TA STAD Series User manual

This manual suits for next models

22

Other TA Control Unit manuals

TA UDV User manual

TA

TA UDV User manual

TA STA User manual

TA

TA STA User manual

TA T011S User manual

TA

TA T011S User manual

TA STAF Series User manual

TA

TA STAF Series User manual

TA TBV User manual

TA

TA TBV User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Certification of Registration
Number 2125 and 2125 M
Certified by SP
Q
U
A
L
I
Y
A
N
D
E
N
V
I
R
O
N
M
E
N
S
Y
S
E
M
O
U
R
&
A
N
D
E
R
S
S
O
N
A
B
STAD (NPT threads), STAS (soldering) 5-5-12
Balancing valves 2002.04
Draining optional
Valves with draining for 3/4” NPS hose connection.
Valves without draining have a sleeve. This sleeve can
temporarily be removed and a draining kit be fitted, which is
available as an accessory.
Measuring points
The measuring points are self-sealed. Remove the cap and
insert the probe through the seal.
Application:
Heating- and cooling systems.
Tap water systems.
Functions:
Balancing
Pre-setting
Measuring
Shut-off
Draining (optional)
Pressure class:
PN 20
Temperature:
Max. working temperature: 250°F
Min. working temperature: -4°F
Material:
The valves are made of AMETAL®.
Seat seal: EPDM O-ring
Spindle seal: EPDM O-ring
Handwheel: Polyamide
AMETAL®is the dezincification resistant alloy of TA.
Marking:
Body: PN 20/150, DN and inch size.
Handwheel: Valve type and size.
General
Technical description
5-5-12 - 2
With draining
Excl draining
Draining can be installed during operation
Cvs = GPM at a pressure drop of 14,5 psi and fully open valve.
Excl. draining
Draining can be installed during operation
Cvs = GPM at a pressure drop of 14,5 psi and fully open valve.
Excl. draining
Draining can be installed during operation
Cvs = GPM at a pressure drop of 14,5 psi and fully open valve.
STAD: NPT threads
TA No Size D L H Weight
Lbs Cvs
d=3/4” NPS
52 151-814 1/2” N 1/2 NPT 3.50 4.00 1.5 2.92
52 151-820 3/4” 3/4 NPT 3.81 4.00 1.6 6.61
52 151-825 1” 1 NPT 4.31 4.50 2.0 10.1
52 151-832 1 1/4” 1 1/4 NPT 4.88 4.31 2.6 16.5
52 151-840 1 1/2” 1 1/2 NPT 5.13 4.75 3.3 22.3
52 151-850 2” 2 NPT 6.13 4.75 5.0 38.0
TA No Size D L H Weight
Lbs Cvs
52 151-514 1/2” N 1/2 NPT 3.50 4.00 1.5 2.92
52 151-520 3/4” 3/4 NPT 3.81 4.00 1.6 6.61
52 151-525 1” 1 NPT 4.31 4.50 2.0 10.1
52 151-532 1 1/4” 1 1/4 NPT 4.88 4.31 2.6 16.5
52 151-540 1 1/2” 1 1/2 NPT 5.13 4.75 3.3 22.3
52 151-550 2” 2 NPT 6.13 4.75 5.0 38.0
STAD: NPT threads with union end
TA No Size D L H Weight
Lbs Cvs
52 167-414 1/2” N 1/2 NPT 4.82 4.00 1.6 2.92
52 167-420 3/4” 3/4 NPT 5.18 4.00 2.1 6.61
52 167-425 1” 1 NPT 6.02 4.50 2.5 10.1
STAS: With solder ends
TA No Size D L H Weight
Lbs Cvs
52 151-914 1/2” N 1/2” 3.50 4.00 1.4 2.92
52 151-920 3/4” 3/4” 3.81 4.00 1.4 6.61
52 151-925 1” 1” 4.31 4.50 1.9 10.1
52 151-932 1 1/4” 1 1/4” 4.88 4.31 2.4 16.5
52 151-940 1 1/2” 1 1/2” 5.13 4.75 3.1 22.3
52 151-950 2” 2” 6.13 4.75 4.5 38.3
L
d
H
D
L
D
H
L
H
D
L
H
D
5-5-12 - 3
Setting of a valve for a particular pressure drop, e g corresponding to 2.3 turns on the graph, is carried out as follows:
1. Close the valve fully (Fig 1).
2. Open the valve 2.3 turns (Fig. 2).
3. Using a 3 mm Allen key, turn the inner spindle clockwise until stop.
4. The valve is set.
To check the setting: Close the valve, the indicator shows 0.0. Open it to the stop position. The indicator then shows the set value,
in this case 2.3 (Fig. 2).
Diagrams showing the pressure drop for each valve size at different settings and flow rates are available to help determine the
correct valve size and pre-setting (pressure drop). Four turns corresponds to fully opened valve (see Fig. 3). Opening it further will
not increase the capacity.
Fig. 1. Valve closed Fig. 2. The valve is set at 2.3 Fig. 3. Fully open valve
The zero position is calibrated and must not be changed.
Deviation of flow at different settings
The curve (Fig. 4) is valid for valves with normal pipe fittings* (Fig. 5). Try also to avoid mounting taps and pumps, immediately
before the valve.
Fig 4
Setting, No. of turns.
Fig 5
*) The valve can be installed with the opposite flow direction. The specified flow
detailsalsoarevalidforthisdirectionalthoughtolerancescanbegreater(maximum
5% more).
The flow calculations are valid for water (+68°F). For other liquids with approx. the same viscosity as water (≤20 cSt =
3°E=100S.U.), it is only necessary to compensate for the specific density. However, at low temperatures, the viscosity increases
and laminar flow may occur in the valves. This causes a flow deviation that increases with small valves, low settings and low
differential pressures. Correction for this deviation can be made with the software TA Select or direct in TA-CBI.
Setting
Measuring accuracy
Correction factors
5-5-12 - 4
When ∆p and the design flow are known, use the formula to calculate the Cv-value or use the diagram.
Software
TA Select: Makes it easy to choose the right balancing valves by taking into account the desired flow, pressure drop and flow rate.
Measuring instruments
Use the TA-CBI electronic instrument. It is programmed with valve characteristics for TA valves, enabling measured differential
pressure to be read off directly as a flow rate. For further information on TA-CBI, see catalogue leaflet TA-CBI.
Conversion disc
By using the conversion disc it is easy to calculate the relationship between flow, pressure and setting values for all valve sizes.
Manuals
See the following manuals for descriptions of various balancing methods:
Total hydronic balancing
Manual no. 1: Balancing control circuits
Manual no. 2: Balancing distribution systems
Manual no. 3: Balancing radiator systems
Manual no. 4: Stabilising differential pressure
Sizing
Support material
Cv values
No of
Turns 1/2”N 3/4” 1” 1 1/4” 1 1/2” 2”
0.5 .147 .593 .70 1.32 2.03 2.97
1.246 .878 1.19 2.20 3.83 4.87
1.5 .364 1.38 2.4 3.60 5.34 8.35
2.662 2.20 4.20 5.40 7.08 13.6
2.5 1.02 3.24 6.15 8.24 10.2 18.8
31.60 4.49 8.00 11.0 14.6 24.9
3.5 2.30 5.51 9.28 13.7 18.6 30.7
42.92 6.61 10.1 16.5 22.3 38.3
Cv
Cv
1,52 q in GPM, ∆p in Ft
q in GPM, ∆p in psi
5-5-12 - 5
Wanted:
Presetting for a 1”valve at a desired flow rate of 6.7 GPM and a pressure drop of 3 ft.
Solution:
Draw a straight line joining 6.7 GPM and 3 ft. This gives Cv=5.9. Now draw a horizontal line from Cv=5.9.
This intersects the bar for a 1”valve at the desired pre-setting of 2.35.
NOTE:
If the flow rate is out of the scale in the diagram, the reading can be made as follows: Starting with the example above, we get 3
ft., Cv=5.9 and flow-rate 6.7 GPM. At 3 ft. and Cv=0,59 we get the flow-rate 0,67 GPM, and at Cv=59, we get 67 GPM. That is, for
a given pressure drop, it is possible to read 10 times or 0.1 times the flow and Cv-values.
Diagram 1/2” - 2”
5-5-12 - 6
Measuring point
Max 250°F
Measuring point, extension
2 3/8 IN (60 mm)
Can be installed without draining of the system.
Handwheel, complete
Draining kit
Can be installed during operation
Size plate, handwheel
Identification tag
(incl 1 pc per valve)
Allen key
Tour & Andersson retains the right to make changes to its products and specifications without prior notice.
Accessories
TA No L
52 179-014 1 3/4
TA No
52 179-006
TA No
52 186-003
TA No d
52 179-997 3/4”NPS
TA No Size
308 812-01 1/2N
308 812-02 3/4
308 812-03 1
308 812-04 1 1/4
308 812-05 1 1/2
308 812-06 2
TA No
52 161-990
TA No
52 187-103 3 mm Pre-setting
52 187-105 5 mm Draining
d
1 1/4