Swegon REACT Ma User manual

REACT Ma
Instructions for Use 20201117
Art. 1546067
The document was originally written in Swedish
Symbol key
Symbols on the machine.
This product complies
with applicable EU directives
Symbols in this user manual
Warning/Caution!
Application area
The product is a measurement unit designed for comfort
ventilation indoors. The product is used to measure supply and
extract air flow in ventilation ducts.
The product may not be used for anything other than its
intended use.
General
Read through the entire instructions for use before you
install/use the product and save the instructions for future
reference. It is not permissible to make changes or modify
this product other than those specified in this document.
The packaging contains the following
items:
1 x REACT M
1 x Instructions for use
Protective equipment
Always use appropriate personal protective equipment
for the work in question, in the form of gloves, respira-
tors and protective glasses during handling, installation,
cleaning and service/maintenance.
Electrical safety
Permitted voltage, see “Electrical data”. It is not permissible
to insert foreign objects into the product’s contactor
connections or the electronics's ventilation openings; risk
for short circuiting.
24 V isolation transformer to be connected should comply with
the provisions of IEC 61558-1.
Cable sizing must be carried out for cabling between the product
and the power supply source.
Disconnect the power supply when working on products that
are not required to run in production.
Always follow the local/national rules for who shall be permitted
to carry out this type of electrical installation.
Handling
• Always use appropriate transport and lifting devices when the
product is to be handled to reduce ergonomic loads.
• The product must be handled with care.
• It is not permissible to carry the product by the measuring
tube.
Installation
• Moist, cold and aggressive environments must be avoided.
• Avoid installing the product near a heat source.
• Assemble the product according to applicable industry
regulations.
• Install the product so that it is not accessible by unauthorized
persons, for example above a suspended ceiling.
• Install the product for easy access during service/maintenance.
• Supplement the duct system with a cleaning hatch in the
vicinity of the product to facilitate cleaning.
• If the product is mounted above a fixed ceiling, the inspection
hatch must be located so that the product is accessible for
inspection.
• If the product is mounted so that it is possible to gain access
to the inside of the product, it must be supplemented with
appropriate protection, for example, a ventilation unit.
• If the product is mounted in cold areas, the whole product
must be insulated on the outside against condensation.
• For installation, the accessory FSR is recommended.
• The product can be installed position-independent.
• It is recommended to mount the product so that the
product’s display is visible.
• The product must be laid down prior to installation so that it
cannot fall over.
• Check to make sure that the product does not have any
visible defects.
• Check that the product is properly secured after it has been
installed.
• Use the product’s eyes to secure the cables with cable ties.
• Check that all cables are properly secured in place after
installation.
• Check that the actuator/controller is properly mounted in
place.

REACT M
2Swegon reserves the right to alter specications. 20201117
Installation, torque, dimensions and weights
Figure 4. Dimensions (mm), REACT M circular. The damper can
be installed at an optional angle.
Circular design
Size ØD (mm)
A (mm)
B (mm)
C (mm)
Weight (kg)
Flow range
Tolerance Q*
±5% with at
least ±x l/s
Min. Max=Vnom*)
l/s
m3/h
l/s
m3/h
100 220 50 200 0.8 518 90 324 2
125 220 50 225 0.9 932 147 529 2
160 220 50 260 1.1 16 58 254 914 2
200 220 50 300 1.2 25 90 404 1454 3
250 220 50 350 1.4 40 144 658 2369 5
315 220 50 415 1.7 63 227 1054 3794 8
400 220 50 500 2.1 102 367 1732 6235 13
500 230 50 600 2.5 164 590 2670 9612 20
630 230 50 730 3.0 300 1080 4174 15026 32
*) Vnom at 250 Pa in pressure reading.
*Installed according to the instructions
1.
3*.
4.
Figure 3. Straight duct section requirements, circular ducts,
quantity Ø before the product:
Figures 1-5 require no straight duct section (figure 3*illustrates
the T piece with cleaning hatch).
Figure 6 requires a straight duct section before the product
equivalent to 4 x the diameter of the duct.
2.
5.
6.
80
65
30
210
Ød
C
BB
100
3
6
0
°
Installation – all designs
• The product’s air flow measurement requires a straight duct
section as per the installation figures.
• In unfavourable conditions before or with disruption, the
product’s tolerances cannot be guaranteed.
• Instructions for Use are supplied with the product on delivery,
but can also be downloaded from www.swegon.com.
Installation – circular version
• Installation is position dependent.
• Can be installed horizontally or vertically.
Figure 2. Installation in the duct system. The ducts must be firmly
fixed to the frame of the building on each side of REACT M.
2
10
1
A
1. REACT M
2. FSR Clamp
2
10
A
1. REACT M
2. FSR Clamp
3. Sound attenuator
Figure 1. Requires a straight duct section of 3 x Ø for sound
attenuators with baffle or centre body.

3
20201117 Swegon reserves the right to alter specications.
REACT M
65
B
H
20
20
20
250
65
Figure 7. Dimensions, REACT M rectangular.
Installation – rectangular design
Dimension B in the figure and table below is found in the
table “Rectangular design” to the left.
• Installation is position dependent.
• Can be installed horizontally or vertically.
Straight section before REACT M in rectangular ducts
Type of disruption E (m2=5%) E (m2=10%)
One 90° bend E = 3 x B E = 2 x B
T piece E = 3 x B E = 2 x B
Figure 5. Straight section requirements, rectangular ducts.
Rectangular design
Size WxH (mm)
Weight (kg)
Flow range
Tolerance Q*±5%
with at least ±x l/s
Min Max=Vnom*)
l/s m3/h l/s m3/h
200 x 200 2.5 67 240 527 1897 8
300 x 200 3.0 100 360 790 2845 12
400 x 200 3.4 133 480 1054 3793 17
500 x 200 3.9 167 600 1317 4742 21
600 x 200 4.3 200 720 1581 5690 25
700 x 200 4.8 233 840 1844 6638 29
800 x 200 5.3 267 960 2107 7586 33
1000 x 200 6.2 333 1200 2634 9483 42
300 x 300 3.4 152 548 1204 4334 19
400 x 300 3.8 203 731 1605 5779 25
500 x 300 4.3 254 914 2006 7223 32
600 x 300 4.8 305 1096 2408 8668 38
700 x 300 5.1 355 1279 2809 10113 44
800 x 300 5.7 406 1462 3210 11557 51
1000 x 300 6.6 508 1827 4013 14447 63
400 x 400 4.4 273 983 2158 7769 34
500 x 400 4.9 341 1228 2697 9711 43
600 x 400 5.3 409 1474 3237 11653 51
700 x 400 5.9 478 1720 3776 13595 60
800 x 400 6.4 546 1965 4316 15537 68
1000 x 400 7.3 682 2457 5395 19421 85
1200 x 400 8.3 819 2948 6474 23306 102
1400 x 400 9.2 955 3439 7553 27190 119
1600 x 400 10.2 1092 3931 8632 31074 136
500 x 500 5.3 429 1543 3388 12195 54
600 x 500 5.7 514 1851 4065 14634 64
700 x 500 6.3 600 2160 4743 17073 75
800 x 500 6.7 686 2468 5420 19513 86
1000 x 500 7.7 857 3085 6775 24391 107
1200 x 500 8.7 1028 3702 8130 29269 129
1400 x 500 9.7 1200 4319 9485 34147 150
1600 x 500 10.7 1371 4936 10840 39025 171
600 x 600 6.4 618 2227 4890 17602 77
700 x 600 7.0 722 2598 5704 20536 90
800 x 600 7.4 825 2969 6519 23470 103
1000 x 600 8.5 1031 3711 8149 29337 129
1200 x 600 9.5 1237 4453 9779 35204 155
1400 x 600 10.5 1443 5195 114 0 9 41072 180
1600 x 600 11.6 1649 5937 13039 46939 206
700 x 700 7.4 844 3038 6671 24014 105
800 x 700 7.9 964 3472 7624 27445 121
1000 x 700 8.9 1205 4339 9530 34306 151
1200 x 700 9.9 1446 5207 11435 41168 181
1400 x 700 11.0 1688 6075 13341 48029 211
*) Vnom at 250 Pa in pressure reading.
*Installed according to the instructions
1xB
1xB
Figure 6. Straight duct section requirements, rectangular REACT
M and sound attenuator with baffle. Installation with a straight
duct section applies to both the supply air and the extract air.
Straight duct section before/after REACT M – sound
attenuator with baffle
1. = Rectangular REACT M
2. = Straight duct ≥3xB.
3. = Sound attenuator with baffle.
1
x
B
1
2
3
1. Controller/Actuator always on the side of the rectangular damper.
E = Straight section.
W = Width, duct.
H = Height, duct.
1

REACT M
4Swegon reserves the right to alter specications. 20201117
LN
24 V AC/DC
AB
5 Nm
3 W 5 VA
100s (90°) 95°
250 Pa max. 100 kPa
QX XX / XX
227VM-024-05
5
Nm
3 W 5
V
A
V
V
100s (90°) 95°
250 Pa max. 100 kPa
QX XX
227VM-024-05
XX /
227
0..10 V DC
(2..10 V DC)
U
1 2 4
-+
AB
+U
1 2 4 A B
-
Modbus
-+
BK RD OG PK GY
CA CB
-+
Figure 8. Wiring diagram.
1-2 – Supply voltage 24 V AC/DC
1-4 – Actual value signal (U) 0..10 / ( 2..10 ) V
A-B – Modbus
For further calculations of U see the formulas page 7.
Load on output 4: max. 0.5 mA
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Vmin
• Select new value for Vmin via the edit wheel.
• Vmin should be less than Vmax.
• Vmin is equal to 0/2 V actual value signal.
Connections Handling
Menus
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Flow
• Switch between l/s and m3/h via the edit wheel.
• A “Lit” square on the display indicates the
selected unit.
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Test
• Turn the edit wheel to choose between the
following modes:
oFF – Test mode switched off, the controller regulates
normally
123 – Shows the current software version
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Mode
• Shows the selected actual value signal
• Switch between 0-10 and 2-10 V via the edit
wheel
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Addr
• Used for Modbus. for particulars on how to use
Modbus, see next page.
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Vnom
• Used for factory configuration.
Vnom
Vnom
Flow
Flow
Vmin
Vmin
Vmax
Vmax
T
T
est
est
Mode
Mode
Adr
Adr
I/s
Test
m /h
3
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3
Vmax
• Select new value for Vmax via the edit wheel.
• Vmax should be greater than Vmin.
• Vmax is equal to 10 V actual value signal.
Figure 9. REACT interface.
1 – Select the required function by turning the “Function wheel”.
2 – Set the value or select submenus by turning the “Edit” wheel.
3 – The value flashes twice when a new value is accepted.
Made in Germany
Made in Germany
24
24
V
V
AC/DC 50/60 Hz
AC/DC 50/60 Hz
0...+50°C I
0...+50°C I
P
P
42
42
Edit
Edit
10°
10°
Vnom
Vnom
Flow / Unit
Flow / Unit
Vmin
Vmin
Vmax
Vmax
Test
Test
Mode
Mode
Adr
Adr
Do not
Do not
open
open
I/s
I/s
Test
Test
m /h
m /h
3
3
1
23
VnomVnom FlowFlow
VminVmin
VmaxVmax
TTestest
ModeMode
AdrAdr
I/s
Test
m /h
3

5
20201117 Swegon reserves the right to alter specications.
REACT M
Display number EEPROM value Communication rate Parity Stop bits
1301200 None 2
2311200 Even 1
3321200 Odd 1
4 3 2400 None 2
5 4 2400 Even 1
6 5 2400 Odd 1
7 6 4800 None 2
8 7 4800 Even 1
9 8 4800 Odd 1
10 99600 None 2
11 10 9600 Even 1
12 11 9600 Odd 1
13 12 19200 None 2
14413 19200 Even 1
15 14 19200 Odd 1
16 15 38400 None 2
17 16 38400 Even 1
18 17 38400 Odd 1
19318 1200 None 1
20 19 2400 None 1
21 20 4800 None 1
22 21 9600 None 1
23 22 19200 None 1
24 23 38400 None 1
3Limited data length per reading of max. 8 addresses
4Default setting
How to use Modbus
Modbus tables are available in a separate document (REACT-Modbus-m)
Function Description
Addr
Enables you to set the actuator's Modbus address, by turning the "edit wheel". It
is possible to set the address from 1 till 247. If you turn the value selector to end
stop "+", the display will show a "2". This makes it possible to select the second
level. If you select the second level, this is indicated in the display by a small circle.
The following functions are available at the second level:
Flow Return to previous level
Vmin Not used.
Vmax Not used.
Test Not used.
Mode Shows the angle of the rotation (0…255 digital 0....100%)
Addr. Used for selecting communication settings for Modbus. See table below.
Vnom
Used for setting response delay for the Modbus communication (see separate
documents)

REACT M
6Swegon reserves the right to alter specications. 20201117
Cleaning
Ideally, the product should be cleaned in connection with
the cleaning of the rest of the ventilation system.
Cleaning of electrical components
• If needed, use a dry cloth to clean the components.
• Never use water, detergent and cleaning solvent or a
vacuum cleaner.
External cleaning
• If necessary use tepid water and a well-wrung cloth.
• Never use detergent and cleaning solvent or a vacuum
cleaner.
Internal cleaning
• When cleaning the ventilation system, the product
must be dismantled if there are no cleaning hatches
close to the product.
• Cleaning equipment such as whisks and the like must
not be fed through the product.
• If necessary remove dust and other particles that can
be present in the product.
• Never use detergent and cleaning solvent or a vacuum
cleaner.
Service/maintenance
• The product does not require any maintenance, except
for any cleaning when necessary.
• In connection with a service, mandatory ventilation
inspection or cleaning of the ventilation system, check
that the general condition of the product appears to be
good. Pay particular attention to the suspension, cables
and that they sit firmly in place.
• It is not permissible to open or repair electrical
components.
• If you suspect that the product or a component is
defective, please contact Swegon.
• A defective product or component must be replaced by
an original spare part from Swegon.
Materials and surface treatment
All sheet-metal parts are galvanized sheet steel (Z275).
Disposal
Waste must be handled according to local regulations.
Product warranty
The product warranty or service agreement will not be
valid/will not be extended if: (1) the product is repaired,
modified or changed, unless such repair, modification
or change has been approved by Swegon AB; or (2) the
serial number on the product has been made illegible or
is missing.
Trouble shooting
The product does not communicate over Modbus
• Make sure that the product is energized.
• Check the product's Modbus connection.
• Check the product's communication settings.
• Check that the product has the right and unique
Modbus address.
The product shows the incorrect/no air flow
• Make sure that the product is energized.
• Check that the product’s set size corresponds with the
physical size.
• Make sure that the product is installed according to the
recommended distance to disruptions, see “Installation”.
• Check that there is an air flow.
• Make sure that the product is correctly oriented in
terms of air direction. The air flow must follow the
instructions on the product.
• Check that the measuring tube is mounted correctly,
plus to plus (red), minus to minus (blue).
• Check that the measuring tubes are undamaged and
not creased.
• Check with the help of the k-factor and pressure
difference between the red and blue measuring tubes
that the flow is within the product’s measurement
range.

7
20201117 Swegon reserves the right to alter specications.
REACT M
4,00 V
V DC
U
1 2 4
CA CB
AB
Figure 10. Shows how to connect a voltmeter for checking the
actual value.
Formulas for calculating air flow
The following applies for analogue control.
Control signal 0..10 V DC give the following formulas:
Vact – Vmin
Vmax
U = 10 V DC
Vact – Vmin
Vmax
U = 2 V DC + 8 V DC
• Calculation of the current actual value (U) when you know
the value of the current flow (Vact):
• Calculation of the current actual value (U) when you know
the value of the current flow (Vact):
Key to formulas above:
U = actual value signal in [V] DC
Vact = current air flow in [l/s, m3/h]
Vmin = set min. flow in [l/s, m3/h]
Vmax = set max. flow in [l/s, m3/h]
Performance checks

REACT M
8Swegon reserves the right to alter specications. 20201117
Declaration of Conformity
Swegon AB hereby declares that:
REACT M complies with the essential characteristic demands
and relevant regulations specified in the directives, 2014/35/
EU (LVD), 2014/30/EU (EMC) and 2011/65/EU (RoHS2):
The following standards have been observed:
EN 60730-1:2011 Automatic electrical controls for household
and similar use - Part 1 Generic standards
EN 61000-6-2:2007
Electromagnetic compatibility (EMC). Generic
standards. Immunity for
industrial environments
EN 61000-6-3:2007
Electromagnetic compatibility (EMC). Generic
standards. Emission standard for residential,
commercial and light-industrial environments
Person responsible for this declaration:
Name: Freddie Hansson, R&D Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 200601
This declaration is applicable only if the product has been
installed according to the instructions in this document
and if no modifications or changes have been made on
this product.
References
www.swegon.com
Building Materials Declaration
REACT M Product Data Sheet
REACT Description of functions & Wiring diagram
REACT Modbus
Technical data
IP class: IP42
Corrosivity class: C3
Leakage classes according to SS-EN 1751
- Leakage class, casing: C
Ambient temperature
Operation: 0 – +50 °C
Storage: -20 – +50°C
RH: 10 - 95%
(non-condensing)
CE marking: 2014/35/ EU (LVD)
2014/30 /EU (EMC)
2011/65/EU (RoHS2)
Electrical data
Power supply: 24 V AC/DC ±20% 50 - 60 Hz
Fixed connection cable,
1000 mm with cable size. 3 x 0.75 mm 2
2 x 0.38 mm 2
Power consumption, for transformer rating:
REACT M 0.6 W 1.3 VA
Table of contents
Other Swegon Measuring Instrument manuals