ST Beta 20P Series User manual

Rev. B 12/2021
Operating Manual
IC:2-60-006-00-00534
1 PHASE PROGRAMMABLE DPM
AC Volt Meter (1 ) : Beta 20Φ
AC Ammeter (1 ) : Beta 10Φ


PROGRAMMABLE DPM
Section Contents
1. Introduction
2. Measurement Reading Screens
4. Installation
4.1 EMC Installation Requirements
4.2 Case Dimensions and Panel Cut-out
4.3 Wiring
4.4 Auxiliary Supply
4.5 Fusing
4.6 Earth / Ground Connections
3. Programming
3.1 Password Protection
3.2 Set Up Screens
3.2.1 Potential Transformer Primary value
3.2.2 Potential Transformer Secondary value
3.2.6 Auto Scrolling
3.2.3 Current Transformer Primary value
3.2.4 Current Transformer Secondary value
3.2.5 Reset of min/max values
1 PHASE PROGRAMMABLE DPM
AC Volt Meter (1 ) : Beta 20Φ
AC Ammeter (1 ) : Beta 10Φ
Installation & Operating Instructions
3

Specifications
6.
5. Connection Diagrams
5.1 Connection Diagrams for BETA 20P 96x96 models
5.2 Connection Diagrams for modelsBETA 10P96x96
5.3 Connection Diagrams for modelsBETA 20P48x96
5.4 Connection Diagrams for modelsBETA 10P48x96
Available Models :
1. BETA 20P : 96X96 with
V
KKA
Y B
RR
A
KVK
Y B
RR
V
V
KKA
Y B
RR
14mm Display
2. BETA 10P : 96X96 with
14mm Display
3. BETA 20P : 96X96 with
20mm Display
4. BETA 10P : 96X96 with
20mm Display
A
K
KV
Y B
RR
V
4. BETA 20P : 48 X 96 size 4. BETA 10P : 48 X 96 size
KVKA
Y B
RR
A
KVK
Y B
RR
4

V
V
KKA
Y B
RR
2 1
1. Introduction
The Series is a panel mounted 96 x 96mm and 48X96mm Digital Panel BETA 20P / 10P
Meters for the measurement of AC Voltage and current in single phase systems.
The instrument integrates accurate measurement technology. The measurements are
True RMS upto 15th Harmonic. The parameters are displayed with Ultra high brightness
LED display with 20mm and 14mm Digit height options.
CT Primary, CT secondary.
The front panel has two push buttons for user interface to
scroll through the available parameters the two keys has
function as follow :
2. : Scrolls the parameters in Reverse of above sequence.
V
Programmable DPM can be configured and Programmed
at site for the following : PT Primary, PT Secondary,
1. : Scrolls through parameter in upward sequence.
Display sequence BETA 20P : System voltage, max.
Value, min value and then back to system Voltage.
Display sequence BETA 10P : system Current, max value min value and back to system current.
These DPMs come with 14mm and 20mm Display options, which enables to take readings
from long distance. The unit of display is illuminated form back side with bright LEDs,
which overcomes the problem with conventional LED annunciators that could not be
clearly understood the parameter being displayed from a distance.
TABLE 1: Parameters Displayed with BETA 20P models
Measured Parameters Unit of measurement
System Voltage Volts
System Voltage max. Value (Hi) Volts
System Voltage min. Value (Lo) Volts
5

TABLE 2: Parameters Displayed with modelsBETA 10P
Measured Parameters Unit of measurement
System Current
System Current max. Value (Hi)
System Current min. Value (Lo)
Amp
Amp
Amp
In normal operation the user is presented with the measurement reading screens. These
screens may be scrolled through one at a time in incremental order by pressing the
key and in decrementing order by pressing key.
V
2. Measurement Reading Screens
Screen 1 : System Voltage
A. Display Screens of PGDV Models :
V
V
KKA
Y B
RR
Screen 2 : System Voltage
Value displayed max Value
after “Hi” flashing on Display
V
V
KKA
Y B
RR
Screen 3 : System Voltage
min Value Value displayed after
“Lo” flashing on Display
V
V
KKA
Y B
RR
6

B. Screens of BETA 10P Models :
Screen 1 : System Current
V
A
KVK
Y B
RR
Screen 2 : System Current Max.
Value Value displayed afte “Hi”
V
A
KVK
Y B
RR
flashing on Display
Value Value displayed after “Lo”
Screen 6 : System Current min.
V
A
KVK
Y B
RR
flashing on Display
3. Programming
The following sections comprise step by step procedures for configuring the BETA 10P
and BETA 20P for individual user requirements. To access the set-up screens press and
hold the This will take the User into the Password “ ” and “ ” Keys Simultaneously.
Entry Screen Followed (Section 3.1).by “CodE” on Display
3.1. Password Protection
Password protection can be enabled to prevent unauthorised access to set-up screens.
By default password protection is not enabled. Password protection is enabled by selecting
a four digit number other than 0000. Setting a password of 0000 disables the password
protection.
7

Enter Password, prompt for first digit.
(* Denotes that decimal point will be flashing).
Press the “ ” key to scroll the value of the first digit from 0
to 9, the value will wrap from 9 round to 0.
Press the “ ” key to advance to next digit.
In the case, where the Password is “0000” pressing the
“ ” key when prompted for the first digit will advance to the
“Password Confirmed” screen.
Password Entry :
V
*
KVKA
Y B
RR
Enter Password, first digit entered, prompt for Second digit.
(* Denotes that decimal point will be flashing).
Use the “ ” key to scroll the value of the second digit from
0 through to 9, the value will wrap from 9 round to 0.
Press the “ ” key to advance to next digit.
*
V
KVKA
Y B
RR
*
V
KVKA
Y B
RR
Enter Password, second digit entered, prompt for Third digit.
(* Denotes that decimal point will be flashing).
Use the “ ” key to scroll the value of the third digit from
0 through to 9, the value will wrap from 9 round to 0.
Press the “ ” key to advance to next digit.
8

Enter Password, fourth digit entered, awaiting verification
of the password.
Enter Password, third digit entered, prompt for Fourth digit.
(* Denotes that decimal point will be flashing).
Use the “ ” key to scroll the value of the fourth digit from
0 through to 9, the value will wrap from 9 round to 0.
Press the “ ” key to advance to next digit.
V
*
KVKA
Y B
RR
V
*
KVKA
Y B
RR
V
KVKA
Y B
RR
Password confirmed.
Pressing “ ” key will advance to the “New Password /
change Password” entry stage.
Pressing the “ ” key will advance to the System Type
Selection screen (See section 3.2).
9

Password Incorrect.
This screen indicates that the unit has not accepted the
Pressing the “ ” key will return to the Enter Password
Pressing the “ ” key exits the Password menu and returns
to the Measurement mode.
New / Change Password
(*Decimal point indicates that this will be flashing). Pressing
the “ ” key will scroll the value of the first digit from 0
0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ ” key to advance the operation to
the next digit and sets the first digit.
Password entered.
V
KVKA
Y B
RR
V
*
KVKA
Y B
RR
V
*
KVKA
Y B
RR
stage.
New / Change Password, first digit entered, prompting for
second digit. (*Decimal point indicates that this will be flashing).
Pressing the “ ” key will scroll the value of the Second digit
from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ ” key to advance the operation to the next
digit and sets the second digit,
10

V
*
KVKA
Y B
RR
New / Change Password, third digit entered, prompting for
fourth digit. (* denotes that decimal point will be flashing).
Pressing the ” key will scroll the value of the “ fourth digit
from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ ” key to advance the operation to the “New
Password Confirmation” screen and sets the fourth digit,
New / Change Password, second digit entered, prompting
for third digit. (*decimal point indicates that this will be flashing).
Pressing the “ ” key will scroll the value of the third digit
from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ ” key to advance the operation to the next
digit and sets the third digit,
V
*
KVKA
Y B
RR
V
*
KVKA
Y B
RR
Pressing the “ ” key to advance the operation to the “New
Password Confirmation” screen and sets the fourth digit,
New / Change Password, fourth digit entered, Awaiting for
confirmation
11

New Password confirmation
Pressing the “ ” key will return to the “New/Change
Password”.
Pressing the “ ” key will Set the new Password and
advances to the Set up (see section 3.2).screen.
V
KVKA
Y B
RR
3.2 Set Up Screens
3.2.. Potential Transformer Primary Value (for BETA20P models)1
The nominal full scale voltage which will be displayed as the Line to neutral voltage.
This screen is displayed followed by “PtPr” on display and enables user to display Line to
Neutral Voltages inclusive of any PT .ratio from 60V to 999kV
Pressing the “ ” key accepts the present value and
advances to the “Potential Transformer secondary
value Edit” menu. (See Section 3.2.2)
Pressing the “ ” key will enter the “Potential transformer
Primary Value Multiplier Selection.
V
V
KKA
Y B
RR
Initially the “multiplier must be selected. Pressing the
“ ” Key will move the decimal point position to the right
Side and show # # #. , after which it will again return to
Pressing the “ ” key accepts the present multiplier (Decimal Point position) and advances
#. # # with Annunciation of “K”, which indicates the value in
kV.
to the “Potential Transformer value Edit” menu.
12

Potential Transformer value Edit
Pressing the “ ” key will scroll the value of the most
significant digit (100s) from 0 through to 9.
Pressing the “ ” key accepts the present value at the cursor
position and advances the cursor to the next Less significant digit.
Note : the ashing decimal point indicates the cursor position, a steady decimal point will
be present to identify the scaling of the number until the cursor position coincides with
the steady decimal point position. At this stage the decimal point will be ashing.
When the least significant digit has been set, pressing
the “ ” key will advance to the “Potential transformer
Primary Value Confirmation” screen.
V
*
V
KKA
Y B
RR
Potential Transformer Primary Value Confirmation
This screen will only appear following an edit of the
Potential Transformer Primary Value followed by “ULN”
If the set value is to be corrected, pressing the “ ”
key will return to the “Potential Transformer Primary
Value Edit” stage.
Pressing the “ ” key sets the value and then
advance to the Potential Transformer Secondary Value edit screen (See section 3.2.2.)
on Display.
V
KVKA
Y B
RR
13

3.2.2 Potential Transformer Secondary Value (for BETA 20P models)
This screen will appear following the edit of PT secondary
in above screen.
Pressing the “ ” key set the value and will advance to
Reset of min / max values selection menu. (See section 3.2.5)
PT secondary value Confirmation
Pressing the “ ” key re-enter Potential Transformer
Value edit menu.
This screen is displayed after PT primary value set followed
by “Pt-S” it automatically goes to value edit .
Pressing “ ” key accepts the present value and then
advances to RESET menu (section 3.2.5).
Pressing the “ ” key will enter the PT secondary value edit
mode. * denotes that the decimal point will be flashing.
Secondary value can be set from 60V to 290VL-N.
back to 0, except Most Significant Digit, in which the value
will be scrolled from 0 through 2 and back to 0.
Pressing “ ” will scroll the digit value 0 through 9 and
Pressing the “ ” key will move curser to next Digit. When Value of Least significant
digit is set pressing “ ” Will enter Secondary value confirmation screen.
V
*
KVKA
Y B
RR
V
KVKA
Y B
RR
14

Current Transformer value Edit
Pressing the “ ” key will scroll the value of the most
significant digit (100s) from 0 through to 9.
Pressing the “ ” key accepts the present value at the
cursor position and advances the cursor to the next Least
3.2.3 Current Transformer Primary Value (for BETA 10P models)
The nominal full scale Current which will be displayed Phase current for both system types.
This screen enables user to display Line current inclusive of any CT Ratio 1 upto 999kA.
Pressing the “ ” key accepts the present value and
advances to the “Current Transformer secondary
value Edit” menu. (See Section 3.2.4)
Pressing the “ ” key will shift decimal point position
from 100s to 1s digit. After 1s position it again shifts
Pressing the “ ” key accepts the decimal point position and enters into Current
the position to 100s digit with annunciation of “K”. It
indicates the value in kA.
V
KVKA
Y B
RR
V
*
KVKA
Y B
RR
Transformer Primary value edit.
significant digit.
Note : the ashing decimal point indicates the cursor position, a steady decimal point will
be present to identify the scaling of the number until the cursor position coincides with the
steady decimal point position. At this stage the decimal point will be ashing.
When the least significant digit has been set, pressing the “ ” key will advance to the
“ transformer Current Primary Value Confirmation” screen.
15

Current Transformer Primary Value Confirmation
This screen will only appear following an edit of the Current
Transformer Primary Value.
If the set value is to be corrected, pressing the “ ” key will
Value Edit” stage.return to the “Current Transformer Primary
Pressing the “ ” key sets the value and then advance to
the Current Transformer Secondary Value edit screen
(See section 3.2.4)
V
KVKA
Y B
RR
This screen is displayed after CT primary value set followed
by “Ct-S” on display screen.
Pressing “ ” key accepts the present value and then
advances to reset menu (section 3.2.5).
Pressing the “ ” key will scroll between 1 and 5.
When desired Current transformer secondary value selected
3.2.4 Current Transformer Secondary Value (for BET A 10P models)
This screen will appear following the edit of PT secondary
CT secondary value Confirmation
on display, pressing “ ” will enter to CT secondary value
confirmation screen.
V
KVKA
Y B
RR
V
KVKA
Y B
RR
in above screen.
Pressing the “ ” key set the value and will advance to
Reset (See section 3.2.5)menu
Pressing the “ ” key re-enter Current Transformer Value
edit menu.
16

3.2.5 RESET of min / max Values
This screen is displayed after CT/PT secondary set followed by “RESET” on Display.
Pressing “ ” key enters into Reset menu and scrolls
Pressing “ ” key enters Screen Auto or fixed selection
menu (section 3.2.6)
By selecting the parameters it resets the respective
parameters as follow :
None : No parameter reset
ALL : Both min and max values reset
Hi : max value reset Lo : min value reset
between the parameters as shown in the screens with
pressing the key again.
V
KVKA
Y B
RR
V
KVKA
Y B
RR
V
KVKA
Y B
RR
V
KVKA
Y B
RR
Pressing “ ” key scrolls between the screens.
Pressing “ ” selects the displayed parameter and enters
to Reset parameter confirmation Screen.
17

Pressing “ ” key re-enters reset menu.
Pressing “ ” resets the selected parameter and enters to
Screen Auto scrolling or fixed. Selection menu (section 3.2.6).
Reset parameter confirmation
This Screen will display after PT/CT secondary value
Confirmation followed by “AUtO” Display.
Pressing the “ ” key will enter into Screen selection
Confirmation screen.
Pressing the “ ” key will scroll between “Yes” and “No”.
3.2.6 Selection of Auto Scrolling or fixed Screen
Select “Yes” for Auto scrolling of parameter display and
Select “No” for fixed display screen.
V
KVKA
Y B
RR
V
KVKA
Y B
RR
V
KVKA
Y B
RR
Pressing the “ ” key set the selected option and
Exit set up with entering into measurement mode.
Auto / Fixed Screen Confirmation
Pressing the “ ” key re-enter Screen selection menu.
18

4. Installation
Retention clip for
easy mounting
Panel
Swivel screw
Mounting of BETA 20P/10P is featured with easy “Clip- in” mounting. Push the meter in panel
slot (size 92 x92 mm), it will click fit into panel with the four integral retention clips on two
sides of meter.
If required Additional support is provided with swivel screws (optional) as shown in figure.
As the front of the enclosure conforms to IP50 it is protected from water spray from all
directions, additional protection to the panel may be obtained by the use of an optional
panel gasket. The terminals at the rear of the product should be protected from liquids.
The BETA 20P/10P should be mounted in a reasonably stable ambient temperature and
0
where 0 to 50 C . Vibration should be kept the operating temperature is within the range
to a not be mounted where it will be subjected to minimum and the product should
excessive direct sunlight.
19

Caution
1. In the interest of safety and functionality this product must be installed by
a qualified engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal
connections of this unit. Ensure that all supplies are de-energised before
attempting any connection or disconnection.
3. These products do not have internal fuses therefore external fuses must
be used to ensure safety under fault conditions.
4.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when installed
to a good code of practice for EMC in industrial environments, e.g.
1.
Screened output and low signal input leads or have provision for fitting RF suppression
components, such as ferrite absorbers, line filters etc., in the event that RF fields
cause problems.
Note: It is good practice to install sensitive electronic instruments that are performing
critical functions, in EMC enclosures that protect against electrical interference which could
cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of
interference.
3. To protect the product against permanent damage, surge transients must be limited
to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source.
The unit has been designed to automatically recover in the event of a high level of
transients. In extreme circumstances it may be necessary to temporarily disconnect
the auxiliary supply for a period of greater than 5 seconds to restore correct operation.
4. ESD precautions must be taken at all times when handling this product.
20
This manual suits for next models
1
Table of contents
Other ST Measuring Instrument manuals