LS 100
LS100 Specifications
MODEL
ITEMS/UNITS LS100-3.3 LS100-5 LS100-12 LS100-15 LS100-24 LS100-36 LS100-48
Input
Voltage Range (*2)(*13) V AC88 - 264 or DC125 - 373 (Withstand AC300 Surge for 5 seconds)
Frequency (*2) Hz 47 - 63
Efficiency(230VAC)(typ) (*1) % 75 79 82 84 86
Current(115/230VAC)(typ) (*1)
A 2.2 / 1.2
Inrush Current(typ) (*3) A 60A at 230VAC, Ta=25°C (Cold Start)
Leakage Current (*10) mA < 1mA at 230VAC, 60Hz
Output
Nominal Voltage VDC 3.3 5 12 15 24 36 48
Maximum Current A 20 16 8.5 7 4.5 3 2.3
Maximum Power W 66 80 102 105 108 110.4
Maximum Line Regulation (*5)(*6)
mV 20 48 60 96 144 192
Maximum Load Regulation (*5)(*7)
mV 40 96 120 192 288 384
Temperature Coefficient Less than 0.02%/°C
Maximum Ripple & Noise (*1)(*4)
mVp-p
80 120 150 200
Hold-up Time(115/230VAC)(typ) (*1)
ms 25 / 150
Voltage Adjustable Range VDC 3 - 3.6 4.75 - 5.5 10.8 - 13.2 13.5 - 16.5 22 - 27.2 32 - 40 42 - 54
Function
Over Current Protection (*8) A > 110% rated output power
Over Voltage Protection (*9) VDC 3.8 - 4.45 5.75 - 6.75 13.8 - 16.2
17.25 - 20.25
27.6 - 32.4 41.4 - 48.6 55.2 - 64.8
Series Operation Possible
Environment
Operating Temperature (*11) °C - 25 - + 70 (Refer to Output Derating Curve)
Storage Temperature °C - 40 - +85
Operating Humidity %
RH
20 - 90 (No dewdrop)
Storage Humidity %
RH
10 - 95 (No dewdrop)
Vibration At no operating, 10 - 55Hz (sweep for 1min)
19.6m/s² Constant, X, Y, Z 1hour each.
Shock(In Package) Less than 196.1m/s²
Cooling Convection cooling
Isolation
Withstand Voltage Input - Output : 3.0kVAC (20mA), Input - FG : 1.5kVAC (20mA)
Output - FG : 500VAC (100mA) for 1min.
Isolation Resistance
Input - FG, Input - Output and Output - FG: More than 100M
Ω
(500VDC) at 25°C and 70%RH
Standards
Safety Standards Approved by UL60950-1, EN60950-1, IEC60950-1
PFHC Built to meet IEC61000-3-2, -3
EMI Built to meet EN55011/EN55022-B, FCC-B
Immunity Built to meet EN61000-4-2 (Level 2,3), -3 (Level 3), -4 (Level 3),
-5 (Level 4), -6 (Level 3), -8 (Level 4), -11
Mechanical
Weight(typ) g 600
Size (W×H×D) mm 159 x 97 x 38 (Refer to Outline Drawing)
(*1) At Maximum Output Power, nominal input voltage, Ta = 25°C.
(*2) For cases where conformance to various safety specs (UL, CSA, EN) are required, to be described as 100 - 240VAC, 50 / 60Hz on name plate.
(*3) Not applicable for the in-rush current to Noise Filter for less than 0.2mS.
(*4) Ripple & noise are measured at 20MHz by using a 300mm twisted pair of load wires terminated with a 0.1uF film capacitor and a 47uF
electrolytic capacitor.
(*5) Measure line & load regulation at output terminal M3.5 tapped point.
(*6) 88 - 264VAC, constant load.
(*7) No load - Full load (Maximum power ), constant input voltage.
(*8) Current limit with automatic recovery. Avoid to operate at overload or dead short for more than 30 seconds.
(*9) OVP circuit will shutdown output, manual reset (Re-power on).
(*10) Measured by each measuring method of UL and EN (at 60Hz), Ta=25°C.
(*11) Refer to Output Derating Curve (PA577-01-02_) for details of output derating versus ambient temperature.
(*12) All parameters NOT specifically mentioned are measured at 230VAC input, rated load and Ta = 25°C.
(*13) Refer to Output Derating Curve (PA577-01-03_) for details of output derating versus input voltage.