Swegon GOLD CX Instruction Manual

OPERATION& MAINTENANCE INSTRUCTIONS
GOLD CX
Generation F

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
2 www.swegon.com
Contents
1. Safety Instructions .................................................3
1.1 Safety Isolating Switch/Main Switch...............................................3
1.2 Risks ............................................................................................3
1.3 Safety Guards ...............................................................................3
1.4 Glycol ...........................................................................................3
2. General ...................................................................4
2.1 Handling the air handling unit before commissioning.....................4
2.2 Range of Application.....................................................................4
2.3 Mechanical Design........................................................................4
2.4 Control System .............................................................................4
2.5 Environmental Documentation......................................................4
2.6 The Components of the Air Handling Units....................................5
2.7 Basic circuit diagram, pipework package........................................6
3. Commissioning.......................................................6
3.1 General.........................................................................................6
3.2 Adjusting the Duct System and air diffusers ...................................7
3.2.1 Adjustment Sequence ............................................................................ 7
3.2.2 Commissioning procedure...................................................................... 7
4. Maintenance...........................................................8
4.1 Filter change .................................................................................8
4.1.1 Dismantling the filters ............................................................................ 8
4.1.2 Installing new filters ............................................................................... 8
4.2 Cleaning and Inspection................................................................9
4.2.1 General.................................................................................................. 9
4.2.2 Filter spaces ........................................................................................... 9
4.2.3 Heat exchangers .................................................................................... 9
4.2.4 Fans and fan spaces ............................................................................... 9
4.3 Service and Functionality Check...................................................10
4.4 Warranty.....................................................................................10
5. Alarms and Troubleshooting............................... 10
5.1 General.......................................................................................10
5.1.1 A and B Alarms .................................................................................... 10
5.1.2 To Reset Alarms.................................................................................... 10
5.1.3 To Change Alarm Priority...................................................................... 10
6. Technical data....................................................... 11
6.1 Dimensions .................................................................................11
6.2 Connection to Wiring Terminals ..................................................13
6.3 Electrical Data .............................................................................14
6.3.1 Air Handling Units................................................................................ 14
6.3.2 Fans..................................................................................................... 15
6.3.3 Electrical Equipment Cubicle................................................................. 16
6.3.4 Control Inaccuracy: .............................................................................. 17
6.3.5 EMC .................................................................................................... 17
6.4 Volume of Glycol/Water in Coil Heat Exchangers..........................17
7. Appendices ...........................................................17
7.1 Declaration of Conformity...........................................................17
7.2 Building Materials Declaration .....................................................17
7.3 License........................................................................................17
7.4 Ecodesign data............................................................................18
The document was originally written in Swedish.

GB.GOLDSKFCX.231015
We reserve the right to alter specifications. www.swegon.com 3
1.3 Safety Guards
The lock on the electric equipment cubicle functions as a safety
guard.
Only a qualified electrician or trained service technicians shall be
allowed to remove the safety guards.
Warning
The power supply to the unit shall be isolated by switch-
ing off the safety isolating switch before removing the
safety guard.
When the air handling unit is operating, the safety guards
must always be mounted, all inspection doors must be
closed, and the junction hood on the top of the unit must
be mounted.
1.4 Glycol
Warning
Never pour glycol down a drain; collect it in a recepta-
cle and leave it at a recycling centre, petrol station, etc.
Glycol is highly dangerous to consume and can cause
fatal poisoning or damage the kidneys. Contact a doctor!
Avoid breathing glycol vapour in confined spaces. If you
get glycol in your eyes, flush them thoroughly with water
(for about 5 minutes). If glycol splashes on your skin,
wash with soap and water.
1. Safety Instructions
All staff concerned must acquaint themselves with these instruc-
tions before beginning any work on the unit. Any damages to
the unit or parts of it due to improper handling or misuse by the
purchaser or the fitter cannot be considered subject to guarantee
if these instructions have not been followed correctly.
Warning
Only a qualified electrician or service personnel trained
by Swegon shall be permitted to carry out any work on
the electrical system or wire external functions in the air
handling unit.
1.1 Safety Isolating Switch/
Main Switch
On 035/080 size units, the safety isolating switch is located on
the right-hand side of the electric cabinet in the centre section of
the unit.
The air handling unit should normally be started and stopped
from the hand-held terminal; not by switching the safety isolat-
ing switch on and off.
Always switch off the safety isolating switch before servicing the
unit if not otherwise specified in the pertinent instructions.
1.2 Risks
Warning
Before carrying out any work, make sure that the power
supply to the air handling unit has been switched off.
Risk areas with moving parts
Moving parts are fan impellers.
The lockable inspection panels serve as a safety guard for the
fans. If the ducts are not firmly connected to the fan outlets,
the outlets must be firmly fitted with a safety guard (wire mesh
screen).
Warning
The inspection doors on the filter/fan sections must not
be opened while the unit is operating.
Stop the unit operating normally via the hand-held micro
terminal.
Wait until the fans have stopped before opening the
door.
There is positive pressure inside the fan section which
could cause the door to fly open.
Keep the key at a safe spot separate from the air han-
dling unit.

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
4 www.swegon.com
2. General
2.1 Handling the air handling
unit before commissioning
The air handling unit and its duct connections should be pro-
tected against wetness and condensation until the unit is com-
missioned.
2.2 Range of Application
The GOLD units are designed for use in comfort ventilation appli-
cations. Depending on the variant selected, GOLD units can be
utilised in buildings such as office buildings, schools, day nurser-
ies, public buildings, shops, residential buildings, etc.
The GOLD CX units can also be used for the ventilation of mod-
erately humid buildings; however not where the humidity is
continuously high, such as in indoor swimming baths.
In order to fully obtain all the benefits the GOLD system has to
offer, it is important to take the special characteristics of the air
handling units into account when planning them into the pro-
ject, installing, commissioning and operating them.
The air handling unit in its basic design should be installed
indoors. The TBTA/TBTB accessory should be used if the air
handling units are installed outdoors. If the duct accessories are
installed outdoors, they must be housed in an insulated casing
(type TCxx).
GOLD CX is designed and tested for temperatures, in the sur-
roundings and the air stream, from -40°C to +40°C. If the air
handling unit is placed outdoors, the expansion vessel must be
equipped with anti-freeze resistance and insulated when the
design outdoor temperature is lower than -10°C.
The fans are approved for continuous operation in temperatures
of up to 40°C.
The fans are tested for, and can manage operation for one hour
at 70°C.
Important!
Always read the safety instructions in Section 1 that
explain the risks involved in running the unit and desig-
nate who shall be permitted to operate and service the
unit, and carefully follow the installation instructions
provided in each paragraph.
The product identification plates are located on the inspection
side of the air handling unit and on a wall inside the fan section.
Refer to the particulars on the product identification plate when
you contact Swegon.
2.3 Mechanical Design
The GOLD CX units are available in 4 physical sizes and for 8
airflow ranges.
The outer sheet steel skin is painted in Swegon’s grey metallic
colour (closest RAL colour: 9007). The handles and decor strips
are black. Internal material: aluminium-zinc plated sheet steel
and Magnelis. Environmental Class C4. Panel thickness of 52
mm with intervening insulation consisting of mineral wool.
The GOLD CX units have class ePM10 60% (M5) or ePM1 50%
(F7) supply air and extract air filters made of glass fibre.
The coil heat exchangers in the size 035-080 one-piece GOLD CX
air handling units are supplied completely mounted from the fac-
tory; including mounted pipework package with all the necessary
components. The system is normally filled with liquid, vented,
commissioned and performance-tested prior to delivery, but can
also be ordered in unfilled condition e.g. for housing improve-
ment projects or if the application requires filling with another
mixture instead of 30 % ethylene glycol. A pipe coupling unit
supplied in unmounted condition is available as an accessory for
the size 100/120 units.
The supply air and extract air fans are of GOLD Wing+ type, an
axi-centrifugal fan with backward-curved blades. The fans are
direct-driven and have a motor control system for variable speed
control.
2.4 Control System
The IQlogic control system is microprocessor-based and is inte-
grated into the air handling unit. It controls and regulates the
fans, heat exchanger, temperatures, airflows, Operation times
and a large number of internal and external functions as well as
alarms.
2.5 Environmental
Documentation
For a complete Declaration of Construction Materials, see our
home page at www.swegon.com (applicable to Sweden only).
The air handling unit is designed in such a way that it can be
easily dismantled into its component parts. When the unit has
ended its useful product life, the services of an accredited recy-
cling company should be utilised for disposal.
The recyclable weight of the GOLD is about 94% of its initial
weight.
Swegon AB is associated with the REPA Register, No.
5560778465.
Contact Swegon AB, Phone: +46 (0)512-322 00, if you have
any questions regarding the dismantling instructions or the air
handling unit’s impact on the environment.

GB.GOLDSKFCX.231015
We reserve the right to alter specifications. www.swegon.com 5
2.6 The Components of the Air Handling Units
The individual components are each specified below in a simplified and diagrammatical description.
Left-hand version
fan arrangement 1
Figure 3b
Outdoor air Supply air Extract air Exhaust air
The air handling units can be ordered in the right-hand version as
shown in Fig. 3a or in the left-hand version as shown in Fig. 3b.
The air handling unit according to Fig. 3a shows Fan Arrange-
ment 1. The unit can also be ordered according to Fan Arrange-
ment 2. The fans and filters are then vertically mirror-inverted.
In the left-hand version (Fig. 3b), the components marked with
an asterisk change function and designation (the components
are named according to whether the function is for supply air or
extract air).
The arrangement of the components and their desig-
nations
1 OUTDOOR AIR* (In left-hand version: Extract air)
2 EXHAUST AIR* (In left-hand version: Supply air)
3 Sizes 035-060: None (see item 5)
Sizes 070-120: Pressure sensor, supply air filter*
4 Extract air fan* with motor and motor controller
5 Sizes 035-060: Pressure sensor, extract air fan* and pressure
sensor, supply air filter*
Sizes 070-120: Pressure sensor, extract air fan*
6 Temperature/air density sensor, extract air.
7 Electrical cabinet with control unit
8 Hand-held terminal
9 Extract air filter*
10 Temperature sensor, supply air (to be mounted in supply air
duct)
11 EXTRACT AIR* (In left-hand version: Outdoor air)
12 SUPPLY AIR* (In left-hand version: Exhaust air)
13 Supply air filter*
14 Sensor, outdoor air temperature*
15 Coil heat exchanger with pipework package
16 Valve actuator
17 Circulation pump
18 Valve pipe with filling valve and safety valve
19 Temperature sensor for freeze protection
20 Sizes 035-060: Pressure sensor, supply air fan* and pressure
sensor, extract air filter*
Sizes 070-120: Pressure sensor, supply air fan*
21 Differential pressure sensor
22 Temperature/air density sensor, supply air.
23 Sizes 035-060: None (see item 20)
Sizes 070-120: Pressure sensor, extract air filter*
24 Supply air fan* with motor and motor controller
25 Temperature/relative humidity sensor, extract air*
26 Tappings for measuring pressure drop across the heat ex-
changer.
GOLD CX, sizes 100/120: Pipework package including control box are supplied in unmounted condition for floor or wall mounting
(accessories).
Fig. 3a
Right-hand version,
fan arrangement 1
2
1
43 5 7
8
10
11
12
13
14 15 2320 2524
9
1716 19
26
22
6
2118

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
6 www.swegon.com
3. Commissioning
3.1 General
Commissioning sequence:
1. Check that there are no foreign objects inside the unit, duct
system or functional sections.
2. Turn the safety isolating switch to the ON position (I).
3. Select the appropriate language, if you have not already done
so. See Section 4.7 in the GOLD Function Manual, Installation
4. The air handling unit has a factory setting that makes it ready
to operate. See separate Commissioning Record.
However, in many cases, these settings need to be adjusted to
suit the current installation.
If necessary, enter the fan position setting (inspection side),
see Section 4.10 in the Function Manual, Installation.
Program the time switch, operating mode, temperatures,
airflows and functions according to the procedures in Section
4 in the Function Manual, Installation.
Select whether the airflow unit of measurement shall be l/s,
m3/s, m3/h or cfm.
Fill out the Commissioning Record and save it in the docu-
ment pocket of the air handling unit.
In some cases it might be necessary to adjust the P-band
and the I-time if the heating regulation system is oscillating
or operates sluggishly. This requires entering a special code.
Contact your Swegon representative.
5. Activate, if needed, manual or auto operation (Dashboard) or
lock the speed of the fans (AIRFLOW ADJUSTMENT image).
Adjust the duct system and the air diffusers according to Sec-
tion 3.2.
6. Check and adjust, if required, the pressure balance in the air
handling unit according to Section 3.3.
7. Finish with filter calibration according to Section 3 in the Func-
tion Manual, Installation.
2.7 Basic circuit diagram,
pipework package
1 Temperature sensor
2 Differential pressure sensor
3 Expansion vessel
4 Manometer
5 Filling valve
6 Safety valve
7 Pump
8 Control valve with actuator
1
2
4
7
8
5
6
3

GB.GOLDSKFCX.231015
We reserve the right to alter specifications. www.swegon.com 7
3.2 Adjusting the Duct System
and air diffusers
In order to prevent the fans from consuming more power than
necessary, it is important to keep the pressure drop in the system
at the lowest possible level. It is also important that duct sys-
tems and air diffusers are correctly commissioned to provide the
comfort expected.
When commissioning air diffusers and the duct systems for the
GOLD, it is appropriate to follow the proportionality method.
This means that the ratio between the airflows in branch ducts
remains constant even if you change the airflow in the main
ducts. The same ratio applies to the air diffusers in the installa-
tion.
When commissioning the duct system there is provision for
locking the speed of the fans in the air handling unit to provide
a specific preset flow rate, see Section 4.1.7 in the Function
Manual, Installation.
3.2.1 Adjustment Sequence
The system should be adjusted in the following order:
1. Adjust of the air diffusers in each branch duct.
2. Adjust the branch ducts.
3. Adjust the main ducts.
3.2.2 Commissioning procedure
1. Set all the air diffusers and dampers to the fully open position.
2. Calculate the quotient between the airflow reading and the
design airflow of all the air diffusers, branch ducts and main
ducts. The air diffuser in every branch that has the lowest
quotient should be fully open. Use this air diffuser as an
INDEX AIR DIFFUSER. The same applies to branch dampers
and main dampers.
When you’ve finished commissioning, one air diffuser in every
branch, one branch damper and one main damper should
consequently be fully open.
Example on how to make an adjustment
– Start adjusting duct branch B, since this one has the
highest quotient.
– The last air device, B3, has the lowest quotient and
should be fully open.
Adjust the other air devices, B1 and B2, so that these
will have the same quotientas air device B3 (see item 5
above).
– Now adjust the air devices in branch duct C. Air
device C4 should be fully open; throttle the others to
the same quotient.
– Adjust the air devices in branch duct A. The index air
device here is air device A3, which means that you first
throttle air device A4 (the reference device) to device
A3:s quotient. Then adjust the others to the same
quotient as air device A4.
– Throttle branch damper B to the same quotient as
branch damper A, throttle branch damper C to the
same quotient as branch damper A.
Check that all dampers have the same quotient.
When commissioning has been completed, 3 air
devices and one branch damper should stand fully
open to obtain the lowest possible pressure in the
system.
qp = design airflow (l/s)
qm = flow reading (l/s)
qm
K (Quotient) =
qp
3. Start adjusting the main duct that has the highest quotient
and the branch duct in the main duct that has the highest
quotient. Starting from this point enables you to then "press"
the air in front of you toward the sections of the system that
have the least air.
4. Adjust the last air diffuser on the duct branch so that it will
have the same quotient as the index air diffuser. This air
diffuser becomes the REFERENCE AIR DIFFUSER. The last air
diffuser on the branch is often the one that has the lowest
quotient and this air diffuser should be open. In this case, the
index air diffuser and the reference air diffuser will be one and
the same.
5. Throttle the other air diffusers in the branch to the same quo-
tient as the reference device.
NOTE! The quotient in the reference terminal will change
every time another air diffuser is throttled, so in practice
the quotient for the reference air diffuser can be set slightly
higher. The reference device must be measured in between
each air diffuser throttled.
6. Go to the branch that had the next highest quotient and
adjust the air diffusers there, etc.
NOTE! All branch dampers should be fully open until all air
diffusers have been adjusted.
7. Throttle the branch damper that had the highest quotient to
the same quotient as the branch that had the lowest quo-
tient.
NOTE! Keep in mind that the index damper changes quotient;
proceed as described in item 5.
8. When all branches have been commissioned, throttle the main
dampers in the same manner.
See also Adjustment example below.

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
8 www.swegon.com
4. Maintenance
Warning
Before carrying out any work, make sure that the power
supply to the air handling unit has been switched off.
4.1 Filter change
Filters made of glass fibre should be replaced, and if a pre-filter
made of woven aluminium is fitted, it should be washed, when
the corresponding filter alarm has been activated.
Order new filters from Swegon or your nearest Swegon repre-
sentative. Specify the size of the GOLD unit, whether the replace-
ment concerns one or two directions of airflow and if you are
replacing standard filters and/or possibly a pre-filter.
4.1.1 Dismantling the filters
It is advisable to clean inside the filter space while the filters are
removed.
Standard filters:
Pull out the handles (A) to free the filters from the filter holder.
Withdraw the filters.
Possible pre-filters inside the air handling unit:
Withdraw the filters.
4.1.2 Installing new filters
Standard filters:
Insert the filters into the filter holder At the same time, draw out
the filter bags, if installed, so that they will not become caught,
damaged or folded.
Insert the filters as far as possible into the unit and press them
lightly against the filter frames, so that they fit tightly.
Push in the handles (A) to clamp the filters in position in the filter
holder.
Close the inspection doors.
Finish with filter calibration according to Section 2 in the Func-
tion Manual, Users.
Pre-filters, if installed, in the AHU:
Insert the filters in the filter guide rails as far as possible into the
AHU and press them lightly against the filter frames, so that they
fit tightly.
Finish with filter calibration according to Section 2 in the Func-
tion Manual, Users.
A
A

GB.GOLDSKFCX.231015
We reserve the right to alter specifications. www.swegon.com 9
4.2 Cleaning and Inspection
4.2.1 General
Access for cleaning must be ensured when planning and during
the installation of the air handling unit. This can, for example,
include the set-up of the unit, and pipe and cable routing.
Clean the interior of the air handling unit if needed. Inspection
of the air handling unit should be performed when you change
filters or at least twice a year.
4.2.2 Filter spaces
The most appropriate time to clean the unit is when you change
the filters.
4.2.3 Heat exchangers
Check whether cleaning is necessary at least twice a year. Clean-
ing can be done from the filter space.
Make sure that the coils are purged of air. If a droplet eliminator
is fitted, remove it and flush it clean with water.
Always clean against the regular direction of airflow.
Cleaning must only be done by blowing with compressed air,
vacuum cleaning with a soft nozzle or wet cleaning with water
and/or solvent. Before you begin cleaning, cover adjacent func-
tional sections to protect them.
If cleaning solvent is used, do not use solvent that will corrode
aluminium or copper. Swegon's cleaning agent is recommended.
This cleaning agent is sold by Swegon Service.
While cleaning, check whether venting is necessary, check the
content of glycol in the water and the condition of the coil for
leakage. Also check that the drain is not clogged.
4.2.4 Fans and fan spaces
Inspect and, if needed, clean the fan impellers to remove dirt
deposits.
Check the impeller to make sure that it is not out of balance.
Check the bearings for noise.
Vacuum clean the fan motor or brush its surfaces. It can also be
cleaned by carefully wiping it with a damp cloth and dishwash-
ing detergent.
Clean the fan space, if needed.

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
10 www.swegon.com
5. Alarms and Troubleshoot-
ing
5.1 General
Alarms are displayed by a flashing red LED in the hand-held
terminal.
When the LED flashes, go in under Alarm log in the instrument
panel, see Section 2.2.3 in the Operating Procedures Manual of
the IQnavigator hand-held micro terminal.
Active alarms, pending alarms and alarm history (50 latest) can
be viewed under Alarm log.
For resetting alarms, you can select individual alarms or all the
alarms.
The reset time can also be viewed under History.
A fault can be traced by examining the function or functional
component indicated in the alarm text.
If the fault cannot be immediately remedied:
Consider whether the air handling unit can continue to operate
until the fault has been remedied. Choose to block the alarm
and/or to change it from stop to operation. See Section 4.8.6 in
the Function Manual, Installation.
5.1.1 A and B Alarms
A alarms send an indication to the output for alarm relay A
(IQlogic module+).
B alarms send an indication to the output for alarm relay B
(IQlogic module+).
Alarms can be forwarded with different priority via these relays.
5.1.2 To Reset Alarms
Alarms with manual resetting can be reset from the hand-held
terminal. Select reset in the alarm log.
Alarms that reset themselves automatically will do so as soon as
the fault has been remedied.
Alarms can also be reset via a communication network (not
applicable to frost guard alarm).
5.1.3 To Change Alarm Priority
See Section 4.8.6 in the Function Manual, Installation.
4.4 Warranty
To submit a warranty claim, you must be able to produce a com-
plete documented and signed Service and Functionality Inspec-
tion Report of the product with hits accessories.
A Service and Functionality Inspection Report must be performed
according to the instructions in Sections 4.1, 4.2 and 4.3.
General conditions for warranty liability are given in the delivery
provisions applicable to the supply.
4.3 Service and Functionality
Check
Service and functionality inspections shall be carried out at the
interval specified below.
Item to check Action 6-month-
ly service
12-month-
ly service
Service
Filters To be replaced when the
display screen indicates
a filter alarm. Check
that the filter installa-
tion frame is in working
order and is tight.
x
Fans, heat ex-
changers, duct
accessories
Inspect and clean if
necessary.
x
Internal surfaces Inspect and clean if
necessary.
x
External sur-
faces
Inspect and clean if
necessary.
x
Gaskets, sealing
strips, bearings,
drive belts
Inspect and remedy if
necessary.
x
Sensors, ca-
bling, measur-
ing tubes
Carry out visual inspec-
tion and remedy if
necessary.
x
Functionality
inspection
Safety func-
tions, fire and
frost protection,
etc.
To inspect the function-
ality.
x
Other control
functions
To inspect the function-
ality. Compare the air
handling unit's values
with the commissioning
report. Remedial meas-
ures should be taken
to correct any possible
inconsistencies.
x
Alarm history Review. x

GB.GOLDSKFCX.231015
We reserve the right to alter specifications. www.swegon.com 11
6. Technical data
6.1 Dimensions
* The air handling unit is supplied
without end connection panel if a
duct accessory housed in an insulated
casing will be connected. The AHU
can also be supplied with full face
end connection panel (accessory).
** Width of centre section's casing =
B + 200 mm.
* The air handling unit is supplied
without end connection panel
if a duct accessory housed in an
insulated casing will be con-
nected. The AHU can also be
supplied with full face end con-
nection panel (accessory).
** Width of centre section's
casing = B + 200 mm.
* The air handling unit is sup-
plied without end connection
panel if a duct accessory housed
in an insulated casing will be
connected. The AHU can also be
supplied with full face end con-
nection panel (accessory).
** Width of centre section's
casing = B + 200 mm.
52
45
45
52
200 700
146
B**
CX
Size A B C D E F G H I J K L M N O Weight, kg
035/040 1038,5 1990 1744 900 245 600 1400 2159 479 240 295 2977 - - - 1933-2188
050/060 1038,5 2318 -900 145 800 1600 2288 344 172 359 2977 600 159 2000 2346-2718
070/080 1273,5 2637 -900 162 1000 1800 2640 320 160 418,5 3447 750 118 ,5 2400 3454-3794
GOLD 035/040
GOLD 050/060
146
M
B** 200 741
52
52*
CX
100
NO
207245 45
GOLD 070/080
CX
52*
52
200B**
743
146MN O
121 11501200
76 2485 76
45

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
12 www.swegon.com
GOLD 100/120
52*
M
P
P
NO
N
180200B**
52
77 3186 77
1048 1000 1048122
45
* The air handling unit
is supplied without end
connection panel if a duct
accessory housed in an
insulated casing will be
connected. The AHU can
also be supplied with full
face end connection panel
(accessory).
Size A B D E F G H I J K L M N O P Weight, kg
100 1122 3340 1070 187 1200 2400 3440 520 210 470 3314 800 420 2500 1720 4294-4772
120 1122 3340 1070 187 1200 2400 3440 520 210 470 3314 800 420 2500 1720 4494-4990
** Width of centre sec-
tion’s casing = B + 200 mm.

GB.GOLDSKFCX.231015
We reserve the right to alter specifications. www.swegon.com 13
6.2 Connection to Wiring Terminals
SD
WLAN
CPU 1
CPU 2
1
A2
B3
GND 4
+5
-6
+7
-8
+9
-10
+11
-12
+13
-
SA TempCom 5Com 4Com 3Com 2Com 1
14
+15
-16
+17
-18
+19
-
Heat Cool
20
C21
NO 22
C23
NO 24
C25
NO 26
C27
NO 28
P29
G30
G0 31
G32
G0
24V AC
Sensor 1 Sensor 2 Sensor 4Sensor 3 Com 6 Com 7 Com 8 Com 9 Com 10 Com 11
+
33 -
34 G
35 G0
36 Y
37 U
38 39 40
24V AC In
41 42
18V AC In
45 46
230V AC In
4743 44
230V AC Out
Digital inputs, terminals 4-17, are of extra-low voltage type. Analogue input, terminals 18-19 have an input impedance of 66 kΩ.
230 VAC control voltage is on external terminals 101 (L) and 102 (N).
Wiring
terminal
Function Remarks
1,2,3 Connections for EIA -485 1= Communication connection A/RT+, 2= Communication connection B/RT–, 3= GND/COM.
4,5 External stop Stops the unit by opening the circuit. On delivery, this function is fitted with a jumper. If the connec-
tion is interrupted, the unit will stop.
6,7 External fire/smoke function 1 External fire and smoke function. On delivery, this function is fitted with a jumper. If the connection is
interrupted, the function will trip and initiate an alarm.
8,9 External fire/smoke function 2 External fire and smoke function. On delivery, this function is fitted with a jumper. If the connection is
interrupted, the function will trip and initiate an alarm.
10,11 External alarm 1 External contact function. Optional: Normally open/normally closed.
12,13 External alarm 2 External contact function. Optional: Normally open/normally closed.
14,15 External low speed External contact function. Oversteers the timer from stop to low speed operation.
16,17 External high speed External contact function. Oversteers the timer from stop or low speed to high speed operation.
18,19 Demand control Input for 0-10 V DC. The input signal influences the supply air/extract airflow set point if the unit is
operating in the demand control mode. For connection of sensors, for example CO2, CO and VOC
20,21 Circulation pump, heating circuit Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a heating load.
22,23 Circulation pump, cooling circuit or
cooling on/off, 1-step operation
Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a cooling load.
24,25 Cooling, on/off, 2-step operation Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes on a cooling load.
26,27 In-operation indication Independent contact, max. 5 A/AC1, 2 A/AC3, 250 VAC. Closes when the unit is operating.
28,29,30 Damper control 24 VAC. 28= Controlled 24 VAC (G), 29= 24 VAC (G), 30= 24 VAC (G0).
31,32 Control voltage 1) 24 VAC control voltage. Terminals 31-32 are loaded with a total of 16 VA. Opened by means of the
safety isolating switch.
33,34 Reference voltage Output for constant 10 VDC. Max. permissible load: 8 mA.
35,36,37,38 Control, recirculation damper The recirculation damper can be loaded with max. 2 mA at 10 VDC. 35= 24 V AC (G), 36= 24 V AC (G0),
37= 0-10 V DC control signal, 38= 0-10 VDC feedback signal.
The max permissible common load on terminals 31-32, outputs for Heat/Cool and damper output (terminals 28-30) is max 32 VA (SD) eller 50 VA (RX/PX/CX).
1) GOLD 100/120: If more than 16 VA is required, use wiring terminals 201 (G) and 202 (G0). Terminals 201-202 can be loaded with a total of max, 48 VA.
The max. permissible load on the correspond-
ing connection is 16 VA.
Glass fuse, 3.15A

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
14 www.swegon.com
6.3 Electrical Data
6.3.1 Air Handling Units
Shows the fuse size for different combinations of fan sizes and capacity variants. Fan A or B can be a supply air fan or an extract air fan
or vice versa. It is the combination of fan A and B that determines the fuse size.
The air handling unit’s rating plate shows the combinations of fan sizes and capacity variants.
Electrical connection is 3-phase, 5-wire, 400 V-10/+15%, 50Hz.
GOLD CX, size Fan A, size/capacity variant Fan B, size/capacity variant Fuse protection (A)
035/040
35-1 (4,0 kW) 35-1 (4,0 kW) 20
35-1 (4,0 kW) 35-2 (5,0 kW) 25
35-1 (4,0 kW) 40-1 (6,5 kW) 25
35-1 (4,0 kW) 40-2 (10 kW) 32
35-2 (5,0 kW) 35-2 (5,0 kW) 25
35-2 (5,0 kW) 40-1 (6,5 kW) 25
35-2 (5,0 kW) 40-2 (10 kW) 32
40-1 (6,5 kW) 40-1 (6,5 kW) 32
40-1 (6,5 kW) 40-2 (10 kW) 32
40-2 (10 kW) 40-2 (10 kW) 40
050/060
50-1 (6,5 kW) 50-1 (6,5 kW) 32
50-1 (6,5 kW) 50-2 (10 kW) 40
50-1 (6,5 kW) 60-1 (2 x 4,0 kW) 40
50-1 (6,5 kW) 60-2 (2 x 6,5 kW) 40
50-2 (10 kW) 50-2 (10 kW) 40
50-2 (10 kW) 60-1 (2 x 4,0 kW) 40
50-2 (10 kW) 60-2 (2 x 6,5 kW) 50
60-1 (2 x 4,0 kW) 60-1 (2 x 4,0 kW) 40
60-1 (2 x 4,0 kW) 60-2 (2 x 6,5 kW) 50
60-2 (2 x 6,5 kW) 60-2 (2 x 6,5 kW) 63
070/080
70-1 (2 x 4,0 kW) 70-1 (2 x 4,0 kW) 40
70-1 (2 x 4,0 kW) 70-2 (2 x 6,5 kW) 50
70-1 (2 x 4,0 kW) 80-1 (2 x 6,5 kW) 50
70-1 (2 x 4,0 kW) 80-2 (2 x 10 kW) 63
70-2 (2 x 6,5 kW) 70-2 (2 x 6,5 kW) 63
70-2 (2 x 6,5 kW) 80-1 (2 x 6,5 kW) 63
70-2 (2 x 6,5 kW) 80-2 (2 x 10 kW) 63
80-1 (2 x 6,5 kW) 80-1 (2 x 6,5 kW) 63
80-1 (2 x 6,5 kW) 80-2 (2 x 10 kW) 80
80-2 (2 x 10 kW) 80-2 (2 x 10 kW) 80
100
100-1 (2 x 6,5 kW) 100-1 (2 x 6,5 kW) 50
100-1 (2 x 6,5 kW) 100-2 (2 x 10 kW) 63
100-2 (2 x 10 kW) 100-2 (2 x 10 kW) 80
120
120-1 (3 x 6,5 kW) 120-1 (3 x 6,5 kW) 80
120-1 (3 x 6,5 kW) 120-2 (3 x 10 kW) 100
120-2 (3 x 10 kW) 120-2 (3 x 10 kW) 125

GB.GOLDSKFCX.231015
We reserve the right to alter specifications. www.swegon.com 15
6.3.2 Fans
RATED DATA PER FAN
GOLD 035/040: Motor shaft power: 4.0 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 5.0 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 6.5 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 10 kW,
motor control system: 3 x 400 V, 50 Hz
GOLD 050/060: Motor shaft power: 6.5 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 10 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 2 x 4.0 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 2 x 6.5 kW,
motor control system: 3 x 400 V, 50 Hz
GOLD 070/080: Motor shaft power: 2 x 4.0 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 2 x 6.5 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 2 x 10 kW,
motor control system: 3 x 400 V, 50 Hz
GOLD 100: Motor shaft power: 2 x 6.5 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 2 x 10 kW,
motor control system: 3 x 400 V, 50 Hz
GOLD 120: Motor shaft power: 3 x 6.5 kW,
motor control system: 3 x 400 V, 50 Hz
or Motor shaft power: 3 x 10 kW,
motor control system: 3 x 400 V, 50 Hz
*) The motor controller limits the output power to the value
specified.

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
16 www.swegon.com
6.3.3 Electrical Equipment Cubicle
The fuse protection of the air handling unit must not exceed the value stated in Section 6.3.1.
ws the internal fuse protection and safety isolating switch for different combinations of fan sizes and capacity variants. Fan A or B can
be a supply air fan or an extract air fan or vice versa.
The air handling unit’s rating plate shows the combinations of fan sizes and capacity variants.
GOLD CX,
size
Fan combination Internal fuse protection (A)
Fan A,
size/capacity variant
Fan B,
size/capacity variant Fan A Fan B
Safety isolating
switch (A)
035/040
35-1 35-1 1x13 1x13 40
35-1 35-2 1x13 1x13 40
35-1 40 -1 1x13 1x13 40
35-1 40-2 1x13 1x16 40
35-2 35-2 1x13 1x13 40
35-2 40-1 1x13 1x13 40
35-2 40-2 1x13 1x16 40
40 -1 40 -1 1x13 1x13 40
40 -1 40-2 1x13 1x16 40
40-2 40-2 1x16 1x16 63
050/060
50-1 50-1 1x13 1x13 40
50-1 50-2 1x13 1x16 40
50-1 60-1 1x13 2x13 80
50-1 60-2 1x13 2x13 80
50-2 50-2 1x16 1x16 63
50-2 60-1 1x16 2x13 80
50-2 60-2 1x16 2x13 80
60-1 60-1 2x13 2x13 80
60-1 60-2 2x13 2x13 80
60-2 60-2 2x13 2x13 80
070/080
70-1 70-1 2x13 2x13 80
70-1 70-2 2x13 2x13 80
70-1 80 -1 2x13 2x13 80
70-1 80-2 2x13 2x16 80
70-2 70-2 2x13 2x13 80
70-2 80-1 2x13 2x13 80
70-2 80-2 2x13 2x16 80
80 -1 80 -1 2x13 2x13 80
80 -1 80-2 2x13 2x16 80
80-2 80-2 2x16 2x16 125
100
100-1 100-1 2x13 2x13 160
100-1 100-2 2x13 2x16 160
100-2 100-2 2x16 2x16 160
120
120 -1 120 -1 3x13 3x13 160
120 -1 120 -2 3x13 3x16 160
120 -2 120-2 3x16 3x16 160

GB.GOLDSKFCX.231015
We reserve the right to alter specifications. www.swegon.com 17
FUSES IN THE ELECTRICAL EQUIPMENT CUBICLE
230 V control current
All the sizes/variants:
One 2-pole, 6A automatic circuit breaker
6.3.4 Control Inaccuracy:
Temperature ± 1oC.
Airflow ± 5%.
FUSES IN THE CONTROL UNIT
3.15 AT, incoming 230V. For mounting, see Section 10.5. For
replacement, dismantle the control unit's plastic enclosure.
6.4 Volume of Glycol/Water in
Coil Heat Exchangers
Total volume (incl. factory-mounted pipework package and
piping):
CX, size 035/040 227 litres
CX, size 050/060 285 litres
CX, size 070/080 354 litres
Total volume of the coils (excl. pipework package and piping):
CX, size 100/120 538 litres
Circulation pump
GOLD CX 035/070, GOLD CX 080 capacity variant 1:
1 x 3-pole MCB C13A
GOLD CX 080, capacity variant 2:
1 x motor protection 10-16 A
6.3.5 EMC
The air handling unit with the power supply 3-phase 400 V con-
forms to IEC 61000-3-12 provided that the short-circuit power
Ssc is greater than or equal to the value in the table below for
each size/capacity variant.
It is the duty of the installer or user of the equipment to ensure,
through consultation with the distribution network operator if
necessary, that the equipment is only connected to a supply with
the correct short-circuit power Ssc for each unit.
GOLD CX,
size - capacity variant Short-circuit power Ssc MVA
035-1 2,3
035-2 3,0
040-1 3,6
040-2 6,0
050-1 3,7
050-2 6,1
060-1 4,4
060-2 6,8
070-1 4,6
070-2 7,0
080-1 7,2
080-2 12,0
100-1 6,5
100-2 11,2
120-1 9,8
120-2 16,7
7. Appendices
7.1 Declaration of Conformity
For Declaration of Conformity, see our home page at www.
swegon.com.
7.2 Building Materials
Declaration
For a complete Declaration of Construction Materials, see our
home page at www.swegon.com.
7.3 License
Copyright 2013-2014 Swegon AB
All right reserved.
Parts of this work are subject to GNU General Public License v2.0
and other Free/Libre Open Source Software licenses.
This program is free software: You can redistribute it and/or
modify it under the terms of the GNU General Public License as
published by the Free Software Foundation, either version 3 of
the License, or (at your option) any later version.
This program is distributed in the hope that it will be useful, but
WITHOUT ANY WARRANTY; without even the implied warranty
of MERCHANTABILITY or FITNESS FOR A PARTICULAR PURPOSE.
See the GNU General Public License for more details.
You should have received a copy of the GNU General Public
License along with this program. If not, see <http://www.gnu.
org/licenses/>.
For full licensing conditions and the Free/Libre Open Source
Software components, please visit:
http://ftp.swegon.se/opensource/opensource/

GB.GOLDSKFCX.231015
We reserve the right to alter specifications.
18 www.swegon.com
7.4 Ecodesign data
The air handling unit complies with the directives 2009/125/EC
and 2014/53/EU.
Data for directive 2014/53/EU is available for sizing in the prod-
uct selection software AHU Design.
Data for directive 327/2011/EU according to below.
All documentation is available in digital form and can be downloaded from
www.swegon.com
Air Handling Units, EU regulation 327/2011 data för ErP redovisning
Datum:
mm kW Actual Req 2015 Actual Req 2015 kW m³/s Pa minˉ¹
035 1 1 Aluminium 616 Domel ZKG 4 A Static Yes 1,01 68,7 58,0 72,6 62 4,20 3,06 901 1635
060 1 2 Aluminium 616 Domel ZKG 4 A Static Yes 1,01 68,7 58,0 72,6 62 4,20 3,06 901 1635
070 1 2 Aluminium 616 Domel ZKG 4 A Static Yes 1,01 68,7 58,0 72,6 62 4,20 3,06 901 1635
035 2 1 Aluminium 616 Domel ZKG 5 A Static Yes 1,01 67,7 58,9 70,8 62 5,10 3,23 1028 1740
060 2 2 Aluminium 616 Domel ZKG 6,5 AStatic Yes 1,01 68,2 60,2 70,1 62 6,67 3,58 1220 1900
070 2 2 Aluminium 616 Domel ZKG 6,5 AStatic Yes 1,01 68,2 60,2 70,1 62 6,67 3,58 1220 1900
040 1 1 Aluminium 744 Domel ZKG 6,5 AStatic Yes 1,01 66,4 60,2 68,2 62 6,67 4,65 915 1380
050 1 1 Aluminium 744 Domel ZKG 6,5 AStatic Yes 1,01 66,4 60,2 68,2 62 6,67 4,65 915 1380
080 1 2 Aluminium 744 Domel ZKG 6,5 AStatic Yes 1,01 66,4 60,2 68,2 62 6,67 4,65 915 1380
100 1 2 Aluminium 744 Domel ZKG 6,5 AStatic Yes 1,01 66,4 60,2 68,2 62 6,67 4,65 915 1380
120 1 3 Aluminium 744 Domel ZKG 6,5 AStatic Yes 1,01 66,4 60,2 68,2 62 6,67 4,65 915 1380
040 2 1 Aluminium 744 Domel ZKG 9 A Static Yes 1,01 66,8 61,9 66,9 62 9,71 5,30 1176 1560
050 2 1 Aluminium 744 Domel ZKG 9 A Static Yes 1,01 66,8 61,9 66,9 62 9,71 5,30 1176 1560
080 2 2 Aluminium 744 Domel ZKG 9 A Static Yes 1,01 66,8 61,9 66,9 62 9,71 5,30 1176 1560
100 2 2 Aluminium 744 Domel ZKG 9 A Static Yes 1,01 66,8 61,9 66,9 62 9,71 5,30 1176 1560
120 2 3 Aluminium 744 Domel ZKG 9 A Static Yes 1,01 66,8 61,9 66,9 62 9,71 5,30 1176 1560
Data according to ErP directive in technical documentation and free access webpage
Type Size Motor
option
Number
of
fans
Impeller
type
Impeller
diameter
Air Flow
qv
Pressure
increase pfs Speed n
Motor
manufacture
Motor
power Installation
category
2023-05-03
AHU data
Fan data
GOLD
SILVER C
Version F
CX
Overall efficiency ηe(s) Efficiency grade N Power
input Ped
Efficiency
category
Vaiable
speed
drive
Specific
ratio
Table of contents
Other Swegon Industrial Equipment manuals