SURAN ENDA EHTC7425A User manual

HUMIDITY TEMPERATURE CONTROLLER
EHTC7425A
%RH
°C
HEAT
%RH
Fan
SET
Rotate
L
R
C(on/off)
HSET
TSET
EHTC7425A-E-10052019
1 / 7.
ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER
Thank you for choosing Humidity and Temperature ControllerENDA EHTC7425A
OUTPUT
Sensor Supply 15VDC , Max. 50mA
30.000.000 Switching for no-load operation; 300.000 switching for 10A resistive load at 250VAC.
HOUSING
Housing type Suitable for flush-panel mounting according to DIN 43 700.
Dimensions W72xH72xD97mm
Weight Approx. 350g (after packing)
Enclosure Material Self extinguishing plastics
While cleaning the device, solvents (thinner, gasoline, acid etc.) or corrosive materials must not be used.
±%0,5 (Full scale) Approx. 100kΩ
Approx. 10Ω
INPUTS Input Resistance
Measurement Range Measurement Accuracy
Input Type
0-20mA
4-20mA
1-5V
0-10V
AS
DS
-40.0....125.0 Cº
0....100 %RH
---------------
EHTD-CB-100
TECHNICAL SPECIFICATIONS
Read this document carefully before using this device. The guarantee will be expired by
damaging of the device if you don't attend to the directions in the user manual. Also we don't
accept any compensations for personal injury, material damage or capital disadvantages.
ENVIRONMENTAL CONDITIONS
Height Max. 2000m
80 up to 31Relative humidity for temperatures% °C decreasing linearly 50% at 40°C., to
Ambient/stroge temperature
Max. Relative humidity
0 ... +50°C/-25 ... 70°C (Without icing)
Rated pollution degree According to EN 60529 Front panel : IP6 , Rear5 panel : IP20
Do not use the device in locations subject to corrosive and flammable gases.
Order Code : EHTC7425A - - -
1
2 -
230..........230V AC
SM..........9...30V DC
7...24V AC
Supply Voltage 4 ModBus- Blank......N/A
RS ...... ModBusI ...
Specify at Order .( )
1 -
AS.......Analog Input
DS......Digital Input
Input
Life expectancy for relay
7 x mm sized2 72
Dual 4 digits display
0/4-20mA, 0-10V, 1- 5V analog or digital input (Specify at Order)
Heating or cooling control selection
PID, On-Off Temperature control selection
PID Auto-calculation (SELF TUNE)
Humidification or drying control selection
Internal supply output for sensor
Timer control for fan relay output
2 Relay outputs with time setting for incubation operations
Adjustable buzzer alarm feature for measurement values
CE marked according to European Norms.
2 3
Sensor must be ordered separately.
230V AC ±10%, 50/60Hz or 9...30V DC / 7...24V AC
Supply
Power consumption Max. 7VA
2.5mm² screw-terminal connections
Wiring
EMC
Safety requirements EN 61326-1: 2013
EN 61010-1: 2010 (pollution degree 2, overvoltage category II)
ELECTRICAL CHARACTERISTICS
0~20mA / 0~10V can be selected for analog output sensors. Temperature range for digital output Enda Sensor is -40~125°C
Temperature input range
Humidity input range 0~20mA / 0~10V can be selected for analog output sensors. Humidity range for digital output Enda Sensor is 0~100 RH
When the device is in current measurement mode, the input impedance is 10 . Therefore voltage input should not be connected to the device whileΩ
in current mode. Otherwise the device will deteriorate. If it is necessary to switch from the voltage measurement mode to the current measurement
mode while the device is running, It must be removed and then changed to one of the input type current measurement modes.
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9
english

DIMENSIONS
97mm
2
1
1
75mm
68 mm
Depth
-While pressing both side of the device in
direction and push it in direction1 2
For removing the device from panel :
Flush mounting
clamp
Rubber
1) While panel mounting, additional distance is
required for connection cables.
2) 10mmPanel thickness should be maximum .
3) 90mmIf there is no free space at back side of the
device, it would be difficult to remove it from the panel.
Panel cut-out
INSTALLATION
20
19
Swithc
Cable size: 1,5mm²
Fuse
F 100 mA 250V AC
Neutral
Phase
SUPPLY
NOT :E
Fuse should
be connected.
Holding screw
0.4-0.5Nm. Equipment is protected throughout by
DOUBLE INSULATION
1) IEC 60227 IEC 60245Mains supply cords shall meet the requirements of or .
2) In accordance with the safety regulations, the power supply switch shall
bring the identification of the relevant instrument and it should be easily
accessible by the operator.
Not :e
ENDA EHTC725A is intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding must be grounded on the instrument
side. During an installation, all of then cables that are connected to the device must be free of energy. The device must be protected against inadmissible humidity, vibrations,
severe soiling. Make sure that the operation temperature is not exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded
and twisted cables. These cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a qualified staff and
must be according to the relevant locally applicable regulations.
Panel
SENSOR (Must be ordered separately)
Silicon
cable Brown SDA
Black SCL
Yellow +3.3V
Blue GND
EHTD-CB-100 Digital Output Humidity Temperature Sensor
EHTC7425A
%RH
°C
HEAT
%RH
Fan
SET
Rotate
L
R
C(on/off)
HSET
TSET
HUMIDITY TEMPERATURE CONTROLLER
230 ± %10V AC
50 / 60 Hz Max 7VA
Made in Turkey
1
2
3
4
5
6
HEAT
250V AC 10A
RESISTIVE
LOAD
HUMIDITY
250V AC 10A
RESISTIVE
LOAD
FAN
250V AC 10A
RESISTIVE
LOAD
ROTATE (L)
250V AC 10A
RESISTIVE
LOAD
ROTATE (R)
250V AC 10A
RESISTIVE LOAD
ENDA EHTC7425A-AS- -RS230VAC
INDUSTRIAL ELECTRONICS
HUM.TEMP.CONTROLLER
8 680407 722617
TEMP. INPUT
HUM. INPUT
7
8
9A
B
COM
+
GND
15V DC
SENSOR GND
Made in Turkey
1
2
3
4
5
6
3.3V DC
GND
HEAT
250V AC 10A
RESISTIVE
LOAD
HUMIDITY
250V AC 10A
RESISTIVE
LOAD
FAN
250V AC 10A
RESISTIVE
LOAD
ROTATE (L)
250V AC 10A
RESISTIVE
LOAD
ROTATE (R)
250V AC 10A
RESISTIVE LOAD
ENDA EHTC7425A-DS-230VAC
INDUSTRIAL ELECTRONICS
HUM.TEMP.CONTROLLER
8 680407 722648
SDA
SCL
7
8
9
+
NC
EHTD-CB-100 ( Used with EHTC7425A-DS-XX )
Max 50mA
230 ± %10V AC
50 / 60 Hz Max 7VA
-40.0....125.0 Cº
0....100 %RH
Sensor Measuring Range Device to be used
EHTD-CB-100 EHTC7425A-DS-XX
ESHT-102-XX
ESHT-102-W-XX
ESHT-102-CB-XX
ESHT-102-DC-XX
EHTS-W-UV-XX
EHTS-CB-UV-XX
EHTS-DC-UV-XX
EHTS-W-LV-XX
EHTS-CB-LV-XX
EHTS-DC-LV-XX
EHTC-W-UV-XX
EHTC-CB-UV-XX
EHTC-DC-UV-XX
EHTC-W-LV-XX
EHTC-CB-LV-XX
EHTC-DC-LV-XX
EHTC7425A-AS-XX
-40.0....125.0 Cº
0....100 %RH
-40.0....60.0 Cº
0....100 %RH
-40.0....125.0 Cº
0....100 %RH
230 ± %10V AC
50 / 60 Hz Max 7VA
Not :e
2 7. /
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9 EHTC7425A-E-10052019

EHTC7425A
%RH
°C
HEAT
%RH
Fan
SET
Rotate
L
R
C(on/off)
HSET
TSET
Heater relay is activated
In “Running Mode”, indicates the measured relative humidity value.
In “Programming Mode”, indicates the parameter value or unit.
In “Running Mode”, indicates the measured temperature value.
In “Programming Mode”, indicates the parameter name.
In “Running Mode” , switces off the buzzer.
In “Programming Mode”, increase the value or changes the parameters.
In “Running Mode”, changes the humidity set value.
In “Running Mode”, changes the temperature set value.
In “Programming Mode”, indicates the parameter value.
In “Running Mode” , switches off the control outputs.
In “Programming Mode”, decrease the value or changes the parameters.
FRONT PANEL COMMANDS & USAGE
unl
Locking & Unlocking Keypad
Loc
During "Running Mode", if and keys are pressed together for 2 seconds, message is displayed and the keypad locked. While keypad is locked, ifLoc
and keys are pressed together for 2 seconds, message is displayed and the keypad unlocked and "Running Mode" is entered. While keypad is locked, if one ofunL
the key is pressed, message is displayed. During keypad locked, temperature and humidity set values can be displayed but can not be changed.Loc
Keypad Locked
Keypad Unlocked
Activating / Deactivating Control Outputs
During "Running Mode", if key is pressed for 2 seconds, message displayed and the control outputs become deactivated and device works as an indicator.C.di5
While control outputs deactivated, by pressing key for 2 seconds, message displayed and device continues to control functions.C.EnB
Stopping Buzzer Alam
When an alarm condition occurs, an audible alarm is triggered. By pressing key, buzzer alarm can be turned off.,
Default Settings
r 001.
Powered on device by pressing message appears on display and device reset to default settings.key,
Displaying Revision Number
If keys are pressed together in "Running Mode", revision number appears on display.
d.par
Displaying and Changing Temperature Set Values
Ölçüm
değerleri
t.5Et
100043.0
57.2 57.1
During "Running Mode", if key is preset, temperature setpoint value flashes for 3 seconds. While flashing, by pressing and keys, temperature value can be
changed. If no key is pressed for 3 seconds or if one of the set keys is pressed again, adjusted set value is saved and the "Running Mode" is entered.
100027.4 5.71
t.5Et t.5Et
Ölçüm
değerleri
h.5Et
100043.0
61.1 61.0
During "Running Mode", if key is preset, humidity setpoint value flashes for 3 seconds. While flashing, by pressing and keys, humidity set value can be
changed. If no key is pressed for 3 seconds or if one of the set keys is pressed again, adjusted set value is saved and the "Running Mode" is entered.
100027.4 61.0
h.5Et h.5Et
Measurement
Value
100043.0
100027.4
SET
SET
SET
SET SET
SET
HUMIDITY TEMPERATURE CONTROLLER
ROTATION
RELAY
r.ofF r.on r.ofF r.on r.ofF r.on
ROTATION
RELAY
L
R
(*)
( )r.on ( )r.ofF
Rotation process runs sequentially for left and right directions,
Rotation process runs consecutively as opened until open duration
time and closed until close duration time
ROTATION OUTPUT GRAPHICS
Indicator(s) LEDs illuminates if ;
Humidity relay is activated
Fan relay is activated
Left relay (rotation)is activated
Right relay (rotation)is activated
Displaying and Changing Humidity Set Values
3. / 7
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9 EHTC7425A-E-10052019

if you want operationSelf-tune
first set t.Pid YE5.parameter to
Is the
measured
temperature value,
equal or below to
60% of the
set value?
Yes
No
If the key is pressed for 7 seconds while in user menu, self tune menu is entered. Then key is
pressed, if the conditions are suitable, self tune process starts. This menu can be exited by pressing any key.
&
User Menu
Operating Mode
Self Tune Menu
If key is pressed, self tune
menu exits and "Running Mode"
is entered. PID parameters will
not be changed.
10005.tun
1000t.hi
1000run 10005ucc
PID parameters are
being calculated.
If the measured temperature value is
greater than 60% of the set value,
self tune operation can not be started.
PID parameters are
calculated. Temperature
control has begun.
If key is pressed, self tune
menu exits and "Running Mode"
is entered. Temperature control
will be performed by according
to the new PID parameters.
SELF TUNE OPERATION
5.Err
Sensor Failure. Check the sensor connection. The audible warning is activated. Temperature and humidification outputs are disabled.
Error - Warning - Alarm Definitions
1000t.Alr
Temperature Alarm. Audible warning is activated. Temperature output is disabled.
1000H.Alr
Humidification Alarm. Audible warning is activated. Humidification output is disabled.
10005.tun
Self tune menu has been entered.
1000t.hi
During self tune menu, indicates that the measured temperature value is greater than 60% of the set value.
1000run
Self tune process is running.
10005ucc
Self tune process has been successfully completed.
SET
SET
4. / 7
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9 EHTC7425A-E-10052019

d.Pnt
Hidden Menu
If key is pressed for 7 seconds while in user menu, hidden menu is entered and then the first parameter in
the hidden menu is displayed. All parameters in the PARAMETER LIST on page 5 can be accessed from this
menu. The parameter access and save functions are as in the user menu. If no operation is performed for 7
seconds, or if the keys are pressed together, "Running Mode" is entered.
Programming Mode
User Menu
and . If and
Device has two menus as user and hidden menu. User menu is the frequently used parameters and the hidden menu is where all parameters are found.Menus can be
transferred between parameters. If keys are pressed together for 2 seconds in the hidden menu, the parameter is transferred to the user menu. Up to 10
parameters can be transferred to the user menu in this way keys are pressed together for 2 seconds in the user menu, parameter is removed from user menu.
If and keys are pressed together for 2 seconds, user menu is entered and first parameter in the user menu is displayed. If no operation is performed
for 7 seconds or when keys are pressed together, "Running Mode" is enterd.
PROGRAMMING THE DEVICE
SET
Temperature set value Upper Limit
Temperature hysteresis
Temperature ofsset value
Temperature unit
Decimal point display
Buzzer ( :Buzzer not active. Buzzer active)no YE5:
Temperature control. :Output is active when the temperature is below set value (cooling control),Lo
Hi : The output is active when the temperature is above the set value (heating control).
Temperature output delay time after power-up
Humidity hysteresis
Humidity ofsset value
Humidification control. :Output is active when the humidity is below set value (cooling control),Lo
Hi : The output is active when the humidification is above the set value (heating control).
Humidification output delay time after power-up
Temperature, Humidity output type
( :0~20mA, 4~20mA, :0~10V, :1~5V)0-20 4-20 0-10 1-5:
Temperature set value Lower Limit
Humidity set value Lower Limit
Humidity set value Upper Limit.
Fan Control ( : Fan not active, : Fan active)no YE5
Temperature, Humidity input type ( :0~20mA, 4~20mA, :0~10V, :1~5V)0-20 4-20 0-10 1-5:
Slave device address selection.
Communication speed
(baud rate) selection
PID temperature control selection ( :On-Off control PID control)no YE5:
Proportional band for PID control.
Integral time for PID control
Derivation time for PID control.
Periodic time for PID control
5nD
t.INP
t.UpL
t.loL
t.HY5
t.oFF
t.cnt
t.Pon
t.PID
t.pb
t.tI
t.td
t.PcP
h.INP
h.UpL
h.LoL
h.HY5
h.oFF
h.cnt
h.Pon
f.Cnt
**
**
**
**
**
Unit
Adr5
bAud
Note: When the menu is opened, the parameters of the menu also appear.
**The marked parameters are valid only for the humidity temperature sensor model with analogue input.
SET
5. / 7
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9 EHTC7425A-E-10052019

F.on
F.oFF
r.Cnt
r.on
r.oFF
A.Pon
A.ttP
A.tHI
A.tLo
A.tH5
A.htP
A.hHI
A.hLo
A.hH5
Fan ON time duration.
Rotating ON time duration
Rotating Control ( :no , :Ye5 )Rotating not active Rotating active
Fan OFF time duration.
Rotating OFF time duration.
Temperature upper level alarm (If is changed, this parameter must be re-programmed)AttP .
Temperature lower level alarm (If is changed, this parameter must be re-programmed)AttP
Temperature alarm hysteresis
Temperature alarm configuration (AB5 : Absolute alarm, rEF : Relative alarm)
A.b5: Alarm values are A.tLo and A.tHi
rEF: Alarm values are A.tlo = and =t.5Et-A.tlo A.tHi t.5Et+A.tHi
Alarm message display delay time after power up
Humidity upper level alarm. (If A.htP is changed, this parameter must be re-programmed)
Humidity lower level alarm.(If A.htP is changed, this parameter must be re-programmed)
Humidity alarm hysteresis.
Humidity alarm configuration (AB5 : Absolute alarm, rEF : Relative alarm)
A.b5 A.hLo A.hHi:Alarm values are and
rEF A.hlo t.5Et-A.hlo A.hHi:Alarm values are = and = h.5Et+A.hHi
6. / 7
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9 EHTC7425A-E-10052019

°C / °F
CONFIGURATION PARAMETERS
t.upl 60
Default
Temperature set value Upper Limit
t.Lol -40
t.Hy5 2
Temperature hysteresis
t.oFF 0
Temperature ofsset value
Unit Type
125
Maximum
t.upl
20
20
t.Lol
Minimum
-40
1
-20
°C / °F
°C / °F
°C / °F
Unit C
Temperature unit OFF= ,ON=°C °F
d.pnt no
Decimal indication OFF= ON=no YE5,
f
YE5
C
no
TEMPERATURE CONTROL PARAMETERS
5nd noYE5no
Buzzer OFF= ON=no YE5,
t.cnt Hi
Temperature control. :Output is active when the temperature is below set value (cooling control),Lo
Hi : The output is active when the temperature is above the set value (heating control). HiLO
: dk:sn :99 00 001
00 00:
Temperature output delay time after power-up
t.Pon
%RH
h.upl 100
h.Lol 0
h.Hy5 2
Humidity hysteresis
h.oFF 0
Humidity ofsset value
100
h.upl
20
20
h.Lol
0
1
-20
HUMIDIFICATION CONTROL PARAMETERS
h.cnt Hi
Humidification control. :Output is active when the humidity is below set value (cooling control),Lo
Hi : The output is active when the humidification is above the set value (heating control). HiLO
: dk:sn :99 00 001
00 00:
Humidification output delay time after power-up
h.Pon
%RH
%RH
%RH
t.inp 0-201-50-20
Temperature, input type ( :0~20mA, 4~20mA, :0~10V, :1~5V)0-20 4-20 0-10 1-5:mA / V
Temperature set value Lower Limit
Humidity set value Lower Limit
Humidity set value Upper Limit
F.on
F.oFF
FAN CONTROLPARAMETERS
Fan ON time duration. : sa:dk :99 00 001
00 00:
: sa:dk :99 00 001
00 00:
F.Cnt Fan Control ( : Fan not active, : Fan active)no YE5 YE5nO YE5
r.on
r.oFF
RIGHT - LEFT Rotating CONTROLPARAMETERS
Rotating ON time duration. : dk:sn :99 00 001
00 00:
: sa:dk :99 00 001
00 00:
r.Cnt Rotating Control ( : Rotating not active, : Rotating active)no Ye5 YE5nO YE5
Fan OFF time duration.
Rotating OFF time duration..
PARAMETER LIST
h.inp 0-201-50-20
Humidity input type ( :0~20mA, 4~20mA, :0~10V, :1~5V)0-20 4-20 0-10 1-5:mA / V
A.tlo
A.tHi
A.tH5
A.ttp
A.tLo 125 125
Ab5 rEF Ab5
A.Pon
Temperature upper level alarm (If is changed, this parameter must be re-programmed).AttP
Temperature lower level alarm (If AttP is changed, this parameter must be re-programmed)
Temperature alarm hysteresis
Temperature alarm configuration (AB5 : Absolute alarm, rEF : Relative alarm)
A.b5: Alarm values are A.tLo and A.tHi
rEF: Alarm values are A.tlo = and =t.5Et-A.tlo A.tHi t.5Et+A.tHi
Alarm message display delay time after power up
ALARM PARAMETERS
-40A.tHi-40 °C / °F
°C / °F
2201 °C / °F
: dk:sn99 00 1:00
00 00:
A.hlo
A.hHi
A.hH5
A.htp
A.hLo 100 100
Ab5 rEF Ab5
Humidity upper level alarm. (If A.htP is changed, this parameter must be re-programmed)
Humidity lower level alarm.(If is changed, this parameter must be re-programmed)A.htP
Humidity alarm hysteresis.
Humidity alarm configuration (AB5 : Absolute alarm, rEF : Relative alarm)
A.b5 A.hLo A.hHi:Alarm values are and
rEF A.hlo t.5Et-A.hlo A.hHi:Alarm values are = and = h.5Et+A.hHi
0A.hHi0
2201
%RH
%RH
%RH
19.20 Bps 9600
1247 1
OFF
Slave device address selection
Communication speed (baud rate) selection
baud
Adr5
MODBUS COMMUNICATION PARAMETERS
00 00:: dk:sn :99 00 1 56
t.Pid PID temperature control selection ( :On-Off control PID control)no YE5:noYE5no
%100 14
0
Proportional band for PID control
t.pb
Integral time for PID control
t.ti
Derivation time for PID control.
t.td 00 00:: dk:sn99 00 0:35
Periodic time for PID control
t.Pcp 00 00:: dk:sn02 00 0:20
7. / 7
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
/ D-72160 Horb a.NDettinger Str. 9 EHTC7425A-E-10052019

Discrate Inputs
Addresses
Decimal Hex
Data
Type Data Content Parameter
Name Read /Write
Permisson
1.4 DISCRATE INPUTS
0000d 0x0000 bit -- R
Temperature relay output status (0=OFF; 1=ON)
R
0001d 0x0001 bit Humidification relay output status (0=OFF; 1=ON) --
1.3 COILS
Coil
Addresses Data Content Parameter
Name Read /Write
Permisson
Data
Type
Decimal Hex
00d 0x00 bit Unit
D.PNt
Temperature control OFF = ON = Relative alarmlo Hi,t.cnt
h.cnt
5nd
01d 0x01 bit
02d 0x02 bit
03d 0x03 bit
04d 0x04 bit
Fan Control ( : Fan not active, : Fan active)no YE5 F.cnt
r.cnt
05d 0x05 bit
06d 0x06 bit
Humidity control OFF = ON = Relative alarmlo Hi,
Humidity alarm configuration OFF = ON = Relative alarmAb5 rEF,
Temperature alarm configuration OFF = Ab5, ON = Relative alarm rEF a.ttp
a.htp
07d 0x07 bit
08d 0x08 bit
Rotating Control ( : Rotating not active, : Rotating active)no YE5
R
0002d 0x0002 bit Fan (0=OFF; 1=ON)relay output status --
R
0003d 0x0003 bit Right relay output statusRotating (0=OFF; 1=ON) --
R
0004d 0x0004 bit Left (0=OFF; 1=ON)Rotating relay output status --
ENDA EHTC7425A HUMIDITY AND TEMPERATURE CONTROLLER MODBUS ADDRESS MAP
A.tH5
h H 5. y
h off.
a.hHi
a.hlo
a.hH5
t.pon
h.pon
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
t.off
h.lol
0001d 0x0001 word
Alarm message display delay time after power-up
t.uPL
A.tHi
t.LoL
A.tlo
h.upl
a.pon
R / W
1.1 HOLDING REGISTERS
Input Register
Addresses
Decimal Hex
Data
Type Data Content Parameter
Name Read /Write
Permisson
1.2 INPUT REGISTERS
0000d 0x0000 word Measured temperature value (°C / °F) -- R
0001d 0x0001 word Measured humidity value (%RH) -- R
* Holding and Input Register parameters of type integer, those “signed integer” is defined as the decimal port of and associated with these
parameters. (So,”14.0” is a parameter value of “140” will be read in). Relevant parameters for a period of “mm:ss” type ones in seconds,
”hh:mm” while those species defined in minutes.
t.HY5
Temperature output delay time after power-up
0002d 0x0002 word
0003d 0x0003 word
0004d 0x0004 word
0005d 0x0005 word
0006d 0x0006 word
0007d 0x0007 word
0008d 0x0008 word
0009d 0x0009 word
0010d 0x000A word
0012d 0x000C word
0013d 0x000D word
0014d 0x000E word
0015d 0x000F word
0016d 0x0010 word
0018d 0x0012 word
0019d 0x0013 word
0020d 0x0014 word
0011d 0x000B word
Humidity output delay time after power-up
t.5Et
h.5Et
0000d 0x0000 word
Temperature input type (0: , 1: , 2: , 3: )0-20 4-20 0-10 1-5
R / W
t.inp
h.inp
0017d 0x0011 word
Humidity input type (0: , 1: , 2: , 3: )0-20 4-20 0-10 1-5
R / W
F.on
0021d 0x0015 word
F.oFF
0022d 0x0016 word
r.on
0025d 0x0019 word
r.oFF
0026d 0x001A word
0023d 0x0017 word Integral time for PID control t.ti
0024d 0x0018 word Derivation time for PID control. t.td
0027d 0x001B word Proportional band for PID control t.pb
PID temperature control selection OFF = ON =yE5 no,
t.pid
09d 0x09 bit
1 1/
0028d 0x001C word Periodic time for PID control t.pcp
Holding Register
Addresses
Decimal Hex
Data
Type Data Content Parameter
Name
Read / Write
Permission
Temperature set value
Temperature set value Upper Limit
Temperature upper level alarm
Temperature lower level alarm
Humidity set value Lower Limit
Humidity set value Upper Limit
Temperature hysteresis
Temperature set value Lower Limit
Temperature ofsset value
Humidity set value
Humidity hysteresis
Humidity ofsset value
Temperature alarm hysteresis
Humidity upper level alarm
Humidity lower level alarm
Humidity alarm hysteresis
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
Fan ON time duration.
Fan OFF time duration.
Rotating ON time duration.
Rotating OFF time duration..
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
Temperature unit OFF= ,ON=°C °F
Decimal indication OFF= ON=no YE5,
Buzzer OFF= ON=no YE5,
Table of contents
Other SURAN Controllers manuals
Popular Controllers manuals by other brands

Intech Instruments Ltd
Intech Instruments Ltd ezeio-STD Supplementary manual

Elmo
Elmo VILLEGGIO NG-TRX Series user manual

WindowMaster
WindowMaster WMI 101 installation instructions

Super-Pro
Super-Pro VAPOR-B1 manual

Timeguard
Timeguard PDWM1500 Installation & operating instructions

digitalview
digitalview SVX-4096-VW instructions