SYCLOPE electronic TRACE'O How to use

Installation and starting instructions
Reference : CTR 0001 Rev : 2
SYCLOPE TRACE’O®: Universal controller for trace detection (Part 1)

General information Page 2/40
Installation and starting instruction manual SYCLOPE TRACE’O®
Parts of the general documentation
Part 1 : Installation and starting instructions
Part 2 : Programming instructions
Part 3 : Communications instructions
General information :
SYCLOPE Electronique 2016®Manual of 2016, February 18th Rev 2
Universal controller for standard and trace measurement.
Product line TRACE’O®
Part 1 : Installation and starting instructions (Ref. DOC0321)
Editor :
SYCLOPE Electronique S.A.S.
Z.I. Aéropole pyrénées
Rue du Bruscos
64 230 SAUVAGNON - France
Tel : (33) 05 59 33 70 36
Fax : (33) 05 59 33 70 37
Email : syclope@syclope.fr
Internet : http://www.syclope.fr
© 2015 - 2016 by SYCLOPE Electronique S.A.S.
Subject to modifications
►

Summary Page 3/40
Installation and starting instruction manual SYCLOPE TRACE’O®
Summary
I. General informations ......................................................................................................... 4
1) Applicability ...................................................................................................................... 4
2) Use of the document ......................................................................................................... 5
3) Symbols and signs............................................................................................................. 5
4) Storage and transport........................................................................................................ 6
5) Packaging ......................................................................................................................... 6
6) Warranty .......................................................................................................................... 6
II. environment and safety procedures .................................................................................... 7
1) Use of the equipment ........................................................................................................ 7
2) User obligations ................................................................................................................ 7
3) Risk prevention ................................................................................................................. 7
4) Identification and localization of the identification plate ....................................................... 8
5) Disposal and conformity..................................................................................................... 9
III. Technical specifications and functions................................................................................10
1) Features ..........................................................................................................................10
2) Main functions..................................................................................................................11
3) Measurement parameters, scales and control ranges..........................................................12
a) Basic versions : Direct entries (2x 4…20mA) or isolated entries (2x 4…20mA) ......................12
b) Version with 1 isolated potentiometric entry and 1 isolated 4-20mA entry............................13
c) Version with 2 potentiometric entries.................................................................................14
IV. Installation and wiring ......................................................................................................15
1) Installation conditions.......................................................................................................15
2) Installation of the wall-mounted controllers........................................................................15
3) Electrical connections .......................................................................................................15
4) Connection of the primary power supply ............................................................................16
5) Connexion of the free of potential relays (KA, KB, KC et KD) ...............................................17
6) Connection of the measurement inputs..............................................................................17
7) Connections of the analogue outputs (IA1 and IA2.............................................................20
8) Connection of the remote control input (CAD) ....................................................................20
9) Connection of the flow control entry sensor (Flsw) or low level detection tank .....................21
10) Connection of the counter entry (Flow) or low level detection tank......................................22
11) Connection of the RS232C printer output ...........................................................................22
12) Branchements du bus de communication RS485.................................................................22
13) Connections of the MODEM port for communications..........................................................23
14) Connection of GMS, Wifi and Ethernet modems for internet access .....................................24
15) Connection of the internal socket modem ..........................................................................24
V. Expendable external connection box ..................................................................................25
VI. General uses ....................................................................................................................26
1) Using « standard » mode..................................................................................................26
2) Using « trace » mode .......................................................................................................27
VII. Introduction to the human-machine interface (HMI) ...........................................................28
1) Display and control keypad ...............................................................................................28
2) Internal connections .........................................................................................................29
3) Terminal block connections ...............................................................................................29
VIII. Commissioning .................................................................................................................30
1) Choosing the language .....................................................................................................30
2) Setting real-time clock ......................................................................................................31
3) Contrast adjust (Only when « Stopped ») ..........................................................................31
4) Setting display screens .....................................................................................................31
5) Programming setpoints.....................................................................................................33
6) Programming technical alarms ..........................................................................................34
7) Calibration of measurement probes ...................................................................................34
8) Start processes and dosages.............................................................................................35
IX. Guide and maintenance. ...................................................................................................37

General informations Page 4/40
Installation and starting instruction manual SYCLOPE TRACE’O®
I. General informations
1) Applicability
SYCLOPE TRACE’O®controller range you have just purchased is an electronic special equipment for
measuring standard chemistry in trace range. It has been carefully developed and manufactured to
ensure your greatest pleasure and peace of action.
Its remarkable capacity of adaptation to the different situations means it can be installed in the most
difficult environments where processes and measurements of water are decisive.
Designed according to the needs of the customer, the SYCLOPE TRACE’O®controller is equipped with
four analog inputs for specific sensors for treating water and also include alarm functions and
regulations with cyclic commands transmitted by means of 4 configurable relays to control pH chemistry
levels of the water.
When using chlorine or ozone measurement, SYCLOPE TRACE’O®controller is able to measure
automatically some traces of chemistry with a special processing for guarantying the good working of
the respective sensors.
Two ports, RS232 and RS485, for a printer and/or a computer link, allows communication by direct link
or modem to a desktop computer (PC) for filing and graphic processing of the acquisition data.
The SYSCOM®software application has been developed to perform these functions.
TRACOM®software also developed by SYCLOPE Electronique S.A.S. makes it possible to ensure the
maintenance and the programming of the basic functions as well as the functions necessary to the
communications with the Internet.
With an adequate interface carrying out internet connectivity, SYCLOPE TRACE’O®will be connected
in real-time to Internet site “mysyclope.com” thus ensuring a management and a total follow-up of
all the parameters as well as a management of alarms by email or SMS in all circumstances. (Yearly
subscription of access to be envisaged)
The simplicity of operation of the SYCLOPE TRACE’O®, the user friendliness and the remarkable
technical aspects of these controllers, will ensure you benefit from their many options, guaranteeing
you full control and supervision of the quality of the water.
The following instructions contain all the information required for the installation, use and maintenance
of your new equipment.
Installation
Technical specifications
Commissioning instructions
Safety tips
If you would like to receive further information or if you encounter any difficulties not described in this
manual, please contact your usual retailer or else directly contact the sales department of SYCLOPE
Electronique S.A.S., either at the agency or at the office for your region, or the technical/quality
departments of our establishments. We will do everything in our power to help you and ensure you
benefit from our advice and know-how in the field of measurement and treatment of swimming-pool
water.
Contact : service-technique@syclope.fr

General informations Page 5/40
Installation and starting instruction manual SYCLOPE TRACE’O®
2) Use of the document
Please read this entire document before starting to install, adjust or commission your controller device,
in order to ensure the safety of swimmers, users and equipment.
The information provided in this document must be strictly observed. SYCLOPE Electronique S.A.S.
declines all responsibility in cases where failure to comply with the instructions of this documents is
observed.
The following symbols and pictograms will be used to facilitate reading and understanding of these
instructions.
●Information
►Action to be taken
Item of a list or catalogue
3) Symbols and signs
Identification of a continue voltage or current
Identification of an alternative voltage or current
Protective ground
Functional ground
Risk of injury or accident. Identify a warning concerning a potentially dangerous risk.
Documentation must be consulted by the user with each time the symbol is notified. If the
instructions are not respected, that presents a risk of death, physical injuries or property
damages.
Electric hazard. Identify a warning statement relative to a mortal electric danger. If the
instructions are not strictly respected, that implies an inevitable risk of physical injuries or
death.
Risk of incorrect operation or damage for the device.
Comment or particular information.
Recyclable element

General informations Page 6/40
Installation and starting instruction manual SYCLOPE TRACE’O®
4) Storage and transport
It is important to store and transport your SYCLOPE TRACE’O®in its original packaging in
order to minimize risk of damage.
Furthermore, the package must be stored in an environment that is protected against
humidity and exposure to chemical products.
Environmental conditions for transport and storage:
Temperature: -10 °C to 70 °C
Air humidity: Maximum of 90% with no condensation
5) Packaging
The controller is delivered without electrical power cable.
The pre-holes of the box are drilled and equipped with according electrical glands in
compliance with IP65 level protection. Cables must be adapted to the electrical glands to
respect the level of protection.
Grounded cables for connecting pH and ORP (Redox) sensors are not provided.
Content of the packaging :
One analyzer/controller SYCLOPE TRACE’O®
Installation and starting instruction notice
Programming notice
Communication notice (Option)
6) Warranty
The warranty is provided according to the terms of our general conditions of sale and delivery as long
as the following conditions are met:
Use of the equipment according to the instructions of this notice
No modifications of the equipment which may modify its behavior and no incorrect
manipulation
Respect for the electrical safety conditions
Consumable material is no longer covered by the warranty when in use.

Environment and safety procedures Page 7/40
Installation and starting instruction manual SYCLOPE TRACE’O®
II. environment and safety procedures
Please:
Read this manual carefully before unpacking, installing or commissioning this equipment
Take into account all the hazards and recommended precautionary measures
Failure to respect these procedures can result in serious injury to users or damage the device.
1) Use of the equipment
The SYCLOPE TRACE’O®system has been designed to measure and control physico-chemical
parameters by means of sensors and controls of suitable actuators in the context of the possible uses
described in this manual.
All other uses are considered to be non-conforming and must therefore be forbidden.
SYCLOPE Electronique S.A.S. will not be responsible in any case for any damages that result
from such uses.
Any use of sensors or interfaces not-in conformity to the features defined in this handbook
must also be proscribed.
2) User obligations
The user undertakes not to allow its employees to work with the SYCLOPE TRACE’O®equipment
described in this manual unless they:
Are aware of the fundamental instructions relating to work safety and prevention of accidents
Are trained in the use of the device and its environment
Have read and understood these instructions, warnings and manipulation rules
3) Risk prevention
The installation and connection of the SYCLOPE TRACE’O®equipment should only be
performed by personnel specialized and qualified for this task.
The installation must comply with current safety standards and instructions!
Before switching the controller on or manipulating the relay outputs, remember always to
cut off the primary power supply!
Never open the controller when it is powered on!
Maintenance operations and repairs should only be performed by trained, specialized
personnel!
Take care when choosing the location for installing the equipment according to the
environment!
The SYCLOPE TRACE’O®electronic box should not be installed in a hazardous
environment and should be protected against splashing with water or chemical products. It
should be installed in a dry, well-ventilated location, isolated from corrosive vapours.

Environment and safety procedures Page 8/40
Installation and starting instruction manual SYCLOPE TRACE’O®
Make sure that the chemical sensors used with this device correspond well to the chemicals
used. Refer to the individual technical note of each sensor. Chemistry of water is very
complex, in case of doubt, contact immediately our engineering service or your approved
installer/reseller.
Chemical sensors are sensitive elements using consumable parts. They must be supervised,
maintained and calibrated regularly using specific calibrator systems not-provided with this
equipment. In the event of defect, a surplus possible hazard of chemical injections can be
noted. In the doubt, a service contract must be taken near your reseller/installer or failing
this near our engineering services. Contact your approved installer/reseller or our business
service for more information.
4) Identification and localization of the identification plate
Label of the manufacturer Serial number
Model of the product Particular risks Read de manual
Reference of the product Product which can be recycled
Range of the power supply Limitation of dangerous substances
Values of the maimum current EC compliance
Class of the protection Country of the manufacturer
Identification of the manufacturer Manufacturer Square code
Identification plate
8
9
11
12
13
14
15
1
2
3
4
5
6
7
1
2
3
4
5
6
8
11
12
7
14
13
10
15
TRACE’O
Ref:CTR 0001
90 - 240VAC 50/60Hz
www.syclope.fr Made in France
0,3 - 0,16A
IP65
S/N:13044217

Environment and safety procedures Page 9/40
Installation and starting instruction manual SYCLOPE TRACE’O®
5) Disposal and conformity
The recyclable packaging of the SYCLOPE TRACE’O®equipment must be disposed of according to
current regulations.
Elements such as paper, cardboard, plastic or any other recyclable elements must be taken
to a suitable sorting center.
According to European directive 2012/19/UE, this symbol means that as of 2012, July 4th,
electrical appliances cannot be thrown out together with household or industrial waste.
According to current regulations, consumers within the European Union are required, as of
this date, to return their used devices to the manufacturer, who will take care of disposing
them at no extra expense.
According to European directive 2011/65/UE, this symbol means that the SYCLOPE
TRACE’O®controller is designed in compliance with the restrictions on hazardous
substances
According to low-voltage directive (2014/35/UE), the electromagnetic compatibility directive
(2014/30/UE) and the RoHs2 directive (2011/65/UE) this symbol means that the device has
been designed in compliance with the previously cited directives

Technical characteristics Page 10/40
Installation and starting instruction manual SYCLOPE TRACE’O®
III. Technical specifications and functions
1) Features
General characteristics
Type
Specification (s)
Marker(s)
Consumption
0,3 to 0,15A Maxi. (Without external load)
-
Power supply required
Between 90VAC and 240VAC +/-10%
-
Electric protection
Fuse 315 mA Time-lag 5x20 glass
F1
Operating Temp. (°C)
-5 °C to 45 °C
-
Storage temperature (°C)
-10 °C to 70 °C
-
Humidity
Max. 90% without condensation
-
Case material
ABS or Polycarbonate (US et Canada)
-
Case dimensions
Length : 185 mm (7,3 inches)
Width : 185 mm (7,3 inches)
Height : 119 mm (4,7 inches)
-
Weight of the case
1,2 kg
-
Protection rating
IP 65
-
Display
Blue back-light 128x64 LCD screen
-
Inputs
Measurement inputs
2x 4…20mA inputs on special configuration modules
Auxiliary input
1x 4…20mA auxiliary input for additional function (Option)
Control inputs
1x control input for external Start/Stop
1x control input for level tank or flow-level input
CAD
Flsw
Metering input
1x flow meter pulse input or chemical product level tank
Flow
Outputs
Relay outputs
4x Free of potential relays Max. 5A 250VAC
KA;KB;KC;KD
Analog outputs
2x Analog outputs 0/4…20 mA Max 500 Ω
IA ; IB
Printer output
1x RS232 for serial printer
SV3
Communications
RS485 Bus
1x Communication port RS485 type for compatible software
protocol type “MODBUS RTU”
RS485
Modem (Optional)
1x RJ-45 connector for phone line socket modem or GSM,
WIFI or Ethernet internal modem.
Modem line

Technical characteristics Page 11/40
Installation and starting instruction manual SYCLOPE TRACE’O®
2) Main functions
Main functions
Function
Specification (s)
Comment(s)
Controls
Controls of the 2 selected parameters
According the version
Trace detection
Total chlorine / Ozone
Specific processes
Actuator type 4x Free of potential relays outputs
0/4…20 mA outputs
PWM command
Impulse command
On/Off command with hysteresis
Alarms Low, high and technical alarms
Expressed in real measurement values
Control of top and bottom thresholds
Closed-loop control Remote control
Flow rate control
Closed-loop control of injections with an
external contact (filtering, for example)
or with flow-switch control from cell.
Level tanks Low level detection for chemical tanks
Control of each injection channel to one
or two external contact(s). (Flow et Flsw)
Timers
Programming of polarisation
depolarisation controls timers
According to the type of measurement
entries.
Communication RS485 local port half-duplex
External communication port with
“MODBUS RTU” supported.
Maintenance
Assistance to maintenance
Checking of general good working
Supervision
Remote supervision via modem
Event tracking

Technical characteristics Page 12/40
Installation and starting instruction manual SYCLOPE TRACE’O®
3) Measurement parameters, scales and control ranges
a) Basic versions : Direct entries (2x 4…20mA) or isolated entries (2x 4…20mA)
The main and auxiliary entries are programmable as bellow:
Measurements and controls
Parameter
Range of measurement
Accuracy
T°C /°K / °F -5 to 45°C
0 to 100°C ± 0,5 %
pH 2 to 11 pH ± 0,5 %
Free chlorine
0 to 1mg/l
0 to 2mg/l
0 to 5mg/l
0 to 10mg/l
± 0,5 %
Active chlorine
0 to 1mg/l
0 to 2mg/l
0 to 5mg/l
0 to 10mg/l
0 to 20mg/l
0 to 50mg/l
0 to 100mg/l
0 to 200mg/l
0 to 250mg/l
± 0,5 %
Total chlorine (Trace function)
0 to 1mg/l
0 to 2mg/l
0 to 5mg/l
0 to 10mg/l
0 to 20mg/l
± 0,5 %
Chlorine dioxide
0 to 0,5mg/l
0 to 1mg/l
0 to 2mg/l
0 to 5mg/l
0 to 10mg/l
± 0,5 %
Chlorites 0 to 1mg/l
0 to 2mg/l ± 0,5 %
Bromine
0 to 1mg/l
0 to 2mg/l
0 to 5mg/l
0 to 10mg/l
0 to 20mg/l
± 0,5 %
Oxygen
0 to 0,5mg/l
0 to 1mg/l
0 to 2mg/l
0 to 5mg/l
0 to 10mg/l
0 to 50mg/l
0 to 100mg/l
0 to 200mg/l
0 to 250mg/l
0 to 500mg/l
0 to 1000mg/l
0 to 2000mg/l
0 to 5000mg/l
± 0,5 %

Technical characteristics Page 13/40
Installation and starting instruction manual SYCLOPE TRACE’O®
Ozone (Trace function)
0 to 0,5mg/l
0 to 1mg/l
0 to 2mg/l
0 to 5mg/l
0 to 10mg/l
± 0,5 %
Redox (ORP)
0 to 1000mV
0 to 1500mV
0 to 2000mV
+/- 1000mV
+/- 1500mV
+/- 2000mV
± 0,5 %
Peroxide (H2O2)
0 to 2mg/l
0 to 10mg/l
0 to 20mg/l
0 to 50mg/l
0 to 100mg/l
0 to 200mg/l
0 to 500mg/l
0 to 1000mg/l
0 to 2000mg/l
0 to 5000mg/l
0 to 1000mg/l
± 0,5 %
Peracetic Acid (PA)
0 to 2mg/l
0 to 10mg/l
0 to 20mg/l
0 to 50mg/l
0 to 100mg/l
0 to 200mg/l
0 to 500mg/l
0 to 1000mg/l
0 to 2000mg/l
0 to 5000mg/l
0 to 1000mg/l
± 0,5 %
PHMB
0 to 50mg/l
0 to 100mg/l
0 to 200mg/l
0 to 500mg/l
± 0,5 %
Input current 0 to 20mA ± 0,5 %
b) Version with 1 isolated potentiometric entry and 1 isolated 4-20mA entry
The main entry can be programmed according to the version as bellow :
Measurements and controls of the main entry
Parameter
Range of measurement
Accuracy
pH 2 to 11 pH ± 0,5 %
Rédox 0 to 1000 mV ± 0,5 %
Rédox 0 to 1500 mV ± 0,5 %
Rédox +/- 1000 mV ± 0,5 %
Rédox +/- 1500 mV ± 0,5 %
SYCLOPE TRACE’O®controller will detect automatically the type of the additional module!

Technical characteristics Page 14/40
Installation and starting instruction manual SYCLOPE TRACE’O®
The auxiliary entry can be programmed as the normal 4…20mA entry (cf. :a)
c) Version with 2 potentiometric entries
The main entry and the auxiliary entry can be programmed only as bellow :
Measurements and controls
Parameter
Range of measurement
Accuracy
pH 2 to 11 pH ± 0,5 %
Rédox 0 to 1000 mV ± 0,5 %
Rédox 0 to 1500 mV ± 0,5 %
Rédox +/- 1000 mV ± 0,5 %
Rédox +/- 1500 mV ± 0,5 %
SYCLOPE TRACE’O®controller will detect automatically the type of the additional module!

Commissioning Page 15/40
Installation and starting instruction manual SYCLOPE TRACE’O®
IV. Installation and wiring
1) Installation conditions
To guarantee user safety and ensure correct operation of your SYCLOPE ODISEA®,
please observe the following installation instructions:
Install the controller in a dry location
The controller must be protected against rain, frost and direct sunlight
The room temperature must range between 0°C and 50°C, with no condensation.
Choose an installation location free from vibration, on a suitable support and with no
deformation
If these instructions are not observed:
The controller is at risk of being damaged
The measurements can be disrupted
The warranty is not applicable!
2) Installation of the wall-mounted controllers
Before performing the installation and electrical connections, remember to turn off the
power!
The rating of IP65 is only guaranteed when the closing cover and the glass of the electric
box are closed and when the cable glands match the diameters of your cables and are
correctly sealed
►Drilling three holes (∅5-mm) according to the following drilling plan
►Inserting the 5-mm plugs using a hammer
►Insert the upper screw (top screw) first without completely tightening it
►Insert the lower screws and tighten them
►Tighten the upper screw
►Use a spirit level to check for correct and accurate fixing to the wall.
3) Electrical connections
The electrical installation must be performed in accordance with current standards by
authorized personnel!
A 30 mA differential circuit breaker must be installed!
150mm
119mm

Commissioning Page 16/40
Installation and starting instruction manual SYCLOPE TRACE’O®
A breaker circuit of maximum 10A must be installed near the controller and easily accessible
to stop the main power. It must be identified as a circuit-breaker for the controller!
Before performing the connections, remember to turn off the power!
Use multicore cables if possible!
If not possible, always use a special wiring tip to be sure that wires do not make a contact
together!
Protect the wirings by using electrical clamps.
The SYCLOPE TRACE’O®controller must be connected to the main recirculation pump
system by means of the "remote control" input (CAD) to disallow functionality in the case of
the main pump being stopped.
The controller is protected by a glass time-lag fuse type of 315 mA over-current and by a varistor
against voltage surges over 275 V.
Reference
Name
FUS5X20T315
Time-lag fuse 315mA 5x20 Glass
In case of fuse destroyed, check that the card is not burnt. If this is the case, the complete
card must be changed!
In case of varistor burned, please return the controller to our technical after-sales
department for repairing!
4) Connection of the primary power supply
The SYCLOPE TRACE’O®controller is equipped with a switching power supply. It is
therefore able to be supplied by an AC voltage used between 90V to 240V - 50/60Hz.
►Use a 3-point 1.5 mm2cable to wire the power supply
►Strip the 3 wires for 7 mm
►Pass the 3-point cable through a cable gland
►Wire the live to 1 and the neutral to 2 of the sector terminal block B1
►Wire the ground to contact PL1 with the help of an M4 eyelet terminal
►Tighten the cable gland to ensure tightness
The controller does not have its own independent power switch. It is directly powered when
connected to the main power supply.

Commissioning Page 17/40
Installation and starting instruction manual SYCLOPE TRACE’O®
5) Connexion of the free of potential relays (KA, KB, KC et KD)
The free of potential output relays are used to control the various measured parameters. They are
used also for alarm transfers or for driving magnet valves of water entries when the controller is
programmed as a trace measurement.
6) Connection of the measurement inputs
The main entry and the auxiliary entry are dedicated to various type of parameters. The controller is
equipped with three entries maximum according to the module configuration.
Using SYCLOPE cells is mandatory. They are adapted to the different type of sensors and
offer the best guaranty of good measurement. No claim will be received in case of unrespect
of this condition.
a) Basic version (2 entries 4…20mA NOT isolated)
The amperometric measurement inputs generate their own power supply and should not be
powered in any case!
When no module is used, the entries are NOT insolated!
Please, respect the polarity of the amperometric sensor! When using a SYCLOPE cell, the
colors of the wires are :
Entry + : White wire
Entry - : Blue wire
Temperature probe
without polarity
Amperometric sensor :
Respect polarity

Commissioning Page 18/40
Installation and starting instruction manual SYCLOPE TRACE’O®
b) Full mA entries module (3x entries 4…20mA)
The amperometric measurement inputs generate their own power supply and should not be
powered in any case!
The main and auxiliary entries E1 and E2 are isolated (E1 & E2).
The last passive entry is not isolated (E3).
Please, respect the polarity of the amperometric sensor!
Entry + : Blue wire (Left terminal)
Entry - : White wire (Right terminal)
c) Potentiometric and mA entries module (1x mV & 2x 4…20mA)
The amperometric measurement inputs (E1 and E2) generate their own power supply and
should not be powered in any case!
The main potentiometric entry E1 is isolated (E1).
The auxiliary 4…20mA entry E2 is isolated (E2).
The last passive entry is not isolated (E3).
Please, respect the polarity of the amperometric sensor!
Entry + : Blue wire (Left terminal)
Entry - : White wire (Right terminal)
Temperature probe
without polarity
Amperometric sensor :
Respect polarity
pH or REDOX sensor
Hot point to the left
Amperometric sensor :
Respect polarity

Commissioning Page 19/40
Installation and starting instruction manual SYCLOPE TRACE’O®
d) Potentiometric entries module (2x mV & 1x 4…20mA)
The main and auxiliary potentiometric entries are isolated ! (E1 &E2).
The last passive entry is not isolated (E3).
Please use a shielded cable connected as bellow:
Entry + : Hot wire of the shielded cable
Entry - : Guard of the shielded cable
e) Connecting a 4…20mA « Active » sensor
E1 and E2 entries cannot be used with an « active » sensor when isolated !
Normally, the E1 and E2 entries are powered and E3 entry is passive (No power generated).
When connecting an active sensor (power generated by another source, the wiring must be
executed as bellow:
When using an « active » sensor:
+of the active output (sensor) ⇔-to the entry (E1, E2 or E3)
-of the active output (sensor) ⇔-of the internal power supply (+Ref-)
pH or REDOX sensor
Hot point to the left
pH or REDOX sensor
Hot point to the left

Commissioning Page 20/40
Installation and starting instruction manual SYCLOPE TRACE’O®
7) Connections of the analogue outputs (IA1 and IA2
The analogue outputs of the SYCLOPE TRACE’O®controller are used to forward information to a
central unit or to control a dosing unit by means of a signal of 0/4…20 mA.
The analogue outputs of the SYCLOPE TRACE’O®controller are fully configurable. You can therefore
assign an output to any measured parameter and use it for regulation or transfer operations.
8) Connection of the remote control input (CAD)
The SYCLOPE ODISEA®controller has a remote control input “CAD” which stops the regulation
units. This input is an open/closed contact input used in a subservient manner to the main circulation
pump of the pool filtration system.
It is compulsory to slave your SYCLOPE ODISEA®controller to the switch of the filter
motor to prevent incidents caused by overloads!
The remote control input is designed to receive a NO contact (normally open).