2
DIR
We reserve the right to alter specifications. 20111222 www.swegon.com
Technical description
Design
The DIR is a complete, flat displacement unit for mount-
ing recessed into studded walls. The unit consists of a
two parts: the plenum box and the perforated front plate.
The plenum box is equipped with a air volume measuring
point, or mounting frame and a rectangular connection
spigot. The telescopic mounting frame has a distribution
plate which is equipped with a number of adjustable
deflectors. This plate is removable for access to the duct
system. The perforated front plate is fixed to the mount-
ing frame.
Materials and surface treatment
The displacement unit is manufactured in galvanised sheet
steel and is coated with our pure white standard paint,
RAL 9010. The unit is also available in other standard
colours: Dusty grey 7037, white aluminium RAL 9006,
jet black RAL 9005, grey aluminium RAL 9007 and signal
white RAL 9003 (NCS 0500).
Customisation
In addition to the standard sizes, these displacement units
are available in special dimensions, with reinforced front
panels etc. Please contact your nearest sales representa-
tive for further information.
Accessories
Connection duct:
DIRT 4a. A rectangular connection duct with a circular
duct connection and a rubber seal. The connection duct
is telescopic by 300 mm in height.
Planning
It is possible to modify the affected area by adjusting the
deflectors behind the perforated front plate. This does
not affect the air flow, pressure drop or sound level. This
flexibility simplifies any future changes in the furnishing of
the room etc.
Installation
The plenum box is mounted before the wall board is
fixed. The plenum box is screwed into place through the
sides. The hole for the connection sleeve inlet is cut as
illustrated in the diagram. The wall board is then fixed in
place, the mounting frame pushed inside the displace-
ment unit and fixed using screws. Finally the front panel is
hung in place on the mounting frame. See Figure 1.
Commissioning
The measurement outlet is on the lower edge of the
displacement unit. The k-factor of the unit is stated in
the product label, and can also be found on our website
in the relevant k-factor guide. It is recommended that a
measurement unit and commissioning damper is used to
regulate the air flow. It should be placed before the inlet
of the connection duct. See Figure 2.
Maintenance
The displacement unit can be cleaned when necessary
using luke warm water with added detergen. The duct
system is accessed by removing the perforated front plate
and the distribution plate. See Figure 2.