This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
Side
B
Side
A
Side
BJAPANESE ENGLISH
JY997D14801F
Safety Precaution
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and .
Depending on the circumstances, procedures indicated by may
also cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer
from who you purchased your product.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name Manual No. Description
FX3G/FX3U/FX3UC
Series
User's Manual
- Analog Control
Edition
JY997D16701
MODEL CODE:
09R619
Describes specifications for
analog control and
programming method for FX3G/
FX3U/FX3UC Series PLC.
FX3G/FX3U/FX3UC
Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming
for basic/applied instructions
and devices.
FX3G Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains FX3G Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3U Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains FX3U Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3UC Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains FX3UC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
Applicable standards
FX3U-4AD-TC-ADP units made in June, 2005 or later comply with the EC Directive
(EMC Directive) and UL standards (UL, cUL). Further information can be found in the
following manual.
→ Refer to the FX3G Series Hardware Manual (Manual No. JY997D33401)
→ Refer to the FX3U Series Hardware Manual (Manual No. JY997D18801)
→ Refer to the FX3UC (D, DSS) Series Hardware Manual (Manual No.
JY997D28601)
→ Refer to the FX3UC-32MT-LT-2 Hardware Manual (Manual No. JY997D31601)
Regarding the standards that relate to the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Caution for EC Directive
The analog special adapters have been found to be compliant to the European
standards in the aforesaid manual and directive. However, for the very best per-
formance from what are in fact delicate measuring and controlled output device
Mitsubishi Electric would like to make the following points;
As analog devices are sensitive by nature, their use should be considered care-
fully. For users of pr-oprietary cables (integral with sensors or actuators), these
users should follow those manufacturers installation requirements.
Mitsubishi Electric recommend that shielded cables should be used. If NO other
EMC protection is provided, then users may experience temporary loss or
accuracy between ±10% in very heavy industrial areas.
However, Mitsubishi Electric suggest that if adequate EMC precautions are fol-
lowed for the users complete control system, users should expect accuracy as
specified in this manual.
•Sensitive analog cable should not be laid in the same trunking or cable
conduit as high voltage cabling. Where possible users should run analog
cables separately.
•Good cable shielding should be used. When terminating the shield at Earth
- ensure that no earth loops are accidentally created.
•When reading analog values, EMC accuracy can be improved out by
averaging the readings. This can be achieved either through functions on the
analog special adapters or through a users program in the FX3U(C) Series
PLC main unit.
1. Outline
FX3U-4AD-TC-ADP (hereinafter called TC-ADP) is an analog special adapter for
measuring temperature via four channels of connected Type K or Type J thermocouple
thermometer.
1.1 Incorporated Items
Verify that the following product and items are included in the package:
1.2 External Dimensions, Part Names, and Terminal Layout
[1] DIN rail mounting groove (DIN rail: DIN46277)
[2] Name plate
Manual
This
manual
Product
J-type
L2+
L2-
24+
24-
J-type
L1+
L3-
L4+
L4-
L3+
L1-
[6]
[5] [10]
[7]
[8]
[9]
[3]
[2]
[4]
Weight: Approx. 0.1 kg (0.22 lbs)
Special adapter
connector cover
is removed
[11]
[1]
90(3.55")
98(3.86")
106(4.18")
7(0.28") 74(2.92")
15.5
(0.62")
17.6
(0.7")
15.1
(0.6")
2. Installation
For installation/uninstallation details, refer to the following manuals:
→ Refer to the FX3G Series User's Manual - Hardware Edition.
→ Refer to the FX3U Series User's Manual - Hardware Edition.
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
2.1 Connection to the FX3U Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC main unit and special adapter, and
demount the main unit and special adapter mounted on DIN rail or mounted directly
using screws.
2) Install an expansion board to the main unit.
For the expansion board installation procedure, refer to the following manual:
→ Refer to the FX3U Series User's Manual - Hardware Edition
3) Remove the special adapter connector cover on
the expansion board (fig.A).
When connecting this product to another special
adapter, please replace the 'expansion board' in
the above description with a 'special adapter' and
perform the procedure as indicated.
4)
Slide the special adapter slide lock
(fig.B) of the main unit.
When connecting this product to another special
adapter, please replace the 'main unit' in the
above description with a 'special adapter' and
perform the procedure as indicated.
[3] Special adapter slide lock:
Used to connect additional special adapters onto the left side of this special
adapter.
[4] Special adapters connector cover:
Remove this cover to connect additional special adapters to the left side.
[5] Direct mounting hole:2 holes of φ4.5 (0.18") (mounting screw: M4 screw)
Not used when connecting to FX3UC Series PLC.
[6] POWER LED (green):
Lit while 24V DC power is supplied properly to terminals '24+' and '24-'.
[7] Terminal block (European type):
Connect thermocouple sensor input, Type K or J changeover input, and 24V DC
power supply.
[8] Special adapter connector:
Used to connect this special adapter to PLC main unit or special adapter.
[9] DIN rail mounting hook
[10] Special adapter fixing hook
[11] Special adapter connector:
Used to connect communication or analog special adapters to the left side of the
TC-ADP.
INSTALLATION
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
•Use the product within the generic environment specifications described in PLC
main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl2, H2S, SO2, or NO2), flammable gas, vibration or
impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•When drilling screw holes or wiring, make sure cutting or wire debris does not
enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•Connect special adapter securely to their designated connectors.
Loose connections may cause malfunctions.
RUN
STOP
FX
3U
-48MR/ES
-48MR/ES
FX
3U
-48M
3)
4)
B
B
A
4)
5)
Connect the
special adapter
(fig.C) to the
main unit as
shown on the
right
.
6) Slide back the
special adapter
slide lock (fig.B)
of the main unit
to fix the special
adapter (fig.C).
Connection precautions
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of a
communication or analog special adapter.
2.2 Connection to the FX3UC (D, DSS) Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from
the DIN rail.
2) Remove the special adapter connector
cover (fig.A).
3) Slide the special adapter slide lock (fig.B)
of the main unit.
When connecting this product to another
special adapter, please replace the 'main
unit' in the above description with a 'special
adapter' and perform the procedure as
indicated.
4) Connect the
special
adapter (fig.C)
to the main
unit as shown
on the right.
5) Slide back the
special
adapter slide
lock (fig.B) of
the main unit
to fix the
special
adapter (fig.C).
2.3 Connection to the FX3UC-32MT-LT(-2) Series PLC
→ For details, refer to the FX3UC Series User's Manual - Hardware Edition.
RUN
STOP
FX
3U
-48MR/ES
FX
FX
3U
-48M
-48M
FX
3U
-**-**
-***
POWER
FX
3U
-48M
6)
C
B
B
5)
5)
5)
6
)
4)
3)
B
A
B
3)
2)
POWER
FX
3U
-***-***
5)
C
B
B
4)
4)
4)
5)
2.4 Connection to the FX3G Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from
the DIN rail.
2) Install a connector conversion adapter to the main unit.
For the connector conversion adapter installation procedure, refer to the
following manual:
→ Refer to the FX3G Series User's Manual - Hardware Edition
3) Remove the special adapter connector
cover when connecting this product to
another special adapter.
Removal of the special adapter
connector cover is not required when
connecting this product to the
connector conversion adapter.
4)
Slide the special adapter slide lock
(fig.A) of the connector conversion
adapter.
When connecting this product to
another special adapter, please replace
the 'connector conversion adapter' in
the above description with a 'special
adapter' and perform the procedure as
indicated.
5) Connect the
special adapter
(fig.B) to the
connector
conversion
adapter as
shown on the
right.
6) Slide back the
special adapter
slide lock (fig.A)
of the connector
conversion
adapter to fix the
special adapter
(fig.B).
3. Wiring
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
•Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical
systems.
•Make sure to properly wire to the European terminal board in accordance
with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or
damage to the product.
- The disposal size of the cable end should be 9mm (0.35").
- Tightening torque should be between 0.22 and 0.25N•m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
•Make sure to properly wire to the FX3G/FX3U/FX3UC Series PLC in
accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or
damage to the product.
- The disposal size of the cable end should follow the dimensions
described in this manual.
- Tightening torque should follow the specifications in this manual.
B
B
A
4)
4)
4)
3)
A
4)
4)
A
3)
A
6)
A
B
6)
5)
5)
5)
3.1 Applicable cable and terminal tightening torque
3.1.1 Type terminal block (European type)
1) Wire size
- The power supply wiring and the Type K/J changeover input wiring should use
22-20 AWG wire.
- Thermocouple wiring should use the compensating lead wire suitable for the
type of thermocouple.
→ For details of compensating lead wire, Refer to Section 3.3.
2) Applicable cable
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it, or
strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
When using a stick terminal with insulating sleeve, choose a wire with proper cable
sheath referring to the above outside dimensions, or otherwise, the wire cannot be
inserted easily. The tightening torque must be 0.22 to 0.25N•m.
3.2 Power Supply Wiring
→ For the power supply wiring, refer to the FX3G / FX3U / FX3UC Series
User’s Manual - Analog Control Edition
3.3 Selection of thermocouple
→ For the terminal configuration, refer to Section 1.2
Precautions on thermocouple wiring
•Thermocouple type
- There are 2 types of thermocouples: Type K and Type J. Select the desired type.
However, be sure to connect the same type of thermocouple to all the channels.
- Use insulated thermocouple types.
•Compensating lead wire
To connect the
thermocouple, use one of
the right types of
compensating lead wires.
The compensating lead
wire indicates the
temperature value of approximately 0.12°C higher than that of the wire resistor
(10Ω). Temperature value should be used in consideration of this point.
If the compensating lead wire is very long, the wire may be easily affected by noise,
etc. It is, therefore, recommended that the length of the compensating lead wire
should be 100 m (328' 1") or less.
Example of thermocouple wiring
*1 When using the Type J thermocouple, short-circuit the 'Type J' terminals and turn
the special auxiliary relay (Type K/J mode changeover) ON.
→ For details of auxiliary relays, refer to the FX3G / FX3U / FX3UC Series
User's Manual - Analog Control Edition
*2 24V DC service power supply of the FX3G/FX3U Series PLC can also be used.
Type Wire size
Single-wire 0.3mm2to 0.5mm2(AWG22 to 20)
2-wire 2 pieces of 0.3mm2(AWG22)
Manufacturer Model Pressure bonding tool
Phoenix Contact Co., Ltd. AI 0.5-8WH CRIMPFOX ZA 3
(or CRIMPFOX UD 6)
9mm
(0.35")
- Strand wire/single wire
8mm
(0.31")
Contact area
(Crimping area)
14mm(0.55")
2.6mm(0.1")
Insulation sleeve
- Stick terminal with insulating sleeve
Thermocouple Type of compensating lead wire
Type K KX,KCA,KCB,KCC
Type J JX
3k
Ω
TC-ADP
L +
L -
24+
24-
Compensating lead
wire (Shielded)
Terminal
block
24V DC
External power
supply wiring
J-type
J-type
Thermocouple
*1
Thermocouple Wiring
Using Type J
Temperature
compensation circuit
*2
ch
ch
Grounding
(Ground resistance: 100
Ω
or less)
L +, L -, ch : represents the channel number.
L +
L -
Temperature
compensation circuit
3k
Ω
+5V
3.4 Grounding
Grounding should be performed as stated below.
•The grounding resistance should be 100Ωor less.
•Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
→ For details, refer to the FX3G Series User's
Manual - Hardware Edition.
→ For details, refer to the FX3U Series User's
Manual - Hardware Edition.
→ For details, refer to the FX3UC Series User's
Manual - Hardware Edition.
•The grounding wire size should be AWG 22-20 (0.3-0.5 mm2).
•The grounding point should be close to the PLC, and all grounding wire should be
as short as possible.
4. Specifications
4.1 Applicable PLC
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
4.2 General Specifications
For the general specifications, refer to the manual of the PLC main unit.
The items other than the following are equivalent to those of the PLC main unit.
4.3 Power Supply Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric distributor.
•Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
•Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•The product is a precision instrument. During transportation, avoid any impacts.
Failure to do so may cause failures in the product. After transportation, verify the
operations of the product.
Model name Applicability
FX3U Series PLC Ver. 2.20 or later (from first production)
FX3UC Series PLC Ver. 1.30 or later (from the production manufactured in August,
2004 with SER No. 48****)
FX3G Series PLC Ver. 1.00 or later (from first production)
Item Specification
Dielectric withstand
voltage 500V AC for one minute Conforming to JEM-1021
Between all terminals and
ground terminal of PLC
main unit
Insulation resistance 5MΩor more by 500V DC megger
Item Specification
A/D conversion
circuit driving power
24V DC +20%/-15%, 45mA for 24V DC
Connect a 24V DC power supply to the terminal block.
Interface driving
power
5V DC, 15mA
5V DC power is supplied from the internal power supply of
main unit.
PLC Another
equipment
PLC Another
equipment
PLC Another
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
4.4 Performance Specifications
Item
Specifications
Centigrade (°C) Fahrenheit (°F)
Input signal Thermocouple type K or J
JIS C 1602-1995
Rated
temperature
range
Type K -100°C to +1000°C Type K -148°F to +1832°F
Type J -100°C to +600°C Type J -148°F to +1112°F
Digital output
Type K -1000 to +10000 Type K -1480 to +18320
Type J -1000 to +6000 Type J -1480 to +11120
Resolution
Type K 0.4°C Type K 0.72°F
Type J 0.3°C Type J 0.54°F
Total accuracy ±(0.5% full scale +1°C)
A/D conversion
time
•FX3U/FX3UC Series PLC: 200µs
(The data will be updated at every scan time of the PLC.)
•FX3G Series PLC: 250µs
(The data will be updated at every scan time of the PLC.)
Input
characteristics
Insulation
method
•The photocoupler is adopted to insulate the analog input
area from the PLC.
•The DC-DC converter is adopted to insulate the power
supply line from the analog input area.
•A channels are not insulated from each other.
Occupied
points
0 point (This number is not related to the maximum number of
input/output points of the PLC.)
0
+600
°
C
+6000
-100
°
C
-1000
+610°C
Type J
+6100
-1100
Approx.
-110°C
0
+1000
°
C
+10000
-100
°
C
-1000
-110°C
+1010°C
Type K
+10100
-1100
0
+1832
°
F
+18320
-148
°
F
-1480
Approx.
-166
°
F
Approx.+1850
°
F
Type K
+18500
-1660
0
+1112
°
F
+11120
-148
°
F
-1480
Approx.+1130
°
F
Type J
+11300
-1660
Approx.
-166
°
F
FX3U-4AD-TC-ADP
USER'S MANUAL
This manual describes the part names, dimensions, mounting, and
specifications of the product. Before use, read this manual and the manuals of
all relevant products fully to acquire proficiency in handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective September 2008
Specifications are subject to change without notice.
©2005 Mitsubishi Electric Corporation
Manual Number JY997D14801
Revision F
Date September 2008
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
Side
B
Side
A
Side
BJAPANESE ENGLISH
JY997D14801F
Safety Precaution
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and .
Depending on the circumstances, procedures indicated by may
also cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer
from who you purchased your product.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name Manual No. Description
FX3G/FX3U/FX3UC
Series
User's Manual
- Analog Control
Edition
JY997D16701
MODEL CODE:
09R619
Describes specifications for
analog control and
programming method for FX3G/
FX3U/FX3UC Series PLC.
FX3G/FX3U/FX3UC
Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming
for basic/applied instructions
and devices.
FX3G Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains FX3G Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3U Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains FX3U Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3UC Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains FX3UC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
Applicable standards
FX3U-4AD-TC-ADP units made in June, 2005 or later comply with the EC Directive
(EMC Directive) and UL standards (UL, cUL). Further information can be found in the
following manual.
→ Refer to the FX3G Series Hardware Manual (Manual No. JY997D33401)
→ Refer to the FX3U Series Hardware Manual (Manual No. JY997D18801)
→ Refer to the FX3UC (D, DSS) Series Hardware Manual (Manual No.
JY997D28601)
→ Refer to the FX3UC-32MT-LT-2 Hardware Manual (Manual No. JY997D31601)
Regarding the standards that relate to the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Caution for EC Directive
The analog special adapters have been found to be compliant to the European
standards in the aforesaid manual and directive. However, for the very best per-
formance from what are in fact delicate measuring and controlled output device
Mitsubishi Electric would like to make the following points;
As analog devices are sensitive by nature, their use should be considered care-
fully. For users of pr-oprietary cables (integral with sensors or actuators), these
users should follow those manufacturers installation requirements.
Mitsubishi Electric recommend that shielded cables should be used. If NO other
EMC protection is provided, then users may experience temporary loss or
accuracy between ±10% in very heavy industrial areas.
However, Mitsubishi Electric suggest that if adequate EMC precautions are fol-
lowed for the users complete control system, users should expect accuracy as
specified in this manual.
•Sensitive analog cable should not be laid in the same trunking or cable
conduit as high voltage cabling. Where possible users should run analog
cables separately.
•Good cable shielding should be used. When terminating the shield at Earth
- ensure that no earth loops are accidentally created.
•When reading analog values, EMC accuracy can be improved out by
averaging the readings. This can be achieved either through functions on the
analog special adapters or through a users program in the FX3U(C) Series
PLC main unit.
1. Outline
FX3U-4AD-TC-ADP (hereinafter called TC-ADP) is an analog special adapter for
measuring temperature via four channels of connected Type K or Type J thermocouple
thermometer.
1.1 Incorporated Items
Verify that the following product and items are included in the package:
1.2 External Dimensions, Part Names, and Terminal Layout
[1] DIN rail mounting groove (DIN rail: DIN46277)
[2] Name plate
Manual
This
manual
Product
J-type
L2+
L2-
24+
24-
J-type
L1+
L3-
L4+
L4-
L3+
L1-
[6]
[5] [10]
[7]
[8]
[9]
[3]
[2]
[4]
Weight: Approx. 0.1 kg (0.22 lbs)
Special adapter
connector cover
is removed
[11]
[1]
90(3.55")
98(3.86")
106(4.18")
7(0.28") 74(2.92")
15.5
(0.62")
17.6
(0.7")
15.1
(0.6")
2. Installation
For installation/uninstallation details, refer to the following manuals:
→ Refer to the FX3G Series User's Manual - Hardware Edition.
→ Refer to the FX3U Series User's Manual - Hardware Edition.
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
2.1 Connection to the FX3U Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC main unit and special adapter, and
demount the main unit and special adapter mounted on DIN rail or mounted directly
using screws.
2) Install an expansion board to the main unit.
For the expansion board installation procedure, refer to the following manual:
→ Refer to the FX3U Series User's Manual - Hardware Edition
3) Remove the special adapter connector cover on
the expansion board (fig.A).
When connecting this product to another special
adapter, please replace the 'expansion board' in
the above description with a 'special adapter' and
perform the procedure as indicated.
4)
Slide the special adapter slide lock
(fig.B) of the main unit.
When connecting this product to another special
adapter, please replace the 'main unit' in the
above description with a 'special adapter' and
perform the procedure as indicated.
[3] Special adapter slide lock:
Used to connect additional special adapters onto the left side of this special
adapter.
[4] Special adapters connector cover:
Remove this cover to connect additional special adapters to the left side.
[5] Direct mounting hole:2 holes of φ4.5 (0.18") (mounting screw: M4 screw)
Not used when connecting to FX3UC Series PLC.
[6] POWER LED (green):
Lit while 24V DC power is supplied properly to terminals '24+' and '24-'.
[7] Terminal block (European type):
Connect thermocouple sensor input, Type K or J changeover input, and 24V DC
power supply.
[8] Special adapter connector:
Used to connect this special adapter to PLC main unit or special adapter.
[9] DIN rail mounting hook
[10] Special adapter fixing hook
[11] Special adapter connector:
Used to connect communication or analog special adapters to the left side of the
TC-ADP.
INSTALLATION
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
•Use the product within the generic environment specifications described in PLC
main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl2, H2S, SO2, or NO2), flammable gas, vibration or
impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•When drilling screw holes or wiring, make sure cutting or wire debris does not
enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•Connect special adapter securely to their designated connectors.
Loose connections may cause malfunctions.
RUN
STOP
FX
3U
-48MR/ES
-48MR/ES
FX
3U
-48M
3)
4)
B
B
A
4)
5)
Connect the
special adapter
(fig.C) to the
main unit as
shown on the
right
.
6) Slide back the
special adapter
slide lock (fig.B)
of the main unit
to fix the special
adapter (fig.C).
Connection precautions
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of a
communication or analog special adapter.
2.2 Connection to the FX3UC (D, DSS) Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from
the DIN rail.
2) Remove the special adapter connector
cover (fig.A).
3) Slide the special adapter slide lock (fig.B)
of the main unit.
When connecting this product to another
special adapter, please replace the 'main
unit' in the above description with a 'special
adapter' and perform the procedure as
indicated.
4) Connect the
special
adapter (fig.C)
to the main
unit as shown
on the right.
5) Slide back the
special
adapter slide
lock (fig.B) of
the main unit
to fix the
special
adapter (fig.C).
2.3 Connection to the FX3UC-32MT-LT(-2) Series PLC
→ For details, refer to the FX3UC Series User's Manual - Hardware Edition.
RUN
STOP
FX
3U
-48MR/ES
FX
FX
3U
-48M
-48M
FX
3U
-**-**
-***
POWER
FX
3U
-48M
6)
C
B
B
5)
5)
5)
6
)
4)
3)
B
A
B
3)
2)
POWER
FX
3U
-***-***
5)
C
B
B
4)
4)
4)
5)
2.4 Connection to the FX3G Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from
the DIN rail.
2) Install a connector conversion adapter to the main unit.
For the connector conversion adapter installation procedure, refer to the
following manual:
→ Refer to the FX3G Series User's Manual - Hardware Edition
3) Remove the special adapter connector
cover when connecting this product to
another special adapter.
Removal of the special adapter
connector cover is not required when
connecting this product to the
connector conversion adapter.
4)
Slide the special adapter slide lock
(fig.A) of the connector conversion
adapter.
When connecting this product to
another special adapter, please replace
the 'connector conversion adapter' in
the above description with a 'special
adapter' and perform the procedure as
indicated.
5) Connect the
special adapter
(fig.B) to the
connector
conversion
adapter as
shown on the
right.
6) Slide back the
special adapter
slide lock (fig.A)
of the connector
conversion
adapter to fix the
special adapter
(fig.B).
3. Wiring
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
•Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical
systems.
•Make sure to properly wire to the European terminal board in accordance
with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or
damage to the product.
- The disposal size of the cable end should be 9mm (0.35").
- Tightening torque should be between 0.22 and 0.25N•m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
•Make sure to properly wire to the FX3G/FX3U/FX3UC Series PLC in
accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or
damage to the product.
- The disposal size of the cable end should follow the dimensions
described in this manual.
- Tightening torque should follow the specifications in this manual.
B
B
A
4)
4)
4)
3)
A
4)
4)
A
3)
A
6)
A
B
6)
5)
5)
5)
3.1 Applicable cable and terminal tightening torque
3.1.1 Type terminal block (European type)
1) Wire size
- The power supply wiring and the Type K/J changeover input wiring should use
22-20 AWG wire.
- Thermocouple wiring should use the compensating lead wire suitable for the
type of thermocouple.
→ For details of compensating lead wire, Refer to Section 3.3.
2) Applicable cable
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it, or
strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
When using a stick terminal with insulating sleeve, choose a wire with proper cable
sheath referring to the above outside dimensions, or otherwise, the wire cannot be
inserted easily. The tightening torque must be 0.22 to 0.25N•m.
3.2 Power Supply Wiring
→ For the power supply wiring, refer to the FX3G / FX3U / FX3UC Series
User’s Manual - Analog Control Edition
3.3 Selection of thermocouple
→ For the terminal configuration, refer to Section 1.2
Precautions on thermocouple wiring
•Thermocouple type
- There are 2 types of thermocouples: Type K and Type J. Select the desired type.
However, be sure to connect the same type of thermocouple to all the channels.
- Use insulated thermocouple types.
•Compensating lead wire
To connect the
thermocouple, use one of
the right types of
compensating lead wires.
The compensating lead
wire indicates the
temperature value of approximately 0.12°C higher than that of the wire resistor
(10Ω). Temperature value should be used in consideration of this point.
If the compensating lead wire is very long, the wire may be easily affected by noise,
etc. It is, therefore, recommended that the length of the compensating lead wire
should be 100 m (328' 1") or less.
Example of thermocouple wiring
*1 When using the Type J thermocouple, short-circuit the 'Type J' terminals and turn
the special auxiliary relay (Type K/J mode changeover) ON.
→ For details of auxiliary relays, refer to the FX3G / FX3U / FX3UC Series
User's Manual - Analog Control Edition
*2 24V DC service power supply of the FX3G/FX3U Series PLC can also be used.
Type Wire size
Single-wire 0.3mm2to 0.5mm2(AWG22 to 20)
2-wire 2 pieces of 0.3mm2(AWG22)
Manufacturer Model Pressure bonding tool
Phoenix Contact Co., Ltd. AI 0.5-8WH CRIMPFOX ZA 3
(or CRIMPFOX UD 6)
9mm
(0.35")
- Strand wire/single wire
8mm
(0.31")
Contact area
(Crimping area)
14mm(0.55")
2.6mm(0.1")
Insulation sleeve
- Stick terminal with insulating sleeve
Thermocouple Type of compensating lead wire
Type K KX,KCA,KCB,KCC
Type J JX
3k
Ω
TC-ADP
L +
L -
24+
24-
Compensating lead
wire (Shielded)
Terminal
block
24V DC
External power
supply wiring
J-type
J-type
Thermocouple
*1
Thermocouple Wiring
Using Type J
Temperature
compensation circuit
*2
ch
ch
Grounding
(Ground resistance: 100
Ω
or less)
L +, L -, ch : represents the channel number.
L +
L -
Temperature
compensation circuit
3k
Ω
+5V
3.4 Grounding
Grounding should be performed as stated below.
•The grounding resistance should be 100Ωor less.
•Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
→ For details, refer to the FX3G Series User's
Manual - Hardware Edition.
→ For details, refer to the FX3U Series User's
Manual - Hardware Edition.
→ For details, refer to the FX3UC Series User's
Manual - Hardware Edition.
•The grounding wire size should be AWG 22-20 (0.3-0.5 mm2).
•The grounding point should be close to the PLC, and all grounding wire should be
as short as possible.
4. Specifications
4.1 Applicable PLC
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
4.2 General Specifications
For the general specifications, refer to the manual of the PLC main unit.
The items other than the following are equivalent to those of the PLC main unit.
4.3 Power Supply Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric distributor.
•Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
•Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•The product is a precision instrument. During transportation, avoid any impacts.
Failure to do so may cause failures in the product. After transportation, verify the
operations of the product.
Model name Applicability
FX3U Series PLC Ver. 2.20 or later (from first production)
FX3UC Series PLC Ver. 1.30 or later (from the production manufactured in August,
2004 with SER No. 48****)
FX3G Series PLC Ver. 1.00 or later (from first production)
Item Specification
Dielectric withstand
voltage 500V AC for one minute Conforming to JEM-1021
Between all terminals and
ground terminal of PLC
main unit
Insulation resistance 5MΩor more by 500V DC megger
Item Specification
A/D conversion
circuit driving power
24V DC +20%/-15%, 45mA for 24V DC
Connect a 24V DC power supply to the terminal block.
Interface driving
power
5V DC, 15mA
5V DC power is supplied from the internal power supply of
main unit.
PLC Another
equipment
PLC Another
equipment
PLC Another
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
4.4 Performance Specifications
Item
Specifications
Centigrade (°C) Fahrenheit (°F)
Input signal Thermocouple type K or J
JIS C 1602-1995
Rated
temperature
range
Type K -100°C to +1000°C Type K -148°F to +1832°F
Type J -100°C to +600°C Type J -148°F to +1112°F
Digital output
Type K -1000 to +10000 Type K -1480 to +18320
Type J -1000 to +6000 Type J -1480 to +11120
Resolution
Type K 0.4°C Type K 0.72°F
Type J 0.3°C Type J 0.54°F
Total accuracy ±(0.5% full scale +1°C)
A/D conversion
time
•FX3U/FX3UC Series PLC: 200µs
(The data will be updated at every scan time of the PLC.)
•FX3G Series PLC: 250µs
(The data will be updated at every scan time of the PLC.)
Input
characteristics
Insulation
method
•The photocoupler is adopted to insulate the analog input
area from the PLC.
•The DC-DC converter is adopted to insulate the power
supply line from the analog input area.
•A channels are not insulated from each other.
Occupied
points
0 point (This number is not related to the maximum number of
input/output points of the PLC.)
0
+600
°
C
+6000
-100
°
C
-1000
+610°C
Type J
+6100
-1100
Approx.
-110°C
0
+1000
°
C
+10000
-100
°
C
-1000
-110°C
+1010°C
Type K
+10100
-1100
0
+1832
°
F
+18320
-148
°
F
-1480
Approx.
-166
°
F
Approx.+1850
°
F
Type K
+18500
-1660
0
+1112
°
F
+11120
-148
°
F
-1480
Approx.+1130
°
F
Type J
+11300
-1660
Approx.
-166
°
F
FX3U-4AD-TC-ADP
USER'S MANUAL
This manual describes the part names, dimensions, mounting, and
specifications of the product. Before use, read this manual and the manuals of
all relevant products fully to acquire proficiency in handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective September 2008
Specifications are subject to change without notice.
©2005 Mitsubishi Electric Corporation
Manual Number JY997D14801
Revision F
Date September 2008
This manual confers no industrial property rights or any rights of any other kind,
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be
held responsible for any problems involving industrial property rights which may
occur as a result of using the contents noted in this manual.
Warranty
Mitsubishi will not be held liable for damage caused by factors found not to be
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the
Mitsubishi products; damage, secondary damage, accident compensation
caused by special factors unpredictable by Mitsubishi; damages to products
other than Mitsubishi products; and to other duties.
For safe use
This product has been manufactured as a general-purpose part for general
industries, and has not been designed or manufactured to be incorporated in
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric
power, aerospace, medicine or passenger movement vehicles, consult with
Mitsubishi Electric.
This product has been manufactured under strict quality control. However
when installing the product where major accidents or losses could occur if the
product fails, install appropriate backup or failsafe functions in the system.
•
•
•
HEAD OFFICE
HIMEJI WORKS
: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310,
JAPAN
: 840, CHIYODA CHO, HIMEJI, JAPAN
Side
B
Side
A
Side
BJAPANESE ENGLISH
JY997D14801F
Safety Precaution
(Read these precautions before use.)
This manual classifies the safety precautions into two categories:
and .
Depending on the circumstances, procedures indicated by may
also cause severe injury.
It is important to follow all precautions for personal safety.
Associated Manuals
How to obtain manuals
For product manuals or documents, consult with the Mitsubishi Electric dealer
from who you purchased your product.
Indicates that incorrect handling may cause hazardous
conditions, resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous
conditions, resulting in medium or slight personal injury
or physical damage.
Manual name Manual No. Description
FX3G/FX3U/FX3UC
Series
User's Manual
- Analog Control
Edition
JY997D16701
MODEL CODE:
09R619
Describes specifications for
analog control and
programming method for FX3G/
FX3U/FX3UC Series PLC.
FX3G/FX3U/FX3UC
Series
Programming Manual
- Basic & Applied
Instruction Edition
JY997D16601
MODEL CODE:
09R517
Describes PLC programming
for basic/applied instructions
and devices.
FX3G Series
User’s Manual
- Hardware Edition
JY997D31301
MODEL CODE:
09R521
Explains FX3G Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3U Series
User’s Manual
- Hardware Edition
JY997D16501
MODEL CODE:
09R516
Explains FX3U Series PLC
specifications for I/O, wiring,
installation, and maintenance.
FX3UC Series
User’s Manual
- Hardware Edition
JY997D28701
MODEL CODE:
09R519
Explains FX3UC Series PLC
specifications for I/O, wiring,
installation, and maintenance.
Applicable standards
FX3U-4AD-TC-ADP units made in June, 2005 or later comply with the EC Directive
(EMC Directive) and UL standards (UL, cUL). Further information can be found in the
following manual.
→ Refer to the FX3G Series Hardware Manual (Manual No. JY997D33401)
→ Refer to the FX3U Series Hardware Manual (Manual No. JY997D18801)
→ Refer to the FX3UC (D, DSS) Series Hardware Manual (Manual No.
JY997D28601)
→ Refer to the FX3UC-32MT-LT-2 Hardware Manual (Manual No. JY997D31601)
Regarding the standards that relate to the main unit, please refer to either the FX
series product catalog or consult with your nearest Mitsubishi product provider.
Caution for EC Directive
The analog special adapters have been found to be compliant to the European
standards in the aforesaid manual and directive. However, for the very best per-
formance from what are in fact delicate measuring and controlled output device
Mitsubishi Electric would like to make the following points;
As analog devices are sensitive by nature, their use should be considered care-
fully. For users of pr-oprietary cables (integral with sensors or actuators), these
users should follow those manufacturers installation requirements.
Mitsubishi Electric recommend that shielded cables should be used. If NO other
EMC protection is provided, then users may experience temporary loss or
accuracy between ±10% in very heavy industrial areas.
However, Mitsubishi Electric suggest that if adequate EMC precautions are fol-
lowed for the users complete control system, users should expect accuracy as
specified in this manual.
•Sensitive analog cable should not be laid in the same trunking or cable
conduit as high voltage cabling. Where possible users should run analog
cables separately.
•Good cable shielding should be used. When terminating the shield at Earth
- ensure that no earth loops are accidentally created.
•When reading analog values, EMC accuracy can be improved out by
averaging the readings. This can be achieved either through functions on the
analog special adapters or through a users program in the FX3U(C) Series
PLC main unit.
1. Outline
FX3U-4AD-TC-ADP (hereinafter called TC-ADP) is an analog special adapter for
measuring temperature via four channels of connected Type K or Type J thermocouple
thermometer.
1.1 Incorporated Items
Verify that the following product and items are included in the package:
1.2 External Dimensions, Part Names, and Terminal Layout
[1] DIN rail mounting groove (DIN rail: DIN46277)
[2] Name plate
Manual
This
manual
Product
J-type
L2+
L2-
24+
24-
J-type
L1+
L3-
L4+
L4-
L3+
L1-
[6]
[5] [10]
[7]
[8]
[9]
[3]
[2]
[4]
Weight: Approx. 0.1 kg (0.22 lbs)
Special adapter
connector cover
is removed
[11]
[1]
90(3.55")
98(3.86")
106(4.18")
7(0.28") 74(2.92")
15.5
(0.62")
17.6
(0.7")
15.1
(0.6")
2. Installation
For installation/uninstallation details, refer to the following manuals:
→ Refer to the FX3G Series User's Manual - Hardware Edition.
→ Refer to the FX3U Series User's Manual - Hardware Edition.
→ Refer to the FX3UC Series User's Manual - Hardware Edition.
2.1 Connection to the FX3U Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC main unit and special adapter, and
demount the main unit and special adapter mounted on DIN rail or mounted directly
using screws.
2) Install an expansion board to the main unit.
For the expansion board installation procedure, refer to the following manual:
→ Refer to the FX3U Series User's Manual - Hardware Edition
3) Remove the special adapter connector cover on
the expansion board (fig.A).
When connecting this product to another special
adapter, please replace the 'expansion board' in
the above description with a 'special adapter' and
perform the procedure as indicated.
4)
Slide the special adapter slide lock
(fig.B) of the main unit.
When connecting this product to another special
adapter, please replace the 'main unit' in the
above description with a 'special adapter' and
perform the procedure as indicated.
[3] Special adapter slide lock:
Used to connect additional special adapters onto the left side of this special
adapter.
[4] Special adapters connector cover:
Remove this cover to connect additional special adapters to the left side.
[5] Direct mounting hole:2 holes of φ4.5 (0.18") (mounting screw: M4 screw)
Not used when connecting to FX3UC Series PLC.
[6] POWER LED (green):
Lit while 24V DC power is supplied properly to terminals '24+' and '24-'.
[7] Terminal block (European type):
Connect thermocouple sensor input, Type K or J changeover input, and 24V DC
power supply.
[8] Special adapter connector:
Used to connect this special adapter to PLC main unit or special adapter.
[9] DIN rail mounting hook
[10] Special adapter fixing hook
[11] Special adapter connector:
Used to connect communication or analog special adapters to the left side of the
TC-ADP.
INSTALLATION
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before attempting
installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
INSTALLATION
PRECAUTIONS
•Use the product within the generic environment specifications described in PLC
main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive dusts,
corrosive gas (salt air, Cl2, H2S, SO2, or NO2), flammable gas, vibration or
impacts, or expose it to high temperature, condensation, or rain and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,
deterioration or damage may occur.
•When drilling screw holes or wiring, make sure cutting or wire debris does not
enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
•Do not touch the conductive parts of the product directly.
Doing so may cause device failures or malfunctions.
•Connect special adapter securely to their designated connectors.
Loose connections may cause malfunctions.
RUN
STOP
FX
3U
-48MR/ES
-48MR/ES
FX
3U
-48M
3)
4)
B
B
A
4)
5)
Connect the
special adapter
(fig.C) to the
main unit as
shown on the
right
.
6) Slide back the
special adapter
slide lock (fig.B)
of the main unit
to fix the special
adapter (fig.C).
Connection precautions
Connect all the high-speed I/O special adapters before connecting other
special adapters when they are used in combination.
Do not connect a high-speed I/O special adapter on the left side of a
communication or analog special adapter.
2.2 Connection to the FX3UC (D, DSS) Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from
the DIN rail.
2) Remove the special adapter connector
cover (fig.A).
3) Slide the special adapter slide lock (fig.B)
of the main unit.
When connecting this product to another
special adapter, please replace the 'main
unit' in the above description with a 'special
adapter' and perform the procedure as
indicated.
4) Connect the
special
adapter (fig.C)
to the main
unit as shown
on the right.
5) Slide back the
special
adapter slide
lock (fig.B) of
the main unit
to fix the
special
adapter (fig.C).
2.3 Connection to the FX3UC-32MT-LT(-2) Series PLC
→ For details, refer to the FX3UC Series User's Manual - Hardware Edition.
RUN
STOP
FX
3U
-48MR/ES
FX
FX
3U
-48M
-48M
FX
3U
-**-**
-***
POWER
FX
3U
-48M
6)
C
B
B
5)
5)
5)
6
)
4)
3)
B
A
B
3)
2)
POWER
FX
3U
-***-***
5)
C
B
B
4)
4)
4)
5)
2.4 Connection to the FX3G Series PLC
Procedure
1) Turn off the power.
Disconnect all the cables connected to the PLC, and demount the PLC from
the DIN rail.
2) Install a connector conversion adapter to the main unit.
For the connector conversion adapter installation procedure, refer to the
following manual:
→ Refer to the FX3G Series User's Manual - Hardware Edition
3) Remove the special adapter connector
cover when connecting this product to
another special adapter.
Removal of the special adapter
connector cover is not required when
connecting this product to the
connector conversion adapter.
4)
Slide the special adapter slide lock
(fig.A) of the connector conversion
adapter.
When connecting this product to
another special adapter, please replace
the 'connector conversion adapter' in
the above description with a 'special
adapter' and perform the procedure as
indicated.
5) Connect the
special adapter
(fig.B) to the
connector
conversion
adapter as
shown on the
right.
6) Slide back the
special adapter
slide lock (fig.A)
of the connector
conversion
adapter to fix the
special adapter
(fig.B).
3. Wiring
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
WIRING
PRECAUTIONS
•Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.
•Make sure to observe the following precautions in order to prevent any
damage to the machinery or accidents due to abnormal data written to the
PLC under the influence of noise:
1) Do not bundle the main circuit line together with or lay it close to the main
circuit, high-voltage line or load line.
otherwise, noise disturbance and/or surge induction are likely to take
place. As a guideline, lay the control line at least 100mm (3.94") or more
away from the main circuit or high-voltage lines.
2) Ground the shield wire or shield of the shielded cable at one point on the
PLC. However, do not use common grounding with heavy electrical
systems.
•Make sure to properly wire to the European terminal board in accordance
with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or
damage to the product.
- The disposal size of the cable end should be 9mm (0.35").
- Tightening torque should be between 0.22 and 0.25N•m.
- Twist the end of strand wire and make sure that there are no loose wires.
- Do not solder-plate the electric wire ends.
- Do not connect more than the specified number of wires or electric wires
of unspecified size.
- Affix the electric wires so that neither the terminal block nor the connected
parts are directly stressed.
•Make sure to properly wire to the FX3G/FX3U/FX3UC Series PLC in
accordance with the following precautions.
Failure to do so may cause electric shock, a short-circuit, wire breakage, or
damage to the product.
- The disposal size of the cable end should follow the dimensions
described in this manual.
- Tightening torque should follow the specifications in this manual.
B
B
A
4)
4)
4)
3)
A
4)
4)
A
3)
A
6)
A
B
6)
5)
5)
5)
3.1 Applicable cable and terminal tightening torque
3.1.1 Type terminal block (European type)
1) Wire size
- The power supply wiring and the Type K/J changeover input wiring should use
22-20 AWG wire.
- Thermocouple wiring should use the compensating lead wire suitable for the
type of thermocouple.
→ For details of compensating lead wire, Refer to Section 3.3.
2) Applicable cable
3) Termination of cable end
Strip the coating of strand wire and twist the cable core before connecting it, or
strip the coating of single wire before connecting it.
An alternative connection is to use a ferrule with insulating sleeve.
When using a stick terminal with insulating sleeve, choose a wire with proper cable
sheath referring to the above outside dimensions, or otherwise, the wire cannot be
inserted easily. The tightening torque must be 0.22 to 0.25N•m.
3.2 Power Supply Wiring
→ For the power supply wiring, refer to the FX3G / FX3U / FX3UC Series
User’s Manual - Analog Control Edition
3.3 Selection of thermocouple
→ For the terminal configuration, refer to Section 1.2
Precautions on thermocouple wiring
•Thermocouple type
- There are 2 types of thermocouples: Type K and Type J. Select the desired type.
However, be sure to connect the same type of thermocouple to all the channels.
- Use insulated thermocouple types.
•Compensating lead wire
To connect the
thermocouple, use one of
the right types of
compensating lead wires.
The compensating lead
wire indicates the
temperature value of approximately 0.12°C higher than that of the wire resistor
(10Ω). Temperature value should be used in consideration of this point.
If the compensating lead wire is very long, the wire may be easily affected by noise,
etc. It is, therefore, recommended that the length of the compensating lead wire
should be 100 m (328' 1") or less.
Example of thermocouple wiring
*1 When using the Type J thermocouple, short-circuit the 'Type J' terminals and turn
the special auxiliary relay (Type K/J mode changeover) ON.
→ For details of auxiliary relays, refer to the FX3G / FX3U / FX3UC Series
User's Manual - Analog Control Edition
*2 24V DC service power supply of the FX3G/FX3U Series PLC can also be used.
Type Wire size
Single-wire 0.3mm2to 0.5mm2(AWG22 to 20)
2-wire 2 pieces of 0.3mm2(AWG22)
Manufacturer Model Pressure bonding tool
Phoenix Contact Co., Ltd. AI 0.5-8WH CRIMPFOX ZA 3
(or CRIMPFOX UD 6)
9mm
(0.35")
- Strand wire/single wire
8mm
(0.31")
Contact area
(Crimping area)
14mm(0.55")
2.6mm(0.1")
Insulation sleeve
- Stick terminal with insulating sleeve
Thermocouple Type of compensating lead wire
Type K KX,KCA,KCB,KCC
Type J JX
3k
Ω
TC-ADP
L +
L -
24+
24-
Compensating lead
wire (Shielded)
Terminal
block
24V DC
External power
supply wiring
J-type
J-type
Thermocouple
*1
Thermocouple Wiring
Using Type J
Temperature
compensation circuit
*2
ch
ch
Grounding
(Ground resistance: 100
Ω
or less)
L +, L -, ch : represents the channel number.
L +
L -
Temperature
compensation circuit
3k
Ω
+5V
3.4 Grounding
Grounding should be performed as stated below.
•The grounding resistance should be 100Ωor less.
•Independent grounding should be performed for best results.
When independent grounding is not performed, perform "shared grounding" of the
following figure.
→ For details, refer to the FX3G Series User's
Manual - Hardware Edition.
→ For details, refer to the FX3U Series User's
Manual - Hardware Edition.
→ For details, refer to the FX3UC Series User's
Manual - Hardware Edition.
•The grounding wire size should be AWG 22-20 (0.3-0.5 mm2).
•The grounding point should be close to the PLC, and all grounding wire should be
as short as possible.
4. Specifications
4.1 Applicable PLC
The version number can be checked by monitoring D8001 as the last three digits
indicate it.
4.2 General Specifications
For the general specifications, refer to the manual of the PLC main unit.
The items other than the following are equivalent to those of the PLC main unit.
4.3 Power Supply Specifications
STARTUP AND
MAINTENANCE
PRECAUTIONS
•Do not disassemble or modify the PLC.
Doing so may cause fire, equipment failures, or malfunctions.
* For repair, contact your local Mitsubishi Electric distributor.
•Do not drop the product or exert strong impact to it.
Doing so may cause damage.
DISPOSAL
PRECAUTIONS
•Please contact a certified electronic waste disposal company for the
environmentally safe recycling and disposal of your device.
TRANSPORT AND
STORAGE PRECAUTIONS
•The product is a precision instrument. During transportation, avoid any impacts.
Failure to do so may cause failures in the product. After transportation, verify the
operations of the product.
Model name Applicability
FX3U Series PLC Ver. 2.20 or later (from first production)
FX3UC Series PLC Ver. 1.30 or later (from the production manufactured in August,
2004 with SER No. 48****)
FX3G Series PLC Ver. 1.00 or later (from first production)
Item Specification
Dielectric withstand
voltage 500V AC for one minute Conforming to JEM-1021
Between all terminals and
ground terminal of PLC
main unit
Insulation resistance 5MΩor more by 500V DC megger
Item Specification
A/D conversion
circuit driving power
24V DC +20%/-15%, 45mA for 24V DC
Connect a 24V DC power supply to the terminal block.
Interface driving
power
5V DC, 15mA
5V DC power is supplied from the internal power supply of
main unit.
PLC Another
equipment
PLC Another
equipment
PLC Another
equipment
Shared grounding
Good condition
Common grounding
Not allowed
Independent grounding
Best condition
4.4 Performance Specifications
Item
Specifications
Centigrade (°C) Fahrenheit (°F)
Input signal Thermocouple type K or J
JIS C 1602-1995
Rated
temperature
range
Type K -100°C to +1000°C Type K -148°F to +1832°F
Type J -100°C to +600°C Type J -148°F to +1112°F
Digital output
Type K -1000 to +10000 Type K -1480 to +18320
Type J -1000 to +6000 Type J -1480 to +11120
Resolution
Type K 0.4°C Type K 0.72°F
Type J 0.3°C Type J 0.54°F
Total accuracy ±(0.5% full scale +1°C)
A/D conversion
time
•FX3U/FX3UC Series PLC: 200µs
(The data will be updated at every scan time of the PLC.)
•FX3G Series PLC: 250µs
(The data will be updated at every scan time of the PLC.)
Input
characteristics
Insulation
method
•The photocoupler is adopted to insulate the analog input
area from the PLC.
•The DC-DC converter is adopted to insulate the power
supply line from the analog input area.
•A channels are not insulated from each other.
Occupied
points
0 point (This number is not related to the maximum number of
input/output points of the PLC.)
0
+600
°
C
+6000
-100
°
C
-1000
+610°C
Type J
+6100
-1100
Approx.
-110°C
0
+1000
°
C
+10000
-100
°
C
-1000
-110°C
+1010°C
Type K
+10100
-1100
0
+1832
°
F
+18320
-148
°
F
-1480
Approx.
-166
°
F
Approx.+1850
°
F
Type K
+18500
-1660
0
+1112
°
F
+11120
-148
°
F
-1480
Approx.+1130
°
F
Type J
+11300
-1660
Approx.
-166
°
F
FX3U-4AD-TC-ADP
USER'S MANUAL
This manual describes the part names, dimensions, mounting, and
specifications of the product. Before use, read this manual and the manuals of
all relevant products fully to acquire proficiency in handling and operating the
product. Make sure to learn all the product information, safety information, and
precautions.
Store this manual in a safe place so that it can be taken out and read whenever
necessary. Always forward it to the end user.
Registration:
The company and product names described in this manual are registered
trademarks or the trademarks of their respective companies.
Effective September 2008
Specifications are subject to change without notice.
©2005 Mitsubishi Electric Corporation
Manual Number JY997D14801
Revision F
Date September 2008

Other manuals for MELSEC-F FX3U-4AD-TC-ADP

2

This manual suits for next models

1

Other Mitsubishi Controllers manuals

Mitsubishi MELFA CR1D User manual

Mitsubishi

Mitsubishi MELFA CR1D User manual

Mitsubishi QD75P1N User manual

Mitsubishi

Mitsubishi QD75P1N User manual

Mitsubishi MELSEC iQ-F User manual

Mitsubishi

Mitsubishi MELSEC iQ-F User manual

Mitsubishi FX2N User manual

Mitsubishi

Mitsubishi FX2N User manual

Mitsubishi FX2N-10GM User manual

Mitsubishi

Mitsubishi FX2N-10GM User manual

Mitsubishi FX3U Series User manual

Mitsubishi

Mitsubishi FX3U Series User manual

Mitsubishi MELSEC Q Series Owner's manual

Mitsubishi

Mitsubishi MELSEC Q Series Owner's manual

Mitsubishi MELSEC-A series User manual

Mitsubishi

Mitsubishi MELSEC-A series User manual

Mitsubishi MELSEC Q Series Owner's manual

Mitsubishi

Mitsubishi MELSEC Q Series Owner's manual

Mitsubishi A1SJH(S8) User manual

Mitsubishi

Mitsubishi A1SJH(S8) User manual

Mitsubishi QD75M1 User manual

Mitsubishi

Mitsubishi QD75M1 User manual

Mitsubishi q64rd User manual

Mitsubishi

Mitsubishi q64rd User manual

Mitsubishi FX3U-64CCL User manual

Mitsubishi

Mitsubishi FX3U-64CCL User manual

Mitsubishi FX3U-20SSC-H User manual

Mitsubishi

Mitsubishi FX3U-20SSC-H User manual

Mitsubishi MELSEC-F FX-50DU-TKS-C User manual

Mitsubishi

Mitsubishi MELSEC-F FX-50DU-TKS-C User manual

Mitsubishi FX3G-2AD-BD User manual

Mitsubishi

Mitsubishi FX3G-2AD-BD User manual

Mitsubishi Melsec FX-4AD User manual

Mitsubishi

Mitsubishi Melsec FX-4AD User manual

Mitsubishi FX3U Series User manual

Mitsubishi

Mitsubishi FX3U Series User manual

Mitsubishi FX3G-14MR/ES User manual

Mitsubishi

Mitsubishi FX3G-14MR/ES User manual

Mitsubishi MELSEC QJ71C24N User manual

Mitsubishi

Mitsubishi MELSEC QJ71C24N User manual

Mitsubishi FX1N Series User manual

Mitsubishi

Mitsubishi FX1N Series User manual

Mitsubishi FX1N-14MR-ES/UL User manual

Mitsubishi

Mitsubishi FX1N-14MR-ES/UL User manual

Mitsubishi QD60P8-G User manual

Mitsubishi

Mitsubishi QD60P8-G User manual

Mitsubishi FX-16NP-S3 User manual

Mitsubishi

Mitsubishi FX-16NP-S3 User manual

Popular Controllers manuals by other brands

Nordson Vantage Customer product manual

Nordson

Nordson Vantage Customer product manual

Baldor NextMove ESB-2 installation manual

Baldor

Baldor NextMove ESB-2 installation manual

proSmart PS Plug user manual

proSmart

proSmart PS Plug user manual

gefran GPC 40-600A Use and installation  manual

gefran

gefran GPC 40-600A Use and installation manual

Digitrax UT6 Series manual

Digitrax

Digitrax UT6 Series manual

Peaktronics DHC-400 manual

Peaktronics

Peaktronics DHC-400 manual

Innotech GENII CSFCAH REM manual

Innotech

Innotech GENII CSFCAH REM manual

Mars GSW1 user manual

Mars

Mars GSW1 user manual

BIFFI ICON3000 Series Service manual

BIFFI

BIFFI ICON3000 Series Service manual

IDEC SmartAXIS Touch FT1A Series user manual

IDEC

IDEC SmartAXIS Touch FT1A Series user manual

iSMA CONTROLLI MDS520R Mounting instructions

iSMA CONTROLLI

iSMA CONTROLLI MDS520R Mounting instructions

Whelen Engineering Company 295SSA1 installation guide

Whelen Engineering Company

Whelen Engineering Company 295SSA1 installation guide

SEW-Eurodrive DR Series Addendum to the operating instructions

SEW-Eurodrive

SEW-Eurodrive DR Series Addendum to the operating instructions

YASKAWA motoman NX100 Maintenance manual

YASKAWA

YASKAWA motoman NX100 Maintenance manual

Alcor Micro AU9412EEP Technical reference manual

Alcor Micro

Alcor Micro AU9412EEP Technical reference manual

Graco 114-459 Instructions-parts list

Graco

Graco 114-459 Instructions-parts list

Chauvet DMX-40A user manual

Chauvet

Chauvet DMX-40A user manual

Emerson Level-Trol 2500 Series instruction manual

Emerson

Emerson Level-Trol 2500 Series instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.