)
• Integrated humidity sensor
• Integrated CO2 sensor (optional)
• Regulation of heating, cooling, fan
directly through analogue outputs (0–10 V)
• Operation of temperature,
fan, light (1 zone),
and sun protection (2 zones)
via touch display
• 3 analogue outputs (0–10 V)
for controlling heating/cooling valves
and EC motor
• 2 analogue inputs (0–10 V)
for external sensors
• 1 digital input (potential-free)
• Operating modes Comfort (Normal),
OFF, Party (Boost), ECO, Frost Protection
RYMASKON USB-CT
Configuration tool
for rapid transfer of the
unit configuration
A configuration can be transferred to other units.
To do so, a unit must first be configured using the display via the bus.
After which the
RYMASKON USB-CT
and software on the PC can be used to transfer the configuration to other units.
The current software and detailed information are available in the
RYMASKON USB-CT
download area (spluss.de/r/2L6VM.htm).
Connection plan of the configuration tool

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
5
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
The
RYMASKON
®
500
/
600
/
700
series of room control units are designed for controlling the climatic
zone in residential, hotel and office rooms and individually regulate the heating/cooling steps of the internal
rooms. A colour touch display with modern icons is used for the visual display and operation at the location.
The product range is characterised by the variety of combination options of the individual components.
The
RYMASKON
®
600
Controller
series regulates through analogue outputs (0–10 V) up to two
heating
or cooling valves
(6-way valves can also be controlled) and the
fan
(EC ventilator).
The
sun protection
(blinds, shutters) can be controlled in two zones via the bus. Through the appropriate
symbols, it is possible to control the
light
instead of the sun protection.
In addition to the integrated temperature sensor, two external temperature sensors (NTC10K) or two
analogue sensors (0–10V) can also be connected. Measuring elements for relative humidity and CO2 are
also available. The devices are used in room climate technology, including convector fans, cooling ceilings
and heating/cooling systems. Wall mounting is performed on standard in-wall flush boxes. The devices are
optionally available with a Modbus or BACnet communication interface and in various type versions (see
number key).
The basic model
RYMASKON
®
610
Controller
with colour touch display (3.5"), in a white housing,
possesses an integrated temperature and humidity sensor (CO2 sensor optional), 2 analogue inputs for
external sensors (0–10 V), 1 digital input, 3 analogue outputs (0–10 V), and optionally with Modbus or
BACnet connection. The room control units are used for controlling temperature, fan, light (1 zone) and
sun protection (2 zones) directly via the analogue outputs or via the bus.
TECHNICAL DATA (Basic model)
Device type: room control unit with controller
Functions: temperature, fan, light (1 zone),
and sun protection (2 zones)
Communication:
Modbus RTU Slave
address range can be configured between 1...247
or
BACnet MS
/
TP
device ID 65100 (default) and MAC address can be configured between
1...127
RS 485 interface, max. 63 devices,
9600 / 19200 / 38400 / 57500 / 76800 Baud,
none / even / odd parity, 1 / 2 stop bits
Power supply: 24 V AC/DC (± 15 %)
Power consumption: max. 1.92 W
Inputs: 2 analogue inputs 0–10V
1 digital input (potential-free), Impedance <1kOhm
Outputs: 3 analogue outputs 0–10V (heating, cooling, fan)
input impedance > 100kOhm
Operating mode: Comfort, ECO, OFF, Boost, Frost Protection
Control element:
3.5" touch display
with backlighting,
cut-out approx. 50 x 75 mm, resolution 320 x 480 pixels, 255,000 colours
TEMPERATURE
Sensor: integrated temperature sensor
Measuring range: –40...+125 °C
Accuracy: typically ±0.5 °C at +25 °C
HUMIDITY
Sensor: integrated humidity sensor
Measuring range: 0...100 % r.H.
Accuracy: typically ±2 % r.H. (20...80 % r.H.) at +25 °C
CARBON DIOXIDE (CO2)
Sensor: optical NDIR sensor (non-dispersive infrared technology),
with automatic calibration
Measuring range: 0...5000 ppm
Accuracy: typically ±50 ppm ±3 % of the measured value at +25 °C
Electrical connection: 0.14–1.5mm², via screw terminals
Housing: plastic, polycarbonate material, self-extinguishing,
white colour (optionally black or chrome), weight approx. 220g
Housing dimensions: approx. 88 x 112 x 14.5 mm (on-wall)
approx. 88 x 112 x 20.5 mm (on-wall with CO2 sensor)
approx. 52 x 53 x 28.5 mm (in-wall)
Mounting: wall mounting on in-wall flush box, Ø 55mm
Ambient temperature: 0...+50°C (operation); –30...+70°C (storage)
Permitted humidity: 0...95 % r. H., (non-precipitating air)
Protection type:
IP 20
(
according to
EN 60 529)
Standards: CE conformity,
according to EMC directive 2004/108/EU, Low-Voltage directive 2006/95/EU,
according to
EN 61000-6-1/3, EN 60730-1, EN 6100-4-2/4/5/11
DESCRIPTION
Introduction and
technical data

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
6
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
RYMASKON
®
610
Controller (basic model)
Type ⁄ WG02 Communi-
cation
Measuring
element
Control system Colour Display Item No.
Rymaskon 612-MOD-RH-AI Modbus
T
|
RH T
|
V
| 2
S
|
L
white ■RYM6-10CM-2112-000
Rymaskon 612-MOD-RH-CO2-AI Modbus
T
|
RH
|
CO2 T
|
V
| 2
S
|
L
white ■RYM6-10CM-2312-000
Rymaskon 612-BAC-RH-AI BACnet
T
|
RH T
|
V
| 2
S
|
L
white ■RYM6-10CB-2112-000
Rymaskon 612-BAC-RH-CO2-AI BACnet
T
|
RH
|
CO2 T
|
V
| 2
S
|
L
white ■RYM6-10CB-2312-000
Measuring element /
control system:
T
= Temperature sensor
(basic equipment)
RH
= Humidity sensor
CO2
= Carbon dioxide sensor
T
= Temperature
V
= Fan
S
= Sun protection (2 zones)
L
= Light
Channel configuration:
2AI
2 analogue inputs (0–10 V DC) instead of
2RI
1DI
1 digital input (potential-free)
3AO
3 analogue outputs (0–10 V DC) for heating, cooling, fan
Type variants: Basic model
Typ 610
available from stock – freely configurable type variants available upon request!
For configuration options, see number key (above).
ACCESSORIES
RYMASKON USB_CT
Configuration Tool
for quick transfer of the device configuration
from the PC to all devices in the building
1901-51Z3-0002-000
Pos. 1–4 Type name
RYMASKON 600 RYM6
Pos. 5 Channel configuration
Type 610
2RI
,
1DI
,
3AO
(h,c,f) 1
Type 620
1RI
,
1DI
,
2AO
(h,c),
3RO
(f) 0.5A 2
Type 630
1RI
,
1DI
,
2AO
(h,c),
3RO
(f) 7A 3
Type 640
2RI
,
1DI
,
1AO
(f),
2DO
(h, c, PMW) 4
Type 650
2RI
,
1DI
,
1AO
(EC-f),
4RO
(h,c,f) 0.5A 5
Type 660
2RI
,
1DI
,
2DO
(h, c, PMW),
3RO
(f) 7A 6
Pos. 7 Device type
Controller C
Pos. 8 Communication
Modbus M
BACnet B
Pos. 9 Voltage supply
24V AC/DC 2
Pos. 10 Additional measuring elements
without
*
0
RH
(rel. humidity) 1
CO2
(carbon dioxide) 2
RH
+
CO2
3
Pos. 11 Extra options
without 0
AI
instead of
RI
1
Pos. 12 Housing colour
black 1
white 2
chrome 3
P o s . 5
RI
Resistance input (NTC10K)
RO
Relay output (0.5A / 7A)
AI
Analogue input (0–10 V DC) instead of
RI
AO
Analogue output (0–10 V DC)
DI
Digital input (potential-free)
DO
Digital output (potential-free)
(h) Heating
(c) Cooling
(f) Fan
(EC-f) EC fan
(PMW) Pulse Width Modulation
P o s . 10
*
The
temperature sensor
forms
part of the basic equipment and
is included in the option "without"
additional measuring elements.
RYMASKON
®
600
Controller (series)
Number key for type versions 6MYR 000xxx2xC0x

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
7
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
88
52
53
112 28.5
20.5 (CO2-Sensor)
14.5 (Standard)
TOUCHSCREEN
50 x 75
DIMENSIONAL DRAWING
Dimensional drawing
[mm]
WIRING
Connection diagram
Typ 610
(
Basic model)
WARNING:
Switch off the power supply before commencing the wiring work!
AI2
AI1
DI1
G0
B–
A+
Y2
Y3
Y1
G0
24V
G0
RYMASKON 610
0..10V DC Analogue Outputs
Y1 AO1 – default fan speed
Y2 AO2 – default heating stage 1
Y3 AO3 – default cooling stage 1
24V 24V AC/DC Supply
G0 GND
0-10V Analogue Inputs
AI1 Analogue Input 1 (RI optional)
AI2 Analogue Input 2 (RI optional)
DI1 Digital Input (potential-free)
Modbus / BACnet MS/TP
A+
RS485 A+
B–
RS485 B–

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
8
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
Connection diagram
Typ 620
(0.5 A)
Typ 630
(7A)
Connection diagram
Typ 640
WARNING:
Switch off the power supply before commencing the wiring work!
WARNING:
Switch off the power supply before commencing the wiring work!
Y3
Y2
AI1
DI1
G0
B–
A+
R
COM
RLY1
RLY2
RLY3
G0
24V
RYMASKON 620
230V 0.5A Relay Outputs
RYMASKON 630
230V 7A Relay Outputs
RLY1 RO1 – fan speed 1
RLY2 RO2 – fan speed 2
RLY3 RO3 – fan speed 3
R
COM
Relay Common
24V 24V AC/DC Supply
G0 GND
0..10V DC Analogue Outputs
Y2 AO2 – default heating stage 1
Y3 AO3 – default cooling stage 1
0-10V Analogue Input
AI1 Analogue Input 1 (RI optional)
DI1 Digital Input (potential-free)
Modbus / BACnet MS/TP
A+
RS485 A+
B–
RS485 B–
AI2
TR1
AI1
DI1
G0
B–
A+
Y1
TR2
G0
G0
24V
RYMASKON 640
0..10V DC Analogue Output
Y1 AO1 – default fan speed
24V AC 1A Triac (switched to 0V – G0)
TR1 Triac1 (DO1) – default heating PWM
TR2 Triac2 (DO2) – default cooling PWM
24V 24V AC/DC Supply
G0 GND
0-10V Analogue Inputs
AI1 Analogue Input 1 (RI optional)
AI2 Analogue Input 2 (RI optional)
DI1 Digital Input (potential-free)
Modbus / BACnet MS/TP
A+
RS485 A+
B–
RS485 B–

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
9
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
Connection diagram
Typ 660
Connection diagram
Typ 650
WARNING:
Switch off the power supply before commencing the wiring work!
WARNING:
Switch off the power supply before commencing the wiring work!
AI2
TR1
AI1
DI1
G0
B–
A+
R
COM
RLY1
RLY2
RLY3
TR2
G0
24V
RYMASKON 660
230V 7A Relay Outputs
RLY1 RO1 – fan speed 1
RLY2 RO2 – fan speed 2
RLY3 RO3 – fan speed 3
R
COM
Relay Common
24V 24V AC/DC Supply
G0 GND
24V AC 1A Triac (switched to 0V – G0)
TR1 Triac1 (DO1) – default heating PWM
TR2 Triac2 (DO2) – default cooling PWM
0-10V Analogue Inputs
AI1 Analogue Input 1 (RI optional)
AI2 Analogue Input 2 (RI optional)
DI1 Digital Input (potential-free)
Modbus / BACnet MS/TP
A+
RS485 A+
B–
RS485 B–
AI2
Y3
AI1
DI1
G0
B–
A+
R
COM
RLY1
RLY2
RLY3
RLY4
G0
24V
RYMASKON 650
230V 0.5A Relay Outputs
RLY1 RO1 – fan speed 1
RLY2 RO2 – fan speed 2
RLY3 RO3 – fan speed 3 *
RLY4 RO4 – on-off valve – default
heating stage 1
R
COM
Relay Common
24V 24V AC/DC Supply
G0 GND
0..10V DC Analogue Output
Y3 AO1 – default cooling stage 1*
0-10V Analogue Inputs
AI1 Analogue Input 1 (RI optional)
AI2 Analogue Input 2 (RI optional)
DI1 Digital Input (potential-free)
Modbus / BACnet MS/TP
A+
RS485 A+
B–
RS485 B–
Alternatively, relay 3 (RLY3) can be
configured for another on-off valve
(cooling stage 1) and the 0...10V output (Y3)
for an EC fan.
*

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
10
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
The figures below illustrate some sample use cases with A/C controllers
of the
RYMASKON
®
610
Controller
series.
These controllers are very versatile and can easily be configured for the majority of room
heating and cooling tasks, including fan, blower, cooling ceiling and zone heating control.
Please note the setting options described on the following pages; in case of questions,
please contact our sales team.
APPLICATION
EXAMPLES
4-PIPE FAN COIL UNIT CONTROL WITH MODULATING EC FAN
Heating Cooling
0-10V DC
0-10V DC
0-10V DC
Heating Control
0-10V DC EC Fan Control
0-10V DC EC Fan Control
Digital Input
Condensation Switch
Digital Input Night
Override e.g. Door/Window Switch
Digital Input Day
Override e.g. PIR or
Override Night e.g. Window/Door
External Sensor
Fan Coil Unit
RYMASKON 600 Controller
with CO2 and RH Option
TV2TV1
0-10V DC
CHILLED CEILING AND ZONE HEATING APPLICATION WITH FAN ASSISTED FRESH AIR
Heating / Cooling
RYMASKON 600 Controller
with CO2 Option
KW
Condensation Switch
4-PIPE FAN COIL UNIT CONTROL WITH MODULATING EC FAN
Heating Cooling
0-10V DC
0-10V DC
0-10V DC
Heating Control
0-10V DC EC Fan Control
0-10V DC EC Fan Control
Digital Input
Condensation Switch
Digital Input Night
Override e.g. Door/Window Switch
Digital Input Day
Override e.g. PIR or
Override Night e.g. Window/Door
External Sensor
Fan Coil Unit
RYMASKON 600 Controller
with CO2 and RH Option
TV2TV1
0-10V DC
CHILLED CEILING AND ZONE HEATING APPLICATION WITH FAN ASSISTED FRESH AIR
Heating / Cooling
RYMASKON 600 Controller
with CO2 Option
KW
Condensation Switch
4-PIPE CONVECTOR UNIT CONTROL
WITH MODULATING EC FAN
COOLING CEILING AND ZONE HEATING APPLICATION
WITH FAN FOR FRESH AIR SUPPLY

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
11
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
The following diagrams are typical display options for the
RYMASKON
®
600
controller
.
The multi-colour LCD touch display facilitates making the required settings
and visualises the actual state of the controlled system with easily understandable icons.
USER INTERFACE
Screens, lighting
and calibration
The small
action circle
(grey) alternately displays the current sensor values (if enabled).
The large
setpoint ring
illustrates the heating or cooling consumption (red/blue).
If temperature control is in the “dead zone”, the ring is white.
The colour intensity changes depending on the difference between the actual temperature and
the currently controlled heating/cooling temperature (setpoint). From a delta of 2°C (3.6°F) or more,
the entire ring is red/blue.
+-
ENERGY RING COLOURS
MEASURED
TEMPERATURE
Deadzone
HDz - 2°/ 3.6°F CDz + 2° / 3.6°F
calcSP
CDz
HDz
Screen backlighting (standby)
If the display of the main screen is not touched for 30 sec., the display will be dimmed to the configured
standby value (default 5/max. 20).
Use the settings to adjust the brightness of the touch display
(System – Brightness). If this value is configured to 0, the display is completely dark when it is inactive.
Touch the display to automatically re-enable the backlighting.
Tap the icon on the
main screen
to immediately dim the display to the set value.
Tap the icon again in standby to completely switch off backlighting.
Screen calibration
The touch display can be re-calibrated during a unit reset.
The unit performs the following two types of resets:
1. When the unit starts up (power supply present)
2. After completing parameter configuration in setting mode and returning to the main screen.
During reset (dark screen), swipe in the direction of all four edges of the display and then follow the
instructions. Confirm recalibration with “OK”.
Fig. 1a
Main screen
Room
23
.5
°C
A
Blind 1 Blind 2
21
.
0
°C
°C
MAIN SCREEN
Fig. 1b
Auxiliary screen
(opens by tapping the grey action circle
on the main screen)
AUXILIARY SCREEN
Blind 1
Fig. 1c
Blind screen
(opens by tapping the Blind icon
on the main screen)
BLIND SCREEN

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
12
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
MAIN SCREEN
ICONS
Screen areas and
explanation of icons
Arrow key
UP
Arrow key
DOWN
Room
23
.5
°C
A
21
.
0
°C
Blind 1
°C°F
RED RING
(heating)
BLUE RING
(cooling)
WHITE RING
(no heating/
cooling)
STATUS BAROPERATING MODE
SETPOINT RING
BUS
NOTIFICATION
TEMPERATURE
LIMITING
DISPLAY
LOCK (active)
OFF MODE
(setpoint)
BOOST MODE
(active)
READING DISPLAY
Sensor value + Designation
(languages EN/DE/FR/ES/IT)
BUTTON
to the
SUB SCREEN
(→ Page 32)
for more settings, such as parameter
configuration via the display
(→ Page 35)
Icon indicates that
the limit value control
is active.
TEMPERATURE
UNITS
FAN/
BLOWER SPEEDS
A
= AUTOMATIC
M
= MANUAL
1 / 2 / 3 / 6 - SPEED
CONTROL POSSIBLE
ALARM
INFORMATION
ACTION CIRCLE CONTROL BAR
HIGH/LOW LIMIT CONTROL
BRIGHTNESS
DISPLAY
Outside
10
.5
°C
Humidity
45
%RH
MAIN SCREEN
Fig. 2
CONTROL
BLINDS
(max. 2 zones)
LIGHT
ECO MODE
(active)
ALARM
(with bell icon)
configurable
(→ Page 30) The
main screens
of the units have several touch-sensitive areas to change the settings.
• Arrow keys
UP ▲
and
DOWN ▼
to change the current setpoint (temperature/percentage).
• Small
action circle
to display the measured temperature, the CO2 and humidity content
of the air and as a button to access the sub screen.
• Function-based toggle icon shows the
OFF icon
in OFF mode and
the
ECO icon
in ECO mode to cancel the respective modes.
• The
boost icon
enables a time-controlled boost phase if boost mode is active.
•
Fan
icon and blower bar to display and change the fan speed
in up to 7 blower speeds (Auto-1-2-3-4-5-6), if released.
•
Blinds
icon as a button to access the blinds screen
to control the blinds (OPEN/CLOSE) and the slats’ angle of inclination.
•
Lights
icon to switch ON/OFF and to change the light intensity of the room lighting, if released.

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
13
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
TEMPERATURE UNIT
Selection of degrees Celsius (
°C )
or degrees Fahrenheit (
°F)
WARNING!
Changing the default setting for
the temperature unit will set the
defaults for all other parameters.
Changing the default setting for the
temperature unit is intended to be
performed as necessary at the start
of commissioning.
Fig. 3a
Temperature in °C
Fig. 3b
Temperature in °F
Room
22
.7
°C
18
.
3
°C
°C°F
Room
72
.8
°F
65
.
0
°F
°C°F
If the icon for switching between °C /°F is enabled (Settings - Display - Show Unit Swap - Enabled),
the temperature displays can be switched between degrees Celsius and Fahrenheit by tapping the
icon on the main screen.
This option is especially useful for applications in hotels etc. with international guests.
You can also determine which temperature unit (°C /°F) is set as the default value on
the unit in the settings (Systems, Native Units).
If the unit default setting is changed, the unit will reload the factory default settings
with the changed unit for all temperature displays.

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
14
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
TEMPERATURE
CONTROL CIRCUIT
Temperature Control
Loop Operation
The controllers can control up to two heating and cooling stages. The default is one heating and one cooling stage.
Furthermore, use the digital input, the measured temperature or the bus to automatically switch between heating
and cooling mode (Changeover). This allows various control configurations:
• 1-/2-step heating control
• 1-/2-step cooling control
• 1-/2-step heating control and 1-/2-step cooling control (up to 3 outputs)
• 1-/2-step heating/cooling control (with automatic switching – Changeover)
The controller modulates the required output capacity for heating and cooling depending on the calculated target
and actual temperature using P or PI control. The calculated target temperature consists of the nominal target
temperature plus the adjustment made by the user.
In the preferences of the
RYMASKON
®
610
/
620
/
630
controllers
, the output capacity
for
heating stage 1
is linked to analogue output
Y2
(0–10VDC control) and the output capacity
for
cooling stage 1
is linked to analogue output
Y3
(0–10VDC control).
RYMASKON
®
640
/
660
controllers have
their
heating stage 1
linked to digital output
DO1
(PWM control) and
their
cooling stage 1
linked to digital output
DO2
(PWM control).
The control circuits can be configured to directly or inversely control the outputs.
In inverted mode, the output and/or the valve is regulated from 100 % to 0 %.
This can be set separately for each stage in the configuration parameters.
There is a “dead zone” (
HDz
+
CDz
) between heating stage 1 and cooling stage 1. P control in the “dead zone”
results in a heating and cooling consumption of 0 %. PI control in the “dead zone” regulates the heating and
cooling consumption to 0 % if the actual temperature is in that range for a longer period of time. The “dead zone”
tolerates variations in the target temperature range without opening the heating or cooling valves. The controller
has an integrated lock preventing simultaneous heating and cooling consumption.
Use
HDz
(Heating Deadzone) and
CDz
(Cooling Deadzone) to asymmetrically set the “dead zone” left and right of
the calculated setpoint
calcSP
. In some cases it may be important for the cooling process to respond more quickly
than the heating process if the actual temperature deviates from the setpoint.
NOTE:
Conceptually,
calcSP – HDz
is the effective target temperature for heating and
calcSP + CDz
the effective
target temperature for cooling. It is easier for the user to configure and calculate a single setpoint. The
dead zone limits are configured during commissioning to specify effective heating and cooling setpoints.
Users can adjust the target temperature using the arrow keys UP and DOWN.
The target temperature/dead zone changes as follows depending on the operating modes:
•
Comfort mode (standard mode):
The target temperature is adjusted by the users or specified via the bus and
shown on display. The calculated target temperature (calcSP) consists of the nominal target temperature and
the setting adjusted by the user on the display. The dead zone is adjusted according to the parameters to
“Heating DZ COMFORT” (HDz) and “Cooling DZ COMFORT” (CDz). The possible adjustment range is limited by
the parameter “SP Adj. Max” and “SP Adj. Min.” (default ±3°C).
•
ECO mode:
The nominal target temperature remains unchanged. Adjustments made by users are
disabled and the dead zone is adjusted to “Heating DZ ECO” (eHDz) and “Cooling DZ ECO” (eCDz)
according to the parameters.
•
OFF mode:
The control ensures that the configured antifreeze-setpoint is met (fSP).
Adjustments made by users are disabled.
NOTE:
If limit value control is enabled, the set upper and lower limits move the effective and/or calculated target
temperature as required (see chapter “Limit value control”).
+-
CONTROL OUTPUT
HEATING
STAGE 1
COOLING
STAGE 1
calcSP
RYM 610/620/630 - 0-10V DC
RYM 610/620/630 - 0-10V DC
RYM 640/660 - PWM
RYM 610/620/630 - 0-10V DC
RYM 610/620/630 - 0-10V DC
RYM 640/660 - PWM
HDz
MEASURED
TEMPERATURE
100%
0%
COOLING
STAGE 2
HEATING
STAGE 2
ECO Deadzone
2°C /
3.6°F
CDz
fSP
HDz = COMFORT Heating Deadzone
CDz = COMFORT Cooling Deadzone
calcSP= Calculated Setpoint
fSP= Frost Setpoint
eCDzeHDz
RYM610 = RYMASKON 610 has max. 3x 0 -10V DC outputs
RYM620/ 630 = RYMASKON 620/630 has max. 2x 0 -10 V DC outputs
RYM640/ 660 = RYMASKON 640/660 has max. 2x PWM 24V outputs
Note:

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
15
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
CHANGEOVER
Summer/winter mode
in one line
Heating/Cooling
ChangeOver
LIMIT VALUE
CONTROL
High/Low Limit Control
The main temperature control circuit of heating and cooling stages 1 can be
forcibly switched to heating or cooling mode via the bus (Changeover).
This makes it possible to use the same pipe for heating and cooling in different
seasons (summer / winter mode).
Configure and perform the switching to the following values:
• Digital input
(Digital Input Mode)
• Temperature measurement RI1
/
RI2
(RI1/RI2 Mode)
• Bus
(Changeover function)
If RI1/RI2 is selected, the system switches automatically
at the set temperature limits “Changeover High” (default: 25 °C)
and “Changeover Low” (default: 20 °C)
NOTE:
If the unit has analogue inputs
AI1
/
AI2
instead of
RI1
/
RI2
,
Changeover is only possible via the digital input or the bus.
If an
external temperature sensor
is connected (to RI1 or RI2) and
if the input is parameterised to “Floor (NTC10K)” (see chapter “Modes for
inputs RI1 and RI2”), the controller can be used for limit value control via
High Limit Setpoint
(default: 35 °C) and
Low Limit Setpoint
(default: 16 °C).
This function is enabled via the parameter “Limit Ratio”
(default: 0.0 = limit value control disabled).
For controls with the
upper limit value
(High Limit Setpoint), the target
temperature of the main control is reduced by the set value of the limit
ratio if the temperature on RI1/2 exceeds the upper limit value. Example:
If the value 2 is set for limit ratio, the target temperature is reduced by
2 degrees for every degree over the high limit setpoint.
Control using the
lower limit value
works vice versa:
For every degree that the temperature undercuts the lower setpoint,
the target temperature is increased by 2 degrees.
The value for the
target temperature reset
follows this formula:
setpoint reset = (limit setpoint - actual temperature RI1/2) × limit ratio
NOTE:
The target temperature shown on the display does not change
during these increases/decreases. The temperature limiting
icon points to an active reset phase.
NOTE:
The limit value control is enabled using the parameter “Limit Ratio”
(default: 0.0 = disabled).
NOTE:
In OFF mode, limit value control is disabled.
A
Room
20
.1
°C
21
.
5
°C
°C°F
Fig. 4
TEMPERATURE
LIMITING
The icon shows the active
limit value control.

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
16
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
Use the bus, the digital input (e.g., PIR) or
the display to switch the controller into
ECO mode
.
The mode is
enabled
on the display via the
sub screen
;
the mode is
disabled
via the
main screen
.
In ECO mode, the controller regulates the
temperature
in the ECO
dead zone (eHDz + eCDz) range for heating and cooling (see diagram).
Adjustments to the target temperature made by users are disabled.
In ECO mode, the control circuits for
CO2
and
humidity
are set to 0 %
(see chapter “CO2 and humidity control circuit”).
Depending on the configuration,
lighting
in ECO mode is set to 0 %
(switched off) or the current value is maintained.
If released, the toggle icon “Light” remains active (see chapter “Light”).
The current position of the
blind
is maintained in ECO mode.
If released, the “Blind” toggle icon remains active.
ECO MODE
Display and setting
of the ECO mode
TAP THE ICON
TO END
THE MODE
TAP THE ICON
TO ENABLE
THE MODE
ECO ICON
(active)
+-
CONTROL OUTPUT
calcSP
RYM 610/620/630 - 0-10V DC
RYM 610/620/630 - 0-10V DC
HEATING STAGE 2
HEATING STAGE 1
RYM 640/660 - PWM
RYM 610/620/630 - 0-10V DC
COOLING STAGE 1
COOLING STAGE 2
RYM 610/620/630 - 0-10V DC
RYM 640/660 - PWM
HDz
MEASURED
TEMPERATURE
100%
0%
ECO Deadzone
CDz
eHDz = ECO MODE Heating Deadzone
eCDz = ECO MODE Cooling Deadzone
(Default 4.0°C / 9.2°F)
calcSP= Calculated Setpoint (Default 21°C / 70°F)
eCDzeHDz
ECO MODE TEMPERATURE CONTROL
AUXILIARY SCREEN
Room
23
.5
°C
A
21
.
0
°C
Blind 1
MAIN SCREEN
Fig. 5 Fig. 1b
BLIND
(toggle icon active)
LIGHT
(toggle icon active
→ Page 22)

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
17
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
Room
23
.5
°C
A
8
.
0
°C
Blind 1
Use the bus, the digital input (e.g., PIR) or the display
to switch the controller into
OFF mode
.
The mode is
enabled
on the display via the
sub screen
;
the mode is
disabled
via the
main screen
.
In OFF mode, the output capacity for
temperature
,
CO2
,
humidity
and
fan
are set to 0 %.
Depending on the configuration, the
lighting
in OFF mode is set to 0 %
(switched off) and the toggle icon “Lights” is disabled (see chapter “Light”).
The current position of the
blinds
is maintained in OFF mode.
If released, the “Blind” toggle icon remains active.
If the room temperature in OFF mode drops below the antifreeze setpoint,
antifreeze
is enabled (see diagram).
The display shows the snowflake icon , the heating stages are set to
100 % and the fan speed to 33 %.
As soon as the temperature is 2 °C above the antifreeze setpoint,
antifreeze is switched off.
OFF MODE
Display and setting
of OFF mode
TAP THE ICON
TO END
THE MODE
TAP THE ICON
TO ENABLE
THE MODE
OFF ICON
(active)
+-
CONTROL OUTPUT
nSP
MEASURED
TEMPERATURE
100%
0%
OFF MODE TEMPERATURE CONTROL
2°C /
3.6°F
fSP fSP= Frost Setpoint (Default 8°C / 46°F)
nSP= Nominal Setpoint (Default 21°C / 70°F)
Note:
In frost condition the Fan Demand
is set @ 33%
AUXILIARY SCREENMAIN SCREEN
Fig. 6 Fig. 1b
BLIND
(toggle icon active)
LIGHT
(toggle icon inactive
→ Page 22)

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
18
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
CO2
CONTROL CIRCUIT
CO2 Sensor Control
Loop Operation
(Units with CO2 option)
Units with
CO2 sensor
can measure and monitor the CO2 content in the room air to control relevant applica-
tions on that basis and, e.g., increase the fresh air supply if the CO2 concentration is high. To lower the CO2
concentration, the control circuit can be linked to any of the physical outputs (
Y1, Y2, Y3
) or the fan (fan speed
source). As an alternative, use the CO2 control circuit for maximum consumption control
“
Max. VAV
”
or
“
Max.
Fan
”
(configurable in the parameters Y1, Y2, Y3 and fan speed source).
The CO2 control circuit corresponds to the CO2 setpoint and the CO2 proportional band. If configured for direct
control (typical) and the CO2 content exceeds the setpoint (limit value), the control circuit will start to modulate
the output capacity to 100 %. If the CO2 content in the proportional band range is above the setpoint, output
capacity is 100 %. Use the parameter settings to configure the control circuit. It can also be configured for
proportional and integral control (PI) by changing the integral reset time from 0 to a required higher value. Use
the parameter “CO2 Dir.” to change the direction of the actuator (direct, inverse).
In
OFF mode
, the output capacity of the CO2 control circuit is set to 0 %.
In
ECO mode
, the CO2 control circuit works the same way as in standard mode.
Use the configuration parameters to enable/disable the display of the CO2 sensor.
VAV maximum consumption (Max. Temp
/
CO2)
Each analogue output can be configured for “
Max. VAV
” (maximum volume flow).
In that case, the relevant output (
Y1, Y2, Y3
) takes on the maximum consumption capacity
of the CO2 and of the cooling temperature control circuit. Typically, this is used with
consumption-controlled ventilation to open ventilation flaps when more fresh air is needed
or to supply the room with fresh cooling air to lower the temperature.
Maximum blower consumption (Max. Temp
/
Hum)
Each analogue output can be configured for “
Max. Fan
”.
In that case, the relevant output (
Y1, Y2, Y3
) takes on the maximum consumption capacity of the
CO2 and of the blower control circuit. If the CO2 content is high and if the blower control circuit
consumption increases, this is a way to maximise the fan speed.
+
-
CONTROL OUTPUT
LOOP OUTPUT
CO2 CONTROL
CO2 Level
100%
0 ppm 2000ppm
PB
SP
0%
SP = Setpoint (e.g. 800 ppm)
PB = Proportional Band (e.g. 400ppm)
CO2 CONTROL LOOP
HUMIDITY
CONTROL CIRCUIT
Humidity Control
Loop Operation
(Units with RH option)
Units with
RH option
can measure and monitor the relative humidity in the room to control relevant applications on
that basis and, e.g., increase the fresh air supply if humidity is high.
For humidification and de-humidification, the control circuit can be linked to any of the physical outputs
(
Y1, Y2, Y3
)
or the fan (fan speed source).
As an alternative, use the humidity control circuit together with the temperature control circuit to control the fan
speed (
Max. Temp
/
Hum
, see chapter “Fan control”).
The direction of both outputs can be inverted to regulate the actuators from 100 to 0 % instead of from 0 to 100 %.
Use the configuration parameters to enable/disable the display of the humidity sensor.
+
-
CONTROL OUTPUT
LOOP OUTPUT
HUMIDIFICATION
DE-HUMIDIFICATION
HUMIDITY
100%
0%RH 100%RH
PB
SP
0%
SP = Setpoint (e.g. 50%RH)
PB = Proportional Band (e.g. 5%RH)
HUMIDITY CONTROL LOOP

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
19
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
AUXILIARY CONTROL
CIRCUIT
AUX Heating Control Loop
The controllers have an auxiliary control circuit for a
second zone
. This control circuit provides an
additional PI control function for applications needing an additional control circuit.
Use the AUX parameters in the settings or the bus to configure this additional control circuit.
To enable it, set “RI1 Mode“ or “RI2 Mode “ parameter to AUX control circuit.
To control the temperature in the second zone, assign the AUX control circuit to an analogue
output (
Y1, Y2, Y3
). Use the bus (not the display) to control the auxiliary control circuit.
NOTE:
RI2
is not available with
Type 620
.
The controller has a
boost icon
(if released),
and it can be linked to priority switching for a configurable boost time.
The
boost time
(timer)
can be configured from 0 to 480 minutes
(0 = permanently enabled, switch off boost using the display or the bus).
The remaining time is shown on the touch display (Fig. 7a).
The following configuration options are possible:
•
Boost disabled
(Disabled)
•
Heating stage 1
(Htg Stage 1)
•
Heating stage 1 + heating stage 2
(Htg Stages 1&2)
•
Cooling stage 1
(Clg Stage 1)
•
Cooling stage 1 + cooling stage 2
(Clg Stages 1&2)
•
Humidification
control circuit (Humidification)
•
De-humidification
control circuit (De-Humidification)
•
CO2
control circuit (CO2)
•
Fan
•
Aux
control circuit (Aux. Loop)
Digital input boost
(without timer)
If the digital input for boost mode was configured,
you
cannot exit
the mode on the display and it remains
active until the input status changes.
Digital input boost is shown with an icon and the
text
“
Boost
”
(instead of the setpoint) in the large circle (Fig. 7b).
BOOST
Display and setting
of the boost mode
TAP THE ICON
TO END
THE MODE
BOOST MODE
(active)
Room
23
.5
°C
5
Min.
Room
23
.5
°C
Boost
Fig. 7a
Remaining boost time
(timer in minutes)
Fig. 7b
Digital input boost
(without timer)

S+S REGELTECHNIK GMBH |THURN-UND-TAXIS-STR. 22 |D-90411 NÜRNBERG |GERMANY |FON +49 (0) 911 51947- 0 |www.S plusS.de
20
Operating instructions
RYMASKON®600 - BACnet
RYMASKON®600 - Modbus
Speed 0 0
...
8 %
Speed 1 8
...
25 %
Speed 2 25
...
41 %
Speed 3 41
...
58 %
Speed 4 58
...
74 %
Speed 5 74
...
92 %
Speed 6 92
...
100 %
FAN
ICONS AND DISPLAY
Fan icon and line bar chart
(blower speeds)
Room
23
.5
°C
A
21
.
0
°C
Blind 1
A
= AUTO
M
= MANUAL
TAP THE ICON TO
SET MANUALLY
(if released)
IF BLOWER IS ACTIVE,
(SPEEDS 1–6), THE
FAN ICON WILL ROTATE
AUTOMATIC CONTROL (
A
= AUTO) CAN BE
SELECTED VIA THE
BUS
OR ON THE
UNIT
.
MAIN SCREEN AUTO CONTROL
*CONTROLLED VIA THE BUS:
UNIT SWITCHES TO “
AUTO
”
AS SOON AS A NEW SPEED
IS SPECIFIED VIA THE BUS.
Speed 0
Speed 1
AUTO *
1 STEP + AUTO
Speed 0
Speed 1
Speed 2
Speed 3
AUTO *
3 STEP + AUTO
Speed 0
Speed 1
Speed 2
AUTO *
2 STEP + AUTO
Speed 0
Speed 1
Speed 2
Speed 3
Speed 4
Speed 5
Speed 6
AUTO *
6 STEP + AUTO
MANUAL CONTROL
MANUAL FAN SPEED
CONFIGURATION OPTIONS
None
No display
No Input
Display without manual adjustment
0 - 1
ON/OFF (
1 STEP
: 0 % - 100 %)
0 - 1 - 2
2 speeds (
2 STEP
: 0 % - 50 % - 100 %)
0 - 1 - 2 - 3
3 speeds (
3 STEP
: 0 % - 33 % - 66 % - 100 %)
0 - 1 - 2 - 3 - 4 - 5 - 6
6 speeds (
6 STEP
: 0 % - 16 % - 32 % - 50 % - 66 % - 82 % - 100 %)
Fig. 8
This manual suits for next models
9
Table of contents
Other S+S Regeltechnik Control Unit manuals

S+S Regeltechnik
S+S Regeltechnik RYMASKON 400-Modbus User manual

S+S Regeltechnik
S+S Regeltechnik Rymaskon 200-Modbus Series User manual

S+S Regeltechnik
S+S Regeltechnik THERMASREG FM Series Repair manual

S+S Regeltechnik
S+S Regeltechnik Rymakson 400-Modbus Repair manual

S+S Regeltechnik
S+S Regeltechnik Rymaskon 200-Modbus Series User manual

S+S Regeltechnik
S+S Regeltechnik RYMASKON 700 Series User manual