TCL u Series User manual

u Series Digital PID Controller
Operation Manual
uTC52 uTC72 uTC42 uTC92 uTC62
48x48 72X72 48X96 96X96 96X48
(DIN 1/16) (DIN 3/16) (DIN 1/8) (DIN 1/4) (DIN1/8)
March 2006
uTC / uPC OpMan
TCL

1
CONTENT
1 Notice before start- up ……………………………………………………… Page 3
2 Specifications ………………………………………………………………… Page 4
3 Terminal arrangement
3.1 uTC52 Terminals ……………………………………………………… Page 6
3.2 uTC62 Terminals ……………………………………………………… Page 7
3.3 uTC72 Terminals ……………………………………………………… Page 8
3.4 uTC42 Terminals ……………………………………………………… Page 9
3.5 uTC92 Terminals ……………………………………………………… Page 10
4 External dimension and panel cutout …………………………………… Page 11
5 Parts description…………… ……………………………………………… Page 12
6 Operations
6.1 Power On …………………………………………………………….. Page 13
6.2 Change the Set Value (SV) ………………………………………… Page 13
6.3 Change The Alarm Value…………………………………………… Page 13
6.4 Autotuning (AT) ……………..………………………………………… Page 14
6.5 Programmable RAMP / SOAK ……………………………………….. Page 15
7 Operation levels
7.1 Levels diagram ………………………………………………………. Page 16
7.2 Lock function ……………………………..……………………..…… Page 16
8 Parameters
8.1 Level 1 (User Level) ………………………………………………… Page 17
8.2 Level 2 (PID Level)
8.2.1 Level 2 parameters display / hiding condition…..……... Page 18
8.2.2 Description of parameters………………………………… Page 19
8.3 Level 3 (Input Level) ………………………………………………… Page 20
8.4 Level 4 (SET Level)
8.4.1 How to hide parameters (Use SET1~SET7) …………… Page 22
8.4.2 Special functions (Use SET8 / SET9 / SET0)………..… Page 23
8.4.3 Remote SV type selection…………………………………… Page 24
8.4.4 Output mode selection (Use OUTY) ……………………… Page 24
8.5 Program Level
8.5.1 Description of parameters ………………………………… Page 25
8.5.2 Description of operation…………………………………… Page 26
9 Input type table ………………………………………………………………… Page 27
10 Alarm
10.1 Alarm time……………………………………………………………… Page 29
10.2 SETA …………………………………………………………………… Page 29
10.3 Alarm mode …………………………………………………………… Page 30

2
11 Heater Break Alarm(HBA) ……………………………………………… Page 31
12 Error codes ………………………………………………………………… Page 34
13 Modify input type: TC, RTD ……………………………………………… Page 35
14 Modify input type: Linear Input (mA ,V)
14.1 Hardware ……………………………………………………………… Page 36
14.2 Calibration ……………………………………………………………… Page 37
15 Modify output type: Relay, SSR, 4~20mA ………………………………… Page 38
16 Modify output mode: OUT1/ALARM, OUT1/OUT2 ……………………… Page 38
17 Applications
17.1 RAMP & SOAK ………………………..……………………………… Page 39
17.2 TTL Communication:SV output and RATE function……………… Page 40
17.3 1ψPhase angle control (By SCR module) ………………………… Page 41
17.4 1ψPhase angle control (By TRIAC) …………...…………………… Page 42
17.5 3ψPhase angle control ( By DIODE/SCR module)……………….. Page 43
17.6 1ψZero crossing control (By SCR Module) ………………..……… Page 44
17.7 1ψZero crossing control (By TRIAC) ……………….……………… Page 45
17.8 3ψZero crossing control (By SCR module) ……………………… Page 46
17.9 3ψZero crossing control (By TRIAC) ……………………………… Page 47
17.10 3 wires proportional motor valve control ……………..………… Page 48
17.11 Wiring diagram of PC Communication …………………………. Page 49

3
1. Notice before start-up
FY series controller has got the CE approvals as below:
LDV:D/N EN61010-1
EMC:EN 55 022 1994 /A1:1995/ A2:1997
EN 61 000-3-2:1995 / -3-3:1995
EN 61 000-4-2:1995 / -4-3:1996 / -4-5:1995 / -4-6
1996 / -4-8:1993 / -4-11:1996/ EN 50 204:1995
Please confirm the specification of controller is to totally with your requirement before
using it, also read this manual in detail.
Danger
1. Danger! Electric Shock!
DON'T touch AC power wiring terminals when controller has been
powered!
Keep the power off until all of the wirings are completed!
Warning
1. Please confirm that the AC power wiring to controller is correct, otherwise it will
cause serious damage to the controller. ( uTC52 connected to Pin 1 and 6,
uTC 62, 72, 42, 92 to Pin 1 and 2).
2. Be sure to use the rated power supply (AC85~265V or DC24V), otherwise it would be
cause serious damage to the controller.
3. Please use correct wiring as per diagram for (Input, Output etc).
4. Use M3 screw-compatible crimp-on terminals with an insulation sleeve, as shown
below
3.2mm 3.2mm
Torque : 0.4 N.m (4kgf.cm)
5. Avoid installing controller in following environment:
I. A place where the ambient temperature may exceed the range
0 to 50℃
II. A place where the ambient humidity may exceed the range
from 20 to 90%RH.
III.A place where the controller likely to come into contact with water, oil,
chemicals, steam and vapor.
IV. A place where the controller is subject to interface from static
electricity, magnetism, excessive vibration and electrical noise.
6. For thermocouple (TC) input, use shielded compensating lead wire.
7. For RTD input, use shielded wiring which haslow resistance and
a close resistance match between the 3 wires.

4
5. Parts description
uTC52
Y1
Y2
AT
AL
AL
PRO
1
2
1
2
3 5 6 7
10
11
12
15
9
8
uTC62
1 2 13 10 15 14
11 8 9 12 16 57
4 3 6
uTC42
1 2
9
8
12
4
3 5 6
7
13
16
14
15
11
10
uTC72 / uTC92
1
2
16
3 4 5 6 7
8 9 10 11 12 13 14 15
SYMBOL NAME FUNCTION
PV 1Measured value
(PV) display Displays PV or various parameter symbols
(Red)
SV 2Set value
(SV) display Displays SV or various parameter set values
(Green)
SET 3Set key Used for parameter calling up and set value
registration
A/M 4Auto/Manual key Switches between Auto(PID) output mode and
Manual output mode.
5Shift key Shift digits when settings are changed
6Down key
*Program hold Decrease numbers (-1000,-100,-10,-1)
*Program hold
〈
Programmable controller
〉
7Up key
*Program run Decrease numbers (+1000,+100,+10,+1)
*Program run
〈
Programmable controller
〉
OUT1 8OUT1 lamp Lights when OUT1 is activated (Green)
OUT2 9OUT2 lamp Lights when OUT2 is activated (Green)。
AT
10
Auto tuning lamp Lights when Auto tuning is activated (Orange)
AL1
11
Alarm 1 lamp Lights when Alarm 1 is activated (Red)
AL2
12
Alarm 2 lamp Lights when Alarm 2 is activated (Red)
AL3
13
Alarm 3 lamp Lights when Alarm 3 is activated (Red)
MAN
14
Manual output lamp Lights when manual output is activated
(Orange)
PRO
15
*Program running
lamp *Flashes when program is running
〈
Programmable controller
〉。
OUT1%
16
OUT% bar-graph
display Output% is displayed on 10-dot LED.

5
zOptional Spec.
Model uM
uTC52 uTC62 uTC72 uTC42 uTC92
Output 2 For heating and cooling control use.
Relay , SSR , 4~20mA , 0~20mA , 0~5V , 0~10V , 1~5V , 2~10V
SPST type SPDT type SPST type SPDT type SPDT type
Alarm 2 3A , 220V , electrical life:100,000 times or more (under rated load)
Available Available Available AvailableNot
available SPST type SPST type SPST type SPST type
Alarm 3 3A , 220V , electrical life:100,000 times or more (under rated load)
Display range of heater current : 0.0~99.9A ,Accuracy : 1%FS
Included CT : SC-80-T
Heater Break Alarm
(HBA) Alarm relay : AL1
Available for PV or SV transmission
Transmission 4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Remote SV 4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Protocol : MODBUS RTU , MODBUS ASCII , TAIE
RS232 , RS485 , TTL
Communication
Baud rate: 2400 , 4800 , 9600 , 19200 , 38400 bps.
Data bits : 8 , Stop bit : 1 or 2bit , Odd or Even parity.
Water/Dust proof IP65
zSpecial control output (OUT1)
Model uTC52 uTC62 uTC72 uTC42 uTC92
1φzero crossing
control(1φSSR) Available Not available Available Not
available Available
3φzero crossing
control(3φSSR) Not available Available
Motor valve control Available
1φphase angle
control(1φSCR) Not available Available
3φphase angle
control(3φSCR) Not available Available
zProgrammable RAMP/SOAK
Model uPC52 uPC62 uPC72 uPC42 uPC92
Programmable
RAMP/SOAK 2 patterns with 8 segments each.
The 2 patterns can be linked together as 16 segments use.

6
3. Terminal arrangement
3.1 uTC52 Terminals ( 48mm x 48mm , DIN 1/16 )
AC 85~265V
DC 15 ~50V(Option)
A.Power Supply
Relay SSR mA,V
OUT1
G1
K1
G2
K2
OUT1
(1ΦZero Cross
Control)
Relay SSR mA,V
OUT2
2
3
CLOSE
OPEN
COM
OUT1
(Proportional Motor
Valve Control)
B.Control Output
mA,V RTD TC,mV
C.Input
2
3
AL 1
11
12
AL 1
13
14
AL 2
D.Alarm
TRS
E.Transmission
RS232
F.Communication
11
12
13
RD
SD
SG
RS485
11
12
Dx-
Dx+
TTL
11
12
13
RD
SD
SG
(Option)
(Use OUT1 & OUT2)
(Proportional Motor
Valve Control)
H.CT Input
CT
11
12

7
3.2 uTC62 Terminals ( 96mm x 48mm , DIN 1/8 )
AC 85~265V
DC 15 ~50V(Option)
A.Power Supply
Relay SSR mA,V
OUT1
K2
G2
K1
G1
OUT1
(1ΦPhase
Angle Control)
Relay SSR mA,V
OUT2
6
7
CLOSE
OPEN
OUT1
(Proportional Motor
Valve Control)
B.Control Output
mA,V RTD TC,mV
C.Input
AL 1
6
7
AL 2
D.Alarm
TRS
E.Transmission
RS232
G.Communication
14
15
16
RD
SD
SG
RS485
14
15
Dx-
Dx+
TTL
14
15
16
RD
SD
SG
(Option)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
7
8
9
10
COM
6
7
8
9
10
17
18
19
20
17
18
19
20
17
18
19
20
AL 3
12
13
Remote SV
F.Remote
14
15
H.CT Input
CT
14
15

8
3.3 uTC72 Terminals ( 72mm x 72mm)
AC 85~265V
DC 15 ~50V(Option)
A.Power Supply
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
Relay SSR mA,V
OUT1
G1
K1
G2
K2
OUT1
Relay SSR mA,V
OUT2
3
4
CLOSE
OPEN
OUT1
B.Control Output
mA,V RTD TC,mV
C.Input
3
4
AL 2
D.Alarm
TRS
E.Transmission
RS232
G.Communication
15
16
17
RD
SD
SG
RS485
15
16
Dx-
Dx+
TTL
15
16
17
RD
SD
SG
(Option)
COM
3
4
5
6
7
11
12
13
14
11
12
13
14
11
12
13
14
AL 1
18
19
Remote SV
F.Remote
9
10
5
6
7
21
15
16
17
18
20
PROT
G1
G2
OUT1
20
15
17
19
PROT
8
9
10
COM
NO
NC
(Proportional Motor
Valve Control)
(1ΦZero Cross
Control)
(1ΦPhase Angle
Control)
H.CT Input
CT
15
16

9
3.4 uTC42 Terminals ( 48mm x 96mm , DIN 1/8 )
AC 85~265V
DC 15 ~50V(Option)
A.Power Supply
Relay SSR mA,V
OUT1
K2
G2
K1
G1
OUT1
(1ΦPhase
Angle Control)
Relay SSR mA,V
OUT2
6
7
CLOSE
OPEN
OUT1
(Proportional Motor
Valve Control)
B.Control Output
mA,V RTD TC,mV
C.Input
AL 1
6
7
AL 2
D.Alarm
TRS
E.Transmission
RS232
G.Communication
14
15
16
RD
SD
SG
RS485
14
15
Dx-
Dx+
TTL
14
15
16
RD
SD
SG
(Option)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
7
8
9
10
COM
6
7
8
9
10
17
18
19
20
17
18
19
20
17
18
19
20
AL 3
12
13
Remote SV
F.Remote
14
15
H.CT Input
CT
14
15

10
3.5 uTC92 Terminals ( 96mm x 96mm , DIN 1/4 )
AC 85~265V
DC 15 ~50V(Option)
A.Power Supply
Relay SSR mA,V
OUT1
Relay SSR mA,V
OUT2
6
7
B.Control Output
mA,V RTD TC,mV
C.Input
AL 1
6
7
AL 2
D.Alarm
TRS
E.Transmission
RS232
G.Communication
14
15
16
RD
SD
SG
RS485
14
15
Dx-
Dx+
TTL
14
15
16
RD
SD
SG
1
2
3
4
5
6
7
8
9
10
21
22
23
24
25
26
27
28
29
30
17
18
19
20
17
18
19
20
17
18
19
20
AL 3
39
40
Remote SV
F.Remote
14
15
G1
G2
OUT1
(1ΦZero
Cross Control)
40
31
33
39
PROT
G1
K1
G2
K2
OUT1
(1ΦPhase
Angle Control)
CLOSE
OPEN
OUT1
COM
6
7
8
9
10
36
31
32
33
34
35
PROT
RG1
RG2
TG1
TG2
OUT1
(3ΦZero
Cross Control)
40
31
33
35
37
39
PROT
G1
K1
G2
K2
OUT1
(3ΦPhase
Angle Control)
40
31
32
33
34
39
PROT
G3
K3
35
36 RS232
31
32
33
RD
SD
SG
RS485
31
32
Dx-
Dx+
( Remote SV )
11
12
13
14
15
16
17
18
19
20
31
32
33
34
35
36
37
38
39
40
(Proportional Motor
Valve Control)
H.CT Input
14
15
CT

11
4. External dimension and panel cutout〈Unit:mm〉
uTC52 Y1
Y2
AT
AL
AL
PRO
1
250
50
44.5+0.5
44.5+0.5
65
70
uTC62
96
50
90.5+0.5
44.5+0.5
111
70
uTC72 74
74
68.5+0.5
68.5+0.5
89
94
uTC42 96
50
44.5+0.5
90.5+0.5
65
116
uTC92 96
96
90.5+0.5
90.5+0.5
111
116

12
5. Parts description
uTC52
Y1
Y2
AT
AL
AL
PRO
1
2
1
2
3 5 6 7
10
11
12
15
9
8
uTC62
1 2 13 10 15 14
11 8 9 12 16 57
4 3 6
uTC42
1 2
9
8
12
4
3 5 6
7
13
16
14
15
11
10
uTC72 / uTC92
1
2
16
3 4 5 6 7
8 9 10 11 12 13 14 15
SYMBOL NAME FUNCTION
PV 1Measured value
(PV) display Displays PV or various parameter symbols
(Red)
SV 2Set value
(SV) display Displays SV or various parameter set values
(Green)
SET 3Set key Used for parameter calling up and set value
registration
A/M 4Auto/Manual key Switches between Auto(PID) output mode and
Manual output mode.
5Shift key Shift digits when settings are changed
6Down key
*Program hold Decrease numbers (-1000,-100,-10,-1)
*Program hold
〈
Programmable controller
〉
7Up key
*Program run Decrease numbers (+1000,+100,+10,+1)
*Program run
〈
Programmable controller
〉
OUT1 8OUT1 lamp Lights when OUT1 is activated (Green)
OUT2 9OUT2 lamp Lights when OUT2 is activated (Green)。
AT
10
Auto tuning lamp Lights when Auto tuning is activated (Orange)
AL1
11
Alarm 1 lamp Lights when Alarm 1 is activated (Red)
AL2
12
Alarm 2 lamp Lights when Alarm 2 is activated (Red)
AL3
13
Alarm 3 lamp Lights when Alarm 3 is activated (Red)
MAN
14
Manual output lamp Lights when manual output is activated
(Orange)
PRO
15
*Program running
lamp *Flashes when program is running
〈
Programmable controller
〉。
OUT1%
16
OUT% bar-graph
display Output% is displayed on 10-dot LED.

13
6. Operations
6.1 Power On
Controller will display as below
Display input type
(K2) Display range
(0.0~400.0) Ready for use
All LED and 7 segment
displays will be lighted
6.2 Change the Set Value (SV)
Change SV from 0.0 to 100.0
Press key. The SV
number started to flash.
The flashing digit indicates
which digit can be set.
Press key
to select the hundreds digit.
Press key
to change the number to 1
Press key
to store the new
set value.
SET
6.3 Change the Alarm Value
Change AL1 value to “5.0” (AL1 active, if PV exceeds SV over 5.0)
Press key
to display parameter AL1 Press key
to change AL1 value Press key
increase AL1 value
Press key
store the new value
of AL1
SET
SET
* The are total 16 alarm mode types, please referred with “alarm mode” in page 30
* To change alarm mode, press SET + key 5 seconds to enter Level 3 (Input
Level) and then change ALD1/ALD2/ALD3 value.

14
6.4 Autotuning (AT)
Use AT function to automatically calculate and set the optimize PID value for your system.
Press key
to display parameter AT. Press key
to change AT setting Press key
change AT to “YES"
Press key
Start auto tuning
(AT lamp will be
lighted on)
SET
SET
OFFON ON OFF
ON / OFF Control
(Autotuning) PID Control
(After Autotuning)
SV PV
0%
100%
Output%
Autotuning
ATVL=0
OFFON ON OFF
SV
PV
0%
100%
Autotuning
ATVL=20
SV - 20
Autotuning failure
(Overshoot )
*Set ATVL to prevent overshoot occurred during
autotuning process.
Output%
ON / OFF Control
(Autotuning) PID Control
(After Autotuning)
To set ATVL ,press key 5 seconds to enter
Level 2 (PID Level) and then change the value.
SET
Possible cause 1:ATVL is too big. (If not sure,set ATVL=0)
Possible cause 2:Calculation time is too long.
(Set PID parameter manually)

15
6.5 Programmable RAMP / SOAK (Only available for uPC model)
*For detail of the programmable instruction, please refer with page 25.
Press key
to display SV_1 Set SV_1 to 200.0 Set TM_1 to 01.00
(1 hour) Set OUT1 to 100.0
SET
Assume the temperature profile is as below (use total 4 segments )
TIME
SV
RAMP SOAK RAMP SOAK
1 hour 30
minutes 50
minutes 1 hour and
20 minutes
200
120
Set SV_2 to 200.0 Set TM_2 to 00.30
(30 minutes) Set OUT2 to 100.0
Set SV_3 to 120.0 Set TM_3 to 00.50
(50 minutes) Set OUT3 to 100.0
Set SV_4 to 120.0 Set TM_4 to 01.20
(1 hour and 20 minutes) Set OUT4 to 100.0 Press key
to run program
(PRO LED start lighting)
Please operate conroller as following steps:

16
7. Operation levels
7.1 Levels diagram
LCK = 0000
Level 1
(User Level)
SET
SET
Press Key 5 seconds
SET
SET
Level 2
(PID Level) Level 3
(Input Level)
Press
Key 5 seconds
Press Key+ 5 seconds
Press Key+ 5 seconds
* The controller returns to Level 1 if there
is no key operation within 60 seconds.
A/M
* In any Level ,press key
twice will return to Level 1.
Level 4
(SET Level)
SET
Press Key+ 5 seconds
LCK = 1111
SET
Press Key+ 5 seconds
7.2 Lock function
To use lock function, please set parameter “LCK” in level 2.
Levels entering availableLCK Level 1
(User) Level 2
(PID) Level 3
(Input) Level 4
(SET)
Parameters which can be
changed
◎◎◎------ All parameters
(Factory set value)
◎◎------ ◎All parameters
◎◎------ ------ All parameters except level 3
◎◎------ ------ Parameters in level 1
◎◎------ ------ “SV” and “LCK”
◎◎------ ------ Only “LCK”

17
8. Parameters
8.1 Level 1 (User Level)
Process Value
Set Value
Output Limt
Autotuning
Alarm 1 set value
Alarm 2 set value
Set
Set
Set
Set
Set
Alarm 3 set value
PV
SV
Set
()
Heater current display
HBA set value

18
8.2 LEVEL 2 (PID Level)
To enter level 2, press SET key 5 seconds in level 1
8.2.1 Level 2 parameters display /hiding condition
Set
Set
Set
Set
Set
Set
P1≠0
Set
P1=0
Set
Set
Set
Set
Set
Set
Set
Set
Set
P1=0
P2=0
Set
Set
Set
Set
Set
Set
Set
P1=0
P2≠0
Set
Set
Set
Set
Set
Set
Set
P1≠0
P2=0
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
P1≠0
P2≠0
Set
Set
Set
Set
Set
Set
Set
Set
Set
1. Press key 5 seconds to enter level 2.
2. Set LCK to “1111".
3. Press key and key 5 seconds,
to enter level 4 (Set level).
4. Set OUTY to “0"(Single output-P1) .
SET
SET
Set
Single output - P1
1. Press key 5 seconds to enter level 2.
2. Set LCK to “1111".
3. Press key and key 5 seconds,
to enter level 4 (Set level).
4. Set OUTY to “1" (Dual output - P1/P2) .
SET
SET
Dual output - P1/P2

19
8.2.2 Description of parameters
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Set
Proportional band 1
(For output 1)
Range:0.0~200.0%
ON/OFF control if set to 0 (0.0)
Reserved
Auto tuning offset value
Output 1 cycle time
Hysteresis for output 1
ON/OFF control
Proportional band 2
(For output 2)
Integral time 2
(For output 2)
Derivative time 2
(For output 2)
Output 2 Cycle time
Hysteresis for output 2
ON/OFF control
Control gap 1
(For output 1)
Control gap 2
(For output 2)
Function lock
Range:0~3600 seconds
PD control if set to 0
Range:0~900 seconds
PI control if set to 0
Reserved
Range:0~USPL
Range:0~150 seconds
Relay output : 10
Voltage pulse output : 1 , mA output: 0
Range:0~1000
The same with P1
The same with I1
The same with D1
The same with CYT1
The same with HYS1
Set point of output 1 (Heating side)
=SV - GAP1
=SV + GAP2
Return to “P1"
If P2=0.0
Display
Display if output2 is provided
Integral time 1
(For output 1)
Derivative time 1
(For output 1)
If P1=0.0
Display
Levels entering available
LCK Level 1
(User) Level 2
(PID) Level 3
(Input) Level 4
(SET)
Parameters which can be
changed
◎◎◎------ All parameters (default value)
◎◎------ ◎All parameters
◎◎------ ------ All parameters except level 3
◎◎------ ------ Parameters in level 1
◎◎------ ------ “SV” and “LCK”
◎◎------ ------ Only “LCK”
This manual suits for next models
5
Table of contents
Other TCL Controllers manuals
Popular Controllers manuals by other brands

Omron
Omron NT2S-SF123B-EV2 instruction sheet

GE
GE CR1062RL installation instructions

Omron
Omron CJ1M-CPU series Replacement guide

Würth
Würth Proteus-III How-to

Mitsubishi Electric
Mitsubishi Electric CR750-D Series instruction manual

Ingersoll-Rand
Ingersoll-Rand 302 SERIES Installation and operation manual