CHAPTER 2:
SAFETY APPROVALS
UL 62368-1 and CSA22.2 No. 62368-1 - UL Recognized. C-UL for Canada.
IEC 62368-1 - CB Test Report and Certificate.
EN 62368-1 – TUV mark, CE mark.
Marking of the CE symbol indicates compliance to the EMC Directive, the Low Voltage Directive and RoHS Directive of the
European Union.
A “Declaration of Conformity” in accordance with the preceding directives and standards has been made and available on
file at our EU representative TDK LAMBDA GERMANY GmbH, located at Karl-Bold-Str. 40, D-77855 Achern.
A "Declaration of Conformity” may be accessed via company website www.uk.tdk-lambda.com/technical-data
2.1
Safety Instructions
CAUTION: The following safety precaution must be observed during all phases of operation, service and repair of this
equipment. Failure to comply with the safety precautions or warnings in this document violates safety standards of design,
manufacture and intended use of this equipment and may impair the built-in protections within. TDK Lambda shall not be
liable for user’s failure to comply with these requirements.
Die folgenden Sicherheitsvorschriften müssen vor Inbetriebnahme und in jedem Betriebszustand bei Service oder
Reparatur beachtet werden. Missachtung der Sicherheitsvorschriften und Warnhinweise aus diesem Handbuch führen
zur Verletzung der bestehenden Sicherheitsstandards. Bei Betrieb des Gerätes ausserhalb dem bestimmungsgemässen
Einsatz können die im Gerät integrierten Schutzfunktionen beeinträchtigt werden.
TDK-Lambda ist nicht haftbar für Schäden, die durch Missachtung dieser Sicherheitsvorschriften entstehen können.
CAUTION: RFE2500-xy units are not authorized for use as critical component in nuclear control systems, life support systems
or equipment for use in hazardous environments without the express written approval of the managing director of TDK-
Lambda.
Dieses Produkt ist nicht für die Verwendung als kritische Komponente in nuklearen Steuerungssystemen,
lebenserhaltenden Systemen oder Geräte für den Einsatz in gefährlichen Umgebungen, ohne die ausdrückliche
schriftliche Genehmigung durch TDK-Lambda zugelassen.
POWER SYSTEM, OVERVOLTAGE CATEGORY & ENVIRONMENTAL CONDITIONS
The RFE2500-xy units have been evaluated for using in TT and IT (230VAC line - to - line) power systems.
The RFE2500-xy units have been evaluated to Overvoltage category II.
The RFE2500-xy units intended for use in the following operation conditions:
* Indoor use * Pollutiondegree 2 * Max. Operational altitude: 3000m above sea level
*Ambient temperature: -10°C-50°C at 100% load, up to 70°C with output de-rating applied (refer to Specification above).
GROUNDING
RFE2500-xy units are Class I product. To minimize electrical shock hazard, the RFE2500-xy units must be connected to an
electrical ground. The instruments must be connected to the AC power supply mains through a three conductor power
cable, with the ground wire firmly connected to an electrical ground (safety ground) at the power outlet. For instruments
designed to be hard- wired to the supply mains, the protective earth terminal must be connected to the safety electrical
ground before any other connection is made. Any interruption of the protective ground conductor or disconnection of the
protective earth terminal will cause a potential shock hazard that might cause personal injury.
In addition, a screw through the end-equipment’s chassis to the power supply chassis must be fastened that would
connect the power supply to an electrical ground, refer to figure 2-1. This ground-dedicated screw must be other than the
mounting screws, must not serve as a means to fix any other component, and must be free of any glue or coating in order
to secure a solid and reliable connection. In case of doubt, earthing test (resistance of the protective bonding system) shall
be conducted to verify reliability of connection to the earthing system of the equipment.
To properly conduct this earthing test, stream an electric current with a magnitude of 60 A DC or AC, and the test voltage
shall not exceed 12 V, for a duration of 2 minutes between the head of the earthing screw and any other accessible
conductive part on the power supply.
Compliance criteria shall be that the voltage drop over the protective bonding system shall not exceed 2.5V.