Stanley VIP Series User manual

Copyright © 2010
All Rights Reserved
Published in U.S.A.
SCSS-700VS
VIP-Series
Voice Integration Panel
Installation/Operation Manual
G
P/N 53796:GA
Document 53796
03/23/10 Rev:


Installation Procedure
Installation Precautions - Adherence to the following will aid in problem-free installation
with long-term reliability: WARNING - Several different sources of power can be connected
to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit
and associated equipment may be damaged by removing and/or inserting cards, modules, or
interconnecting cables while the unit is energized. Do not attempt to install, service, or operate
this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after
Software Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or change in site-specific
software. Re-acceptance testing is required after any change, addition or deletion of system
components, or after any modification, repair or adjustment to system hardware or wiring. All
components, circuits, system operations, or software functions known to be affected by a
change must be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change, up to a
maximum of 50 devices, must also be tested and proper system operation verified. This
system meets NFPA requirements for operation within the range of 0°C-49°C (32°F-120°F) or
humidity within the range of 10%-93% at 30°C (86°F) noncondensing. However, the useful
life of the system's standby batteries and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it is recommended that this system
and its peripherals be installed in an environment with a normal room temperature of 15-27º
C/60-80º F. Verify that wire sizes are adequate for all initiating and indicating device loops.
Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged
when subjected to lightning induced transients. Although no system is completely immune
from lightning transients and interference, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical Services Department if any problems are
anticipated or encountered. Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage circuits. Remove all electronic
assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible,
make all cable entries from the sides or rear. Before making modifications, verify that they
will not interfere with battery, transformer, or printed circuit board location. Do not tighten
screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in
reduced terminal contact pressure and difficulty with screw terminal removal. Fire alarm
control panels contain static-sensitive components. Always ground yourself with a proper
wrist strap before handling any circuits so that static charges are removed from the body. Use
static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These
instructions must be followed to avoid damage to the control panel and associated equipment.
FACP operation and reliability depend upon proper installation.
While installing a fire alarm system may make lower insurance rates possible, it is not a
substitute for fire insurance! An automatic fire alarm system - typically made up of smoke

detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm
control with remote notification capability - can provide early warning of a developing fire.
Such a system, however, does not assure protection against property damage or loss of life
resulting from a fire. Any fire alarm system may fail for a variety of reasons: Smoke
detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in
walls, or roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire
on another level or floor of a building. A second floor detector, for example, may not sense a
first floor or basement fire. Furthermore, all types of smoke detectors, including ionization
and photoelectric types, have sensing limitations. No type of smoke detector can sense every
kind of fire caused by carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electrical circuits, children
playing with matches, or arson.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and
in rooms used by the system for the connection of alarm transmission wiring,
communications, signaling, and/or power. If detectors are not so located, a developing fire
may damage the alarm system, crippling its ability to report a fire. Audible warning devices
such as bells may not alert people if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building. A fire alarm system will not
operate without any electrical power. If AC power fails, the system will operate from standby
batteries only for a specified time. Rate-of-Rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested
at least once per year by a qualified fire protection specialist. Equipment used in the system
may not be technically compatible with the control. It is essential to use only equipment listed
for service with your control panel. Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service or temporarily disabled. The
most common cause of fire alarm malfunctions, however, is inadequate maintenance. All
devices and system wiring should be tested and maintained by professional fire alarm
installers following written procedures supplied with each device. System inspection and
testing should be scheduled monthly or as required by National and/or local fire codes.
Adequate written records of all inspections should be kept.

1
Content
Section 1
Overview ...................................................................................................................................................... 1-1
1.1 Optional Accessories ................................................................................................................................ 1-1
1.2 Features .................................................................................................................................................... 1-2
1.3 About This Manual .................................................................................................................................. 1-3
1.3.1 Terms Used in this Manual ............................................................................................................... 1-3
Section 2
Agency Listings, Approvals, and Requirements ................................... 2-1
2.1 Federal Communications Commission (FCC) ......................................................................................... 2-1
2.2 Underwriters Laboratories (UL) .............................................................................................................. 2-2
2.2.1 Requirements for All Installations .................................................................................................... 2-2
2.2.2 Requirements for Central Station Fire Alarm Systems .................................................................... 2-2
2.2.3 Requirements for Local Protected Fire Alarm Systems ................................................................... 2-2
2.2.4 Requirements for Remote Station Protected Fire Alarm Systems - Digital Alarm Communicator Trans-
mitter (DACT) .................................................................................................................................. 2-2
Section 3
Installation ................................................................................................................................................. 3-1
3.1 Environmental Specifications .................................................................................................................. 3-1
3.2 Wiring Specifications ............................................................................................................................... 3-1
3.3 SBUS Specifications ................................................................................................................................ 3-3
3.4 Mounting the Cabinet ............................................................................................................................... 3-3
3.4.1 Preventing Water Damage ................................................................................................................ 3-3
3.4.2 Surface Mounting ............................................................................................................................. 3-4
3.4.3 Recessed Mounting ........................................................................................................................... 3-5
3.4.3.1 Cabinet Door and Dead Front Removal ................................................................................. 3-6
3.5 Connecting AC Power and Batteries ....................................................................................................... 3-7
3.6 The VIP-VCM .......................................................................................................................................... 3-8
3.6.1 VIP-VCM Board Layout .................................................................................................................. 3-8
3.6.2 Connecting the VIP-VCM to the SBUS ........................................................................................... 3-9
3.6.3 Installing the Microphone ............................................................................................................... 3-10
3.6.4 To Remove the VIP-VCM .............................................................................................................. 3-11
3.7 Installing the VIP-SW16 Switch Expander ........................................................................................... 3-13
3.8 Installing the VIP-50 .............................................................................................................................. 3-15
3.8.1 VIP-50 Board Layout ...................................................................................................................... 3-15
3.8.2 Mounting the VIP-50 ...................................................................................................................... 3-16
3.8.3 Wiring Specifications ..................................................................................................................... 3-17
3.8.4 Speaker Wiring ............................................................................................................................... 3-18
3.8.4.1 Wiring Lengths .................................................................................................................... 3-18
3.8.4.2 Class B (Style Y) .................................................................................................................. 3-19
3.8.4.3 Class A (Style Z) .................................................................................................................. 3-19

2
3.8.5 VBUS Wiring ................................................................................................................................. 3-20
3.8.6 SBUS Wiring .................................................................................................................................. 3-21
3.8.7 Connecting AC Power .................................................................................................................... 3-22
3.8.8 Backup Battery for VIP-50 ............................................................................................................. 3-24
3.8.9 Calculating Current Draw and Standby Battery .............................................................................3-25
3.9 Installing the VIP-125 ............................................................................................................................ 3-26
3.9.1 VIP-125 Board Layout .................................................................................................................... 3-26
3.9.2 Mounting the VIP-125 .................................................................................................................... 3-27
3.9.3 Wiring Specifications ..................................................................................................................... 3-28
3.9.4 Speaker Wiring ............................................................................................................................... 3-29
3.9.4.1 Wiring Lengths .................................................................................................................... 3-29
3.9.4.2 Class B (Style Y) .................................................................................................................. 3-31
3.9.4.3 Class A (Style Z) .................................................................................................................. 3-32
3.9.5 VBUS Wiring ................................................................................................................................. 3-33
3.9.6 SBUS Wiring .................................................................................................................................. 3-34
3.9.7 Connecting AC Power .................................................................................................................... 3-36
3.9.8 Backup Battery for VIP-125 ........................................................................................................... 3-37
3.9.9 Calculating Current Draw and Standby Battery .............................................................................3-38
3.10 Installing the VIP-CE4 ........................................................................................................................... 3-39
3.11 Installing the SCSS-700RM ................................................................................................................... 3-41
3.11.1 SCSS-700RM Board Layout .......................................................................................................... 3-41
3.11.2 Wiring the SCSS-700RM ............................................................................................................... 3-43
3.11.3 Installing the Microphone ............................................................................................................... 3-45
3.11.4 To Remove the SCSS-700RM ........................................................................................................ 3-46
3.12 Addressing SBUS Devices ..................................................................................................................... 3-48
Section 4
Voice Operation Overview .................................................................................................... 4-1
4.1 Typical Voice Applications ..................................................................................................................... 4-1
4.2 Recording Custom Messages ................................................................................................................... 4-3
4.2.1 Input User Message 3 From the Aux Audio Input ............................................................................4-4
4.2.2 Input Message 3 Using Microphone ................................................................................................. 4-5
4.2.3 Erasing User Message 3 .................................................................................................................... 4-5
4.2.4 Using 7780 Software ........................................................................................................................ 4-5
Manufacturer Warranties and Limitation of Liability

53796 1-1
Section 1
Overview
The Voice Integration Packages are a combination of the addressable fire alarm control panel
and voice integration control all in one package. This manual contains information on how to
install and operate the following Voice Integration Packages:
1.1 Optional Accessories
This manual also contains information on how to install the following compatible accessories
with the VIP series equipment:
*All references to VIP-125 within this manual are applicable to VIP-125HV.
Model Number Consists of These Part Numbers
VIP-Series SCSS-700VS SCSS-700
VIP-VCM (Voice control module)
Model Number Description
VIP-SW16 Adds 16 additional switches to the VIP-VCM or SCSS-700RM to manually select various
voice output groups for emergency announcements from the on-board microphone.
VIP-50 50 watt amplifier with 4 separate audio circuits.
VIP-125/VIP-125HV* 125 watt amplifier with 4 separate audio circuits.
VIP-CE4 Provides four additional audio circuits for each VIP-50.
SCSS-700RM A supervised remote microphone

VIP-Series Voice Integration Package Installation/Operation Manual
1-2 53796
1.2 Features
VIP-Series
• The VIP-VCM has a built-in Digital Message Repeater.
• Single enclosure for system control components.
• SBUS addressable amplifier. The system can support a combination of up to eight
VIP-50s/VIP-125s (50/125 watt amplifiers) for a maximum of 1000 watts per system.
• On-board supervised microphone.
• SCSS-700 system can support up to two SCSS-700RM supervised remote microphones.
• Up to 64 mappable speaker circuits using a combination of VIP-50/VIP-125 and
VIP-CE4s.
• Supports 25 Vrms or 70.7 Vrms speaker circuits using VIP-50s.

Overview
53796 1-3
1.3 About This Manual
This manual is intended to be a complete reference for all installation and operation tasks.
Please let us know if the manual does not meet your needs in any way. We value your
feedback!
1.3.1 Terms Used in this Manual
The following terminology is used with the VIP system:
Term Description
FACP Fire Alarm Control Panel
SLC Signaling Line Circuit
DMR Digital Message Repeater
VBUS The VBUS is an analog voice bus that carries the recorded
voice messages from the VIP-VCM to the VIP-50s/VIP-125s,
or the voice messages generated from a system microphone to
the VIP-50s/VIP-125s.
Module The term module is used for all hardware devices except for
SLC addressable devices and notification appliances.
Input Point An addressable sensing device, such as a smoke or heat detector
or a contact monitor device.
Input Zone A protected area made up of input points.
Output Point
(or Output Circuit) A notification point or circuit for notification appliances. Relay
circuits and auxiliary power circuits are also considered output
points. The output group can be specifically defined as an
output group to be used for voice evacuation circuits.
Audio Circuits Output circuits of the VIP-50, VIP-125 or VIP-CE4.
Group (or “Output Group”) A group of output points. Operating characteristics are common
to all output points in the group.
Output (or “Cadence”) Pattern The pattern that the output will use, for example, Constant,
March Code, ANSI 3.41. Applies to zones and special system
events.
Mapping Mapping is the process of specifying which outputs are
activated when certain events occur in the system.

VIP-Series Voice Integration Package Installation/Operation Manual
1-4 53796
Limitations of Fire Alarm Systems
Manufacturer recommends that smoke and/or heat detectors be located throughout a protected
premise following the recommendations of the current edition of the National Fire Protection
Association Standard 72 (NFPA 72), manufacturer’s recommendations, State and local codes,
and the recommendations contained in Guide for the Proper Use of System Smoke Detectors,
which is made available at no charge to all installing dealers. A study by the Federal
Emergency Management Agency (an agency of the United States government) indicated that
smoke detectors may not go off or give early warning in as many as 35% of all fires. While
fire alarm systems are designed to provide warning against fire, they do not guarantee warning
or protection against fire. A fire alarm system may not provide timely or adequate warning, or
simply may not function, for a variety of reasons. For example:
• Particles of combustion or smoke from a developing fire may not reach the sensing
chambers of smoke detectors because:
Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or
smoke flow.
Smoke particles may become cold,stratify, and not reach the ceiling or upper walls where
detectors are located.
Smoke particles may be blown away from detectors by air outlets
Smoke particles may be drawn into air returns before reaching the detector.
In general, smoke detectors on one level of a structure cannot be expected to sense fires
developing on another level.
• The amount of smoke present may be insufficient to alarm smoke detectors. Smoke
detectors are designed to alarm at various levels of smoke density. If such density levels
are not created by a developing fire at the location of detectors, the detectors will not go
into alarm.
• Smoke detectors, even when working properly, have sensing limitations. Detectors that
have photoelectric sensing chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers
tend to detect fast flaming fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth, neither type of detector is
necessarily best and a given type of detector may not provide adequate warning of a fire.
• Smoke detectors are subject to false alarms and nuisance alarms and may have been
disconnected by users. For example, a smoke detector located in or near a kitchen may go
into nuisance alarm during normal operation of kitchen appliances. In addition, dusty or
steamy environments may cause a smoke detector to falsely alarm. If the location of a
smoke detector causes an abundance of false alarms or nuisance alarms, do not disconnect
the smoke detector; call a professional to analyze the situation and recommend a solution.
• Smoke detectors cannot be expected to provide adequate warning of fires caused by arson,
children playing with matches (especially within bedrooms), smoking in bed, violent
explosions (caused by escaping gas, improper storage of flammable materials, etc.).

Overview
53796 1-5
• Heat detectors do not sense particles of combustion and are designed to alarm only when
heat on their sensors increases at a predetermined rate or reaches a predetermined level.
Heat detectors are designed to protect property, not life.
• Warning devices (including horns, sirens, and bells) may not alert people or wake up
sleepers who are located on the other side of closed or partially open doors. A warning
device that activates on a different floor or level of a dwelling or structure is less likely to
awaken or alert people. Even persons who are awake may not notice the warning if the
alarm is muffled by noise from a stereo, radio, air conditioner or other appliance, or by
passing traffic. Audible warning devices may not alert the hearing-impaired (strobes or
other devices should be provided to warn these people). Any warning device may fail to
alert people with a disability, deep sleepers, people who have recently used alcohol or
drugs, or people on medication or sleeping pills.
Please note that:
i) Strobes can, under certain circumstances, cause seizures in people with conditions
such as epilepsy.
ii) Studies have shown that certain people, even when they hear a fire alarm signal, do not
respond or comprehend the meaning of the signal. It is the property owner’s responsi-
bility to conduct fire drills and other training exercises to make people aware of fire
alarm signals and instruct on the proper reaction to alarm signals.
iii) In rare instances, the sounding of a warning device can cause temporary or permanent
hearing loss.
• Telephone lines needed to transmit alarm signals from a premises to a central station may
be out of service or temporarily out of service. For added protection against telephone line
failure, backup radio transmission systems are recommended.
• System components, though designed to last many years, can fail at any time. As a
precautionary measure, it is recommended that smoke detectors be checked, maintained,
and replaced per manufacturer’s recommendations.
• System components will not work without electrical power. If system batteries are not
serviced or replaced regularly, they may not provide battery backup when AC power fails.
• Environments with high air velocity or that are dusty or dirty require more frequent
maintenance.
In general, fire alarm systems and devices will not work without power and will not function
properly unless they are maintained and tested regularly.
While installing a fire alarm system may make the owner eligible for a lower insurance rate,
an alarm system is not a substitute for insurance. Property owners should continue to act
prudently in protecting the premises and the people in their premises and should properly
insure life and property and buy sufficient amounts of liability insurance to meet their needs.

VIP-Series Voice Integration Package Installation/Operation Manual
1-6 53796
Requirements and recommendations for proper use of fire alarm systems in-
cluding smoke detectors and other fire alarm devices:
Early fire detection is best achieved by the installation and maintenance of fire detection
equipment in all rooms and areas of the house or building in accordance with the requirements
and recommendations of the current edition of the National Fire Protection Association
Standard 72, National Fire Alarm Code (NFPA 72), the manufacturer’s recommendations,
State and local codes and the recommendations contained in Guide for the Proper Use of
System Smoke Detectors, which is made available at no charge to all installing dealers. For
specific requirements, check with the local Authority Having Jurisdiction (ex. Fire Chief) for
fire protection systems.
Requirements and Recommendations include:
• Smoke Detectors shall be installed in sleeping rooms in new construction and it is
recommended that they shall also be installed in sleeping rooms in existing construction.
• It is recommended that more than one smoke detector shall be installed in a hallway if it is
more than 30 feet long.
• It is recommended that there shall never be less then two smoke detectors per apartment or
residence.
• It is recommended that smoke detectors be located in any room where an alarm control is
located, or in any room where alarm control connections to an AC source or phone lines
are made. If detectors are not so located, a fire within the room could prevent the control
from reporting a fire.
• All fire alarm systems require notification devices, including sirens, bells, horns, and/or
strobes. In residential applications, each automatic alarm initiating device when activated
shall cause the operation of an alarm notification device that shall be clearly audible in all
bedrooms over ambient or background noise levels (at least 15dB above noise) with all
intervening doors closed.
• It is recommended that a smoke detector with an integral sounder (smoke alarm) be
located in every bedroom and an additional notification device be located on each level of
a residence.
• To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards. At a
minimum the requirements of Chapter 14 of NFPA 72, 2010 Edition shall be followed. A
maintenance agreement should be arranged through the local manufacturer’s
representative. Maintenance should be performed annually by authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is inadequate
maintenance. As such, the alarm system should be tested weekly to make sure all sensors and
transmitters are working properly.

Overview
53796 1-7
SURVIVABILITY:
Per the National Fire Alarm Code, NFPA 72, all circuits necessary for the operation of the
notification appliances shall be protected until they enter the evacuation signaling zone that
they serve. Any of the following methods shall be considered acceptable as meeting these
requirements:
1) A 2-hour rated cable or cable system
2) A 2-hour rated enclosure
3) Performance alternatives approved by Authority Having Jurisdiction

VIP-Series Voice Integration Package Installation/Operation Manual
1-8 53796

53796 2-1
Section 2
Agency Listings, Approvals, and Requirements
2.1 Federal Communications Commission (FCC)
1. The following information must be provided to the telephone company before the FACP
can be connected to the phone lines:
2. This device may not be directly connected to coin telephone or party line services.
3. This device cannot be adjusted or repaired in the field. In case of trouble with the device,
notify the installing company.
4. If the FACP causes harm to the telephone network, the telephone company will notify the
user in advance that temporary discontinuance of service may be required. If advance
notice is not practical, the telephone company will notify the user as soon as possible.
Users have the right to file complaints, if necessary, with the Federal Communications
Commission.
5. The telephone company may make changes in its facilities, equipment, operations, or pro-
cedures that could affect the operation of the equipment. If this happens, the telephone
company will provide advance notice to allow you to make the necessary modifications to
maintain uninterrupted service.
A Manufacturer: Honeywell International Inc
B Model Number: SCSS-700
C FCC registration number: AC6 USA-34758-AL-E and AC6USA-23901-AL-E
Ringer equivalence: 0.8B
D Type of jack: RJ31X
E Facility Interface Codes: Loop Start: 02LS2
F Service Order Code: 9.0F
Warning
This device has been verified to comply with FCC Rules Part 15. Operation is subject to the following conditions:
(1) This device may not cause radio interference, and (2) This device must accept any interference received,
including interference that may cause undesired operation.

VIP-Series Voice Integration Package Installation/Operation Manual
2-2 53796
2.2 Underwriters Laboratories (UL)
2.2.1 Requirements for All Installations
General requirements are described in this section. When installing an individual device, refer
to the specific section of the manual for additional requirements. The following subsections
list specific requirements for each type of installation (for example, Central Station Fire
Alarm systems, Local Protected Fire Alarm systems, and so on).
1. All field wiring must be installed in accordance with NFPA 70 National Electric Code.
2. Use the addressable smoke detectors specified in FACP installation manual.
3. Use UL listed notification appliances compatible with the FACP from those specified in
the Appendix at the back of this manual.
4. UL installations using Class B wiring for the speaker circuit require the use of a Model
7630 EOL resistor assembly.
5. A full system checkout must be performed any time the panel is programmed.
2.2.2 Requirements for Central Station Fire Alarm
Systems
1. Use both phone lines. Enable phone line monitors for both lines.
2. You must program a phone number and a test time so that the FACP sends an automatic
daily test to the central station.
3. Do not use the ground start option.
4. The AC Loss Hours option must be set from 1-3 hours.
5. The Attempts to Report option must be set for 5.
2.2.3 Requirements for Local Protected Fire Alarm
Systems
At least one UL listed supervised notification appliance must be used.
2.2.4 Requirements for Remote Station Protected Fire
Alarm Systems - Digital Alarm Communicator
Transmitter (DACT)
1. Do not exceed the current load restrictions shown in FACP installation manual.
2. The AC Loss Hours option must be set from 1-3 hours.
The VIP-Series Control is UL listed as a voice evacuation unit for use in NFPA 72 systems. If
the VIP-Series Control and its accessories are to be used as part of a UL installation, carefully
read the UL requirements in this section. For more information on NFPA 72 standards, refer to
the NFPA National Fire Alarm Code.

53796 3-1
Section 3
Installation
This section of the manual is intended to help you plan your tasks to complete the installation.
Please read this section thoroughly, especially if you are installing a VIP-Series control for the
first time.
3.1 Environmental Specifications
It is important to protect the control panel from water. To prevent water damage, the following
conditions should be AVOIDED when installing the units:
• Mount in indoor, dry environments only
• Do not mount directly on exterior walls, especially masonry walls (condensation)
• Do not mount directly on exterior walls below grade (condensation)
• Protect from plumbing leaks
• Protect from splash caused by sprinkler system inspection ports
• Do not mount in areas with humidity-generating equipment (such as dryers, production
machinery)
When selecting a location to mount the control panel, the unit should be mounted where it will
NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity
outside the range of 10%-93% at 30°C (86°F) noncondensing.
3.2 Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with
telephone communication or cause false alarms. To avoid induced noise, follow these
guidelines:
• Isolate input wiring from high current output and power wiring. Do not pull one multi-
conductor cable for the entire panel. Instead, separate the wiring as follows:
• Do not pull wires from different groups through the same conduit. If you must run them
together, do so for as short a distance as possible or use shielded cable. Connect the shield
to earth ground at the panel. You must route high and low voltages separately.
High voltage AC power Terminals
SLC loops
Audio input/output Phone line circuits
Notification circuits
SBUS
Relay circuits

VIP-Series Voice Integration Package Installation/Operation Manual
3-2 53796
• Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit
board where it could induce noise into the sensitive microelectronics or pick up unwanted
RF noise from the high speed circuits. See Figure 3-1 for an example.
High frequency noise, such as that produced by the inductive reactance of a speaker or bell,
can also be reduced by running the wire through ferrite shield beads or by wrapping it around
a ferrite toroid.
Note: All circuits are power limited except the battery and AC cabling. Maintain 1/4 inch spacing between high
and low voltage circuits and between power-limited and non-power limited circuits.
Figure 3-1 Wire Routing Examples
SCSS-700VS

Installation
53796 3-3
3.3 SBUS Specifications
Refer to Section 4 of the FACP’s installation manual for SBUS wiring details.
3.4 Mounting the Cabinet
This section provides instructions on how to install the VIP series cabinet for surface or
recessed mounting. Refer to Section 3.1 when choosing a mounting location.
3.4.1 Preventing Water Damage
Water damage to the fire system can be caused by moisture entering the cabinet through the
conduits. Conduits that are installed to enter the top of the cabinet are most likely to cause
water problems. Installers should take reasonable precautions to prevent water from entering
the cabinet. Water damage is not covered under warranty.
VIP-Series Model Number FACP Installation Manual
SCSS-700VS 53722

VIP-Series Voice Integration Package Installation/Operation Manual
3-4 53796
3.4.2 Surface Mounting
The cabinet can be mounted on the wall surface by using the mounting holes in the back of the
cabinet (see Figure 3-2).
1. Insert two screws level with each other, 14" apart for the top cabinet key shaped holes. See
Figure 3-2.
2. Hang the cabinet onto the two screws. Tighten the screws down.
3. Insert two screws into the two bottom mounting holes and tighten them snug to the
cabinet.
If you need to remove the cabinet door and the dead front panel, see Section 3.4.3.1 for
instructions.
Figure 3-2 Cabinet Mounting Holes
Key Shaped Holes
Bottom Mounting Holes
20"
26-1/2”
This manual suits for next models
1
Table of contents
Other Stanley Security System manuals