4. Explanation of Functions and Precautions
4-1. Input Voltage Range
Input voltage range is single phase 85 ~ 264VAC (47~63Hz)
can withstand 300VAC surge for 5 seconds during operation.
Input voltage which is out of specification may cause unit to
damage. For cases where conformance to various safety
specs (UL, CSA, EN) are required, input voltage range will
be 100 ~ 240VAC (50/60Hz).
4-2. Output Voltage Range
Output voltage is set to the rated value at shipment. V.ADJ
trimmer on the front panel side can be used to adjust the
output voltage within the range specified (refer to
specifications for adjustable range).
To turn the trimmer clockwise, the output voltage will be
increased. Take note when the output voltage is increased
excessively, over voltage protection (OVP) function may
trigger and the output voltage will shut down. Furthermore,
when increasing the output voltage, reduce the output
current so as not to exceed the maximum output power.
4-3. Over Voltage Protection ( OVP )
The OVP function will shut down the output. To reset the
OVP, disconnect the input voltage from the power supply for
a minute and then re-apply. Possible to hiccup if the unit
prior to OVP point is already loaded. The OVP point is fixed
and cannot be adjusted externally.
4-4. Over Current Protection ( OCP )
Hiccup mode with automatic recovery. If the output
current is >101% of peak load, the unit will hiccup.
Avoid continuous operation in overload or short condition
as it may result in damage to the power supply.
4-5. Peak output current
The DRB120 can deliver up to 120% peak current for 10
seconds aiding the startup of capacitive loads and
operation of downstream circuit breakers. The output
peak current specification is Duty ≤35%, ≤rated output
power and ≤5Arms.
4-6. Output Ripple & Noise
The standard specification for maximum ripple value is
measured according to measurement circuit as below. When
load lines are longer, ripple becomes larger. In this case,
electrolytic capacitor, film capacitor, etc. might be necessary
to use across the load terminal. The output ripple cannot be
measured accurately if the probe ground lead of oscilloscope
is too long.
Oscilloscope
Bandwidth : 20MHz
+
-
P.S. C1 C2
1.5m 50
Cable
300mm
uF Electrolytic Capacitor
C2 : 0.1uF Film Capacitor
4-7. Series Operation
For series operation, either method (A) or (B) is possible.
Method ( A )
Output
Terminal
Output
Terminal
Power
Supply
Load
Method ( B )
Output
Terminal
Output
Terminal
Power
Supply