14 of 16
EEPROM Read Error
The control was unable to read the in-
stallers settings from its memory. The
control was forced to load the factory
defaults for all settings. The control will
stop operation until all of the settings in
the Adjust menu have been checked.
Outdoor Sensor Short Circuit
A short circuit has been detected in the
outdoor sensor. The control assumes
an outdoor temperature of 32°F (0°C)
and continues operation. To clear this
error message, correct the short circuit
and press any button on the control.
Outdoor Sensor Open Circuit
An open circuit has been detected in the
outdoor sensor. The control assumes an
outdoor temperature of 32°F (0°C) and
continues operation. To clear this error
message, correct the open circuit and
press any button on the control.
Mixing Supply Sensor Short Circuit
A short circuit has been detected in the
mixing supply sensor. The control con-
tinues to operate the injection pump at
a low speed (17 - 18%) as long as a
demand is present. To clear this error
message, correct the short circuit and
press any button on the control.
Mixing Supply Sensor Open Circuit
An open circuit has been detected in
the mixing supply sensor. The control
continues to operate the injection pump
at a low speed (17 - 18%) as long as a
demand is present. To clear this error
message, correct the open circuit and
press any button on the control.
Error Messages
VIEW
!
OUT
VIEW
!
OUT
VIEW
!
MIX
VIEW
!
SUP
MIX
VIEW
!
SUP
MIX
VIEW
!
RET
MIX
VIEW
!
RET
VIEW
!
BOIL
VIEW
!
BOIL
Replacing Cartridge Assembly
1. Disconnect the electrical supply.
2. Reduce system pressure to 0 psi and allow system to return to room temperature. Isolate the XPB by closing the service valves or
draining the system.
3. Remove screw holding the VSMC module to X – Pump Block. Unplug both pump Molex plugs, power cord and heat source & sensor
terminal blocks from VSMC. Set VSMC control aside in safe place, away from water damage.
4. Remove 4 screws holding plastic housing to pump castings.
5. Remove the body bolts and swing motor assembly away from the body.
6. Pull cartridge out of the motor housing.
7. Install replacement cartridge, making sure that the cover plate is between the cartridge flange and motor.
8. Make sure the replacement cartridge corresponds to the full circulator product number. A complete parts list is available from your
local plumbing supply wholesaler.
9. Reassemble the circulator using the new gasket and bolts supplied.
10. Reassemble plastic housing and VSMC control in reverse order.
11. Follow the “Installation” procedure to start up the circulator.
Mixing Return Sensor Short Circuit
A short circuit has been detected in the
mixing return sensor. If the Maximum
Delta T setting is set to OFF, the con-
trol continues operation. If the Maxi-
mum Delta T setting is not set to OFF,
the control stops operation until the
fault is corrected. To clear this error
message, correct the short circuit and
press any button on the control.
Mixing Return Sensor Open Circuit
An open circuit has been detected in
the mixing return sensor. If the Maxi-
mum Delta T setting is set to OFF, the
control continues operation. If the Maxi-
mum Delta T setting is not set to OFF,
the control stops operation until the
fault is corrected. To clear this error
message, correct the open circuit and
press any button on the control.
Heat Source Sensor Short Circuit
A short circuit has been detected in the
heat source sensor. The boiler contact
is operated as if a heat source sensor
is not installed. The control provides a
heat source enable and does not pro-
vide heat source protection. To clear this
error message, correct the short circuit
and press any button on the control.
Heat Source Sensor Open Circuit
An open circuit has been detected in the
heat source sensor. The boiler contact
is operated as if a heat source sensor is
not installed. The control provides a heat
source enable and does not provide heat
source protection. To clear this error
message, correct the open circuit and
press any button on the control. If the
sensor was deliberately removed, power
down the control.