manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. System Sensor
  6. •
  7. Smoke Alarm
  8. •
  9. System Sensor OSI-RE-SS User manual

System Sensor OSI-RE-SS User manual

SPECIFICATIONS
Wire Gauge for Terminals: 22 AWG (0.64 mm, 0.34 mm2) to 14 AWG (1.6 mm, 2.08 mm2)
Operating Voltage Range: 10.2 to 32 VDC (12 or 24VDC nominal)
Maximum Standby Current: 7 mA @ 32 VDC, 11 mA @ 24 VDC, 20 mA @ 12 VDC, 50 mA @ 10.2 VDC
Maximum Alarm Current (LED on): 11 mA @ 32 VDC, 15 mA @ 24 VDC, 24 mA @ 12 VDC, 54 mA @10.2 VDC
Operating Humidity Range: 0% to 95% Relative Humidity, Non-condensing
Operating Temperature Range: UL-Listed for use from 32°F to 100°F (0°C to 37.8°C)
Application Temperature Range: 20°C to +55°C (-4°F to 131°F)
Adjustment Angle: 20 degrees vertical, 50 degrees horizontal
Sensitivity Levels: Level 1 25%, Level 2 30%, Level 3 40%, Level 4 50% Automatically set at start up
Fault Condition (Trouble): Long-term drift reference out of 20% range, beam blockage or detector out of alignment, imager saturated.
Alignment Aid: LED directional arrows
Alarm Indicator: Local red LED and remote output
I56-6654-000
QUICK START GUIDE
OSI-RE-SS
Smoke Detection System
This guide provides information on how to install the OSI-RE-SS Smoke Detec-
tion System.
Extensive product and critical product security information can be found
in the OSI-RE-SS Installation Guide (Document No. E56-6654) available at
www.systemsensoreurope.com/products/category/beam-smoke-detectors/.
The OSI-RE-SS system consists of an Imager and a reflector.
The products shall be powered from a EN54-4 certified AC/DC Power convert-
ers to be in compliance for CE certification.
FIGURE 1. IMAGER AND REFLECTOR
C2051-00, C2052-00
DETERMINE THE POSITIONS OF THE IMAGER AND REFLECTOR
COMPONENTS
Make sure that the intended mounting locations meet the following criteria
(See Figure 2.):
• Detector spacing must comply with local codes and standards
• Reflector must be located within the Field of View (FOV) of the Imager
• Clear path between the reflector and Imager
• Mounted well above the head-height of people and obstructions
• Avoid direct sunlight onto the units
The Imager and reflector should be placed within a recommended distance
below the ceiling. (See Figure 3.) This value will vary according to regional
specifications, geometry, and specific requirements for the installation. The
distance for flat ceilings and basic spacing requirements (S) is shown in the
following table.
Standard Distance from Ceiling Maximum Spacing (S)
NFPA 72 300 mm (12 in.) minimum 18.3 m (60 ft)
AS1670.1 25 to 600 mm (1 to 23.6 in.) 14 m (45.9 ft)
BS5839.1 25 to 600 mm (1 to 23.6 in.) 15 m (49.2 ft)
GB50166 300 to 1000 mm (11.8 to 39.4 in.) 14 m (45.9 ft)
For full information on spacing requirements, please refer to your local codes
and standards.
FIGURE 2. MOUNTING LOCATIONS
12” minimum
(0.3m)
10’ (3.0m)
minimum
Typical
30’
(9.1m) maximum
To First
Detectors
1/2 S S
Wall
C2053-00
FIGURE 3. MOUNTING LOCATIONS
Ex. Distances according to NFPA 72 (S524 in Canadian applications).
1/2 S maximum
ReflectorTx/Rx
S
Tx/Rx Reflector
16 ft. (5m) minimum
328 ft. (100m) maximum
1/4 S
maximum
C2054-00
Pittway Tecnologica S.r.l.,
Via Caboto 19/3,
34147 TRIESTE, Italy
1 I56-6654-000
13/10/2020
MOUNT THE REFLECTOR USING THE DRILL TEMPLATE
Refer to Appendix II. in Installation guide for drill template instructions.
MOUNTING THE DETECTOR
Remove detachable front rim cover. To detach the Imager part from the
backbox, loosen the 3 holding screws.
To provide cable access to the Termination Card of the Imager remove the
cut-outs from the back, bottom or top of the main assembly by using a sharp
blade to cut around the circular discs.
Secure the back box directly onto the mounting surface using any suitable
number of the 5 pilot holes in the backbox.
Use appropriate fasteners to secure the back box component to the mounting
surface.
FIGURE 4.MOUNTING THE DETECTOR
Cable knock-outs
bottom
Cable knock-outs
top
Holes for the fixing
of the detector
Large knock-out
for 4” J-Box
Mounting holes
C2055-00
WIRE THE TERMINATION CARD ON THE IMAGER
• Wire the initiating device circuit on the Imager Termination Card using
the FIRE and FAULT relay terminals for a four-wire device connection.
(See Figure 5.)
Note: For all relay connections, break wire run to allow monitoring.
• Wire external power to the unit via the POWER terminals. (See Figure 6.)
• Wire the Remote Indicator and/or remote test or reset units if required.
• Securely connect the wires to the plug-in terminals and engage in the
receptacles at the back of the Imager
• Switch on the heater if the installation requires so.
• Re-attach the Imager to the back box
• Remove the protective film from the lens surface of the imager.
• Connect power to the Imager
Note: Analog addressable Input/zone modules can also be used with the
system. For further detail, please consult the relevant FACP Product Guide.
FIGURE 5. WIRING THE TERMINATION CARD
T4
T2
T3
T1
Fault NO
Fault COM
Fault COM
Fault NC
Alarm NO
Alarm Common
Alarm Common
Alarm NC
Power In -
Power In -
Power In +
Power In +
AUX (-)
Remote Test/Reset Input
Remote Trouble Output
Remote Alarm Output
Heater on/off switch
USB
Connector
Jumper
No heater Heater ON
C2056-00
FIGURE 6. WIRING DIAGRAM
POWER +
POWER -
INITIATING +
INITIATING -
CLASS A
RETURN
LOOP
POWER IN (+) POWER OUT (+)
POWER IN (-) POWER OUT (-)
ALARM COM ALARM COM
ALARM NO ALARM NO
TROUBLE
COM
TROUBLE
NC
POWER IN (+) POWER OUT (+)
POWER IN (-) POWER OUT (-)
ALARM COM ALARM COM
ALARM NO ALARM NO
TROUBLE
COM
TROUBLE
NC
AUX (-)
REMOTE ALARM OUTPUT
REMOTE TROUBLE OUTPUT
REMOTE TEST/
REMOTE INPUT
AUX (-)
REMOTE ALARM OUTPUT
REMOTE TROUBLE OUTPUT
REMOTE TEST/
REMOTE INPUT
NOTE: If other sensors are installed on the same loop, a listed end of line power supervision
module is required.
EOL
RESISTOR
C2057-00
2 I56-6654-000
13/10/2020
FIGURE 7. OSI-RE-SS TERMINALS
T1
RTS151/Key
Terminals
T3
T4
T5
T2
OSI-RE-SS Terminals
External
Jumper
10k ohm
External
Resistor
Remote Alarm Output
Remote Trouble Output
Remote Test/Reset Input
AUX -
T2-1
T2-3
T2-2
T2-4
C2058-00
FIGURE 8. REMOTE LED CONNECTIONS
Alarm
Signal
Circuit
Trouble
Signal
Circuit
Yellow
Red
T2-1
T2-2
T2-4
Remote LED connections
C2059-00
INITIALIZATION AND COMMISSIONING
Ensure that neither you nor any other objects are in the line of sight between
the detector and the reflector and start to manually align the Imager to the
reflector (See Figure 9.)
The OSP-002 Laser Alignment Tool can be used for the rough alignment if
the system is to be installed at longer distances or in heavy lit environments.
Follow these steps to adjust the optical sphere of the detector component to
align the system (See Figure 10.):
• Make sure the lever is the 3 o’clock position.
• The 4 arrows will intuitively guide the user to optimal eyeball alignment.
Likely the alignment process will start with all arrows red.
• Gently move the eyeball until all arrows and the middle green LED blink
green for the eyeball to be optimal aligned (See Figure 11.).
• When all arrows are green, gently lock the eyeball by moving the lever
down till the eyeball is solidly locked. The lever is now in the 5 o’clock
position and you feel the resistance of the locked position.
FIGURE 9. COARSE ALIGNMENT
OSP-002 Laser
Alignment Tool
Reflector
C2060-00
FIGURE 10. ARROW ARRAY
C2061-00
FIGURE 11. LOCKING AND SECURING EYE BALL
Level down
C2062-00
By locking the eyeball an internal switch is activated and the detector will
now start its initiation or commissioning process. A normal commissioning
process takes roughly 10 seconds. During the commissioning process, the
beam path must remain clear from object intrusions.In this process cycle, the
detector will measure size of the reflector in the FOV and set the sensitivity
automatically to the optimum sensitivity for the specific distance.
Before going in operational mode, the detector will show its set sensitivity.
This is shown by blinking the 4 arrows to the colour yellow, reflecting the %
of selected obscuration/sensitivity. The key is; 1 blink = 25%, 2 blinks =
30%, 3 blinks = 40% and 4 blinks = 50%. After 5 seconds, the scenario will
be repeated a second time and the arrows LEDs go out and the front OK LED
blinks green. The detector is now in operation and working correctly.
The paintable rim can now be snapped over the front to secure the locking
lever and to hide the alignment LEDS and locking mechanism.
Applying the cover also secures the locking lever in position.
TESTING THE INSTALLATION
After the commissioning, the detector must be tested for correct alarming by
using the OSP-004 test filter at the reflector or using the remote test station.
When using the RTS151KEY for testing the detector, the remote fault LED will
blink the set sensitivity of the detector. The number of blinks, similar to sec-
tion 5, will represent the set sensitivity and the sequence is repeated every 3
seconds till the detector is reset.
IMAGER RESET
The fault relay is non-latching but the alarm relay is latching. The Imager
alarm can be reset by shortly dropping the supply voltage or by using a reset
station.
OPERATION AFTER A POWER FAILURE
After a power failure of any duration, when the supply is restored, the detec-
tor will check the possible new situation against its memorized data.
If the reflector is found in the same position and all parameters are within
acceptable limits, the detector will resume its operation and go out of fault
condition.
If any significant parameters have changed, it will remain in a fault condition
and a re-initialization will be required.
3 I56-6654-000
13/10/2020
OPERATION MODES AND TROUBLESHOOTING GUIDE OSI-RE-SS
Modes Red and Re-
mote Alarm
output
Yellow and
Remote Trouble
Output
Green Initiating means Comments & Troubleshooting Tips
Power on Off Blink Off Apply Power from dis-
charged state
• All wiring correctly done.
• Address switches set.
Alignment Off Blink Off Lever in 3:00 position
and commissioning is
active
• Ready to perform alignment.
• Follow guidance from the 4 arrows to correctly align.
Initializing/
Commissioning
Off Blink Off Lock lever in 6:00 posi-
tion to start commis-
sioning
• Commissioning and setting sensitivity.
• Do not interrupt beam.
Normal Off Off Blink Successful completion of
initialization or detector
reset
• Initializing finished.
• Detector operates normal in quiescent condition.
• Detector successfully reset.
Alarm On Off Off Smoke, Test Filter or RTS-
151KEY Test Station
• Blinks till reset from FACP or RTS151KEY.
Trouble-Drift
Compensation
Off 3 Quick Blinks Blink Long Term Drift Refer-
ence Out of 20% Range
• Reduced IR Signal
• Clean detector and reflector.
Trouble-Beam
Blockage
Off 4 Quick Blinks Blink Beam blockage or detec-
tor out of alignment
• Remove blockage or re-align detector
• Faulty unit.
Trouble-Imager
saturation
Off 5 Quick Blinks Blink Imager saturated • Sunlight or very strong light into detector or reflector.
• Re-position detector or reflector.
• Remove light source.
Test activated-
Pass Result
On Blinks the set sen-
sitivity by number
of blinks (1-4).
Repeats every 3
seconds till reset.
Off FACP or RTS151KEY • Remains in alarm until reset by FACP or RTS151KEY.
• Arrows blink sensitivity level that was selected au-
tomatically.
System Sensor® is registered trademarks of Honeywell International Inc.
DISCLAIMER
Please refer to the insert for the Limitations of Fire Alarm Systems.
For warranty terms, please refer to the Product Guide found at www.systemsensoreurope.com/products/category/beam-smoke-detectors/.
4 I56-6654-000
©2020 System Sensor. 13/10/2020

Other manuals for OSI-RE-SS

1

Other System Sensor Smoke Alarm manuals

System Sensor 1400 User manual

System Sensor

System Sensor 1400 User manual

System Sensor Inovair Flex D4240 User manual

System Sensor

System Sensor Inovair Flex D4240 User manual

System Sensor Innovair DH200PL User manual

System Sensor

System Sensor Innovair DH200PL User manual

System Sensor 2112TL User manual

System Sensor

System Sensor 2112TL User manual

System Sensor FAAST LT Use and maintenance manual

System Sensor

System Sensor FAAST LT Use and maintenance manual

System Sensor 1012 Ionization User manual

System Sensor

System Sensor 1012 Ionization User manual

System Sensor B501 User manual

System Sensor

System Sensor B501 User manual

System Sensor 2WTR-B User manual

System Sensor

System Sensor 2WTR-B User manual

System Sensor Innovair flex D2 User manual

System Sensor

System Sensor Innovair flex D2 User manual

System Sensor 7251 User manual

System Sensor

System Sensor 7251 User manual

System Sensor 2251EIS User manual

System Sensor

System Sensor 2251EIS User manual

System Sensor 6424 Technical specifications

System Sensor

System Sensor 6424 Technical specifications

System Sensor 2251-COPTIR User manual

System Sensor

System Sensor 2251-COPTIR User manual

System Sensor DH400ACDCIHT User manual

System Sensor

System Sensor DH400ACDCIHT User manual

System Sensor D4P120 User manual

System Sensor

System Sensor D4P120 User manual

System Sensor 2WTR-B User manual

System Sensor

System Sensor 2WTR-B User manual

System Sensor DH500ACDC User manual

System Sensor

System Sensor DH500ACDC User manual

System Sensor 2WT-B User manual

System Sensor

System Sensor 2WT-B User manual

System Sensor D4P120 User manual

System Sensor

System Sensor D4P120 User manual

System Sensor 1151 User manual

System Sensor

System Sensor 1151 User manual

System Sensor A310E User manual

System Sensor

System Sensor A310E User manual

System Sensor 1400A Direct Wire User manual

System Sensor

System Sensor 1400A Direct Wire User manual

System Sensor 1112/24B User manual

System Sensor

System Sensor 1112/24B User manual

System Sensor 2251EIS User manual

System Sensor

System Sensor 2251EIS User manual

Popular Smoke Alarm manuals by other brands

Swegon TBLZ-1-49-a GOLD Installation

Swegon

Swegon TBLZ-1-49-a GOLD Installation

Gira Dual Q user manual

Gira

Gira Dual Q user manual

Doro Secure 291 quick guide

Doro

Doro Secure 291 quick guide

Electia SDA-9 owner's manual

Electia

Electia SDA-9 owner's manual

Maverick ET-733 REDI CHEK manual

Maverick

Maverick ET-733 REDI CHEK manual

Eaton Cautiex D4-S5 Installation and operating manual

Eaton

Eaton Cautiex D4-S5 Installation and operating manual

Honeywell DFS8MS installation instructions

Honeywell

Honeywell DFS8MS installation instructions

Honeywell Fire-Lite Alarms D350RPL Installation and maintenance instructions

Honeywell

Honeywell Fire-Lite Alarms D350RPL Installation and maintenance instructions

FireAngel ST-625-INT manual

FireAngel

FireAngel ST-625-INT manual

Johnson Controls DH300RPL Installation and maintenance instructions

Johnson Controls

Johnson Controls DH300RPL Installation and maintenance instructions

Red Arrow SMAS-P2 installation instructions

Red Arrow

Red Arrow SMAS-P2 installation instructions

Alula 2GIG RE214T manual

Alula

Alula 2GIG RE214T manual

Thermoptek FireAngel ST-625 user manual

Thermoptek

Thermoptek FireAngel ST-625 user manual

Ei Electronics EI 100L Emergency Light product manual

Ei Electronics

Ei Electronics EI 100L Emergency Light product manual

BRK electronic PRC710B quick start guide

BRK electronic

BRK electronic PRC710B quick start guide

U-Line H-9468 Installation

U-Line

U-Line H-9468 Installation

Vermont Castings Signature VC3624GS Assembly and owner's manual

Vermont Castings

Vermont Castings Signature VC3624GS Assembly and owner's manual

Ei Electronics Ei151TL User instructions

Ei Electronics

Ei Electronics Ei151TL User instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.