8
SECTION 4
INSTALLING THE SYSTEM
WARNING: The air supplied to the machine must be clean, free of moisture and lubricang uids;
failure to do this voids all warranes.
The AutoJet® VC10 Industrial Heated Spray System is powered by wiring into 480 VAC 1 ø service. Do not connect
power unl all wiring, and connecon of the system is complete.
4.1 FILLING THE HEATING LOOP
A circulang condioning line provides heated uid to all the jacketed components of the system. This line consists of
a 1/3 HP 480 VAC centrifugal pump, immersion heater, thermometer, pressure gauge, and return reservoir.
• Centrifugal pump- circulates the heated uid throughout all the jacketed components.
• Immersion heater- maintains the temperature set point of the heated uid and the process uid.
• Temperature controller- provides temperature regulaon to the in-line immersion heater.
• High limit switch- turns heater o at 300°F for fail safe protecon. Temperature feedback is provided by the
thermometer in the tank for reference.
• Level switch- veries that enough uid is in the system so that components are not damaged.
• Regulator- allows for the system to be lled with a pressurized source of water or glycol soluon. Deionized water
(DI) is recommended to limit mineral deposits. A 50/50 mixture of propylene (or ethylene) glycol and water must
be used for temperatures of 180 to 200°F. The regulator limits the pressure of the system for safe operaon.
• Return reservoir- provides room for expansion of the heated uid, and pressure relief for over lling of the
system. Note that all the condioning lines from the pump, through all jacketed components, and back to the
return reservoir must be run in series. Never split the ow path as this could result in cold spots.
DIRECTIONS FOR FILLING THE HEATING LOOP:
1) Begin by turning the disconnect switch to the “On” posion. Apply power to the system using the “Power On”
pushbuon. The amber indicator will light up.
2) Prior to the system being run for the rst me, the heang circuit must be lled with condioning uid. Connect
the condioning uid source to the ¼” NPT (F) valve in the middle of the standpipe.
3) To ll the reservoir, open the valve and adjust the regulator. The regulator should be set to 5 psi. The over-
pressurizaon valve past the regulator will open at 10 psi.
4) Open the air purge vents located on the return line and the pump; these will automacally purge air out of the
water line.
5) As condioning uid lls the reservoir, loosen the 1/2 G threaded level switch connecon recognizable by an O-
ring (boom connecon on the stand pipe).
6) Allow the uid and air mixture to escape from the loosened connecon unl no air bubbles are seen; hand-ghten
the sensor to begin building pressure.
8) Once the small, yellow light on the sensor is lit, allow the system to connue to ll for several minutes. Wait unl
the inlet regulator at the top of the standpipe levels o at a pressure, and make sure it is adjusted to 5 psi at a no-
ow condion.
9) Turn the pump on by using the selector switch on the system control panel. If the standpipe uid level drops below
the level sensor, the pump will automacally be turned o and the Pump On light will be o.
10) If water begins to leak out of the purge vents, ghten again.