TE Technology TC-24-10 User manual

Instruction Manual
for
Model TC-24-10
Thermoelectric Cooler
Temperature Controller
October 16, 2015
Drawing #3170 Rev. I
1590 Keane Drive Phone: (231) 929-3966
Traverse City, MI 49696 USA Fax: (231) 929-4163
Web: www.tetech.com e-mail: cool@tetech.com
All Materials Copyright © 2012, TE Technology, Inc.
TETECHNOLOGY, INC.
®

2
General Safety Warnings
This manual is available in English only. It must be read and followed carefully before installation and
operation.
THE LATEST REVISION OF THIS MANUAL IS AVAILABLE AT www.tetech.com. Verify that you are
using the latest revision available.
The TC-24-10 should not be used as a toy, or serious injury could result. The TC-24-10 should only
be used for its intended purpose of providing temperature control of TE Technology’s
thermoelectric devices only. The controller is intended for light industrial, laboratory, or similar
use. It is not intended for household use or medical use.
Do not use in an explosive or potentially explosive environment.
Do not use the TC-24-10 to control capacitive or inductive loads or the controller could be damaged
and/or overheat. Examples of capacitive or inductive loads include but are not limited to motors,
fans, filters, and solenoids.
Do not allow the electrical connections on the printed circuit board to touch any electrically
conductive surfaces.
Do not operate in an environment where the controller could come in contact with condensation,
water, metal shavings, dirt or other contaminants, or electrically conductive materials.
Use ESD (Electro Static Discharge) protection when coming in contact with electrical connections
or components on the controller.
Do not touch any of the electrical connections or components of the TC-24-10 while the controller
is energized. Doing so can disrupt the function of the controller.
Do not use if the controller has been damaged in any way.
Only qualified technicians should install and operate this controller with the appropriate personal
protective quipment.
Improper tuning of this temperature controller can lead to excessive thermal cycling and/or
overheating of the thermoelectric device, either of which are known to reduce the lifetime of any
thermoelectric device. Care should be taken to prevent the temperature of the thermoelectric
device from going beyond the range specified by the device manufacturer. Care should also be
taken so that any thermal cycling of the thermoelectric device is a result of changes in the
controller’s set-point temperature and not instability at a given set point due to improper selection
of the tuning variables.
The temperature controller base underneath the transistor-mounting area could exceed 60 °C
under normal operation. Use caution! Protect against accidental contact with hot surfaces.
Use protection devices to prevent hazardous conditions and/or damage to equipment.
Each power input that is used with the controller must be fused separately. Alternatively, a power
supply with integral over-current protection may be used if it is appropriately sized for protecting
the controller/TE device.
WP5 (+ power in) and WP1 (+ load output) are connected to each other inside the controller. When
WP5 is energized a voltage will be present on WP1, even if the output is off or the controller is
being used with two power supplies.

3
The temperature controller is intended to be used with, or incorporated into, other machinery
made by TE Technology, Inc. and must not be put into service until the relevant machinery into
which it is to be incorporated into has been declared in conformity with the essential requirements
of the Machinery Directive 2006/42/EC.
For more information regarding protection devices read TE Technology’s Thermoelectric Cooling Assembly (TCA)
Instruction manual which is available for download from TE Technology’s website at www.tetech.com. The terms
and provisions relating to protection devices as provided in the TCA Instruction manual are herby incorporated by
reference. A copy of the TCA Instruction manual can also be sent via regular mail upon request.
TE Technology, Inc. does not make any warranty, expressed or implied, that the use or operation of the equipment
will be functional or effective if the equipment is not installed and used in accordance with this manual.
TE Technology, Inc. shall not be liable, and Purchaser shall defend, hold harmless, and indemnify TE Technology,
Inc. from and against, any losses, costs, expenses (including reasonable attorneys’ fees), injuries, liabilities or
damages of any kind or nature whatsoever, arising out of the use or inability to use this TE Technology, Inc.
product, from the omission or failure to use protection devices, or from failure to comply with this manual. This
provision is in addition to any other indemnification provisions which are a part of the Purchase Order or contract
with Purchaser.

4
Table of Contents
Features .......................................................................................................................................... 5
Operating Instructions.................................................................................................................... 8
1.0 Setup ............................................................................................................................... 8
2.0 Control Function Description........................................................................................ 14
3.0 Controller Tuning .......................................................................................................... 15
Controller Wiring Diagram (One Power Supply Setup) ................................................................ 17
Controller Wiring Diagram (Two Power Supplies Setup).............................................................. 18
Mechanical Package Drawing ....................................................................................................... 19
Temperature vs. Sensor/Potentiometer Voltage (graphs)........................................................... 20
Temperature vs. Sensor/Potentiometer Voltage (table).............................................................. 21
Thermistor Styles for TC-24-10..................................................................................................... 22

5
Features
TC-24-10 Temperature Controller
The TC-24-10 is a heat- or cool-only temperature controller for thermoelectric (TE) devices. It can also be used with
resistive heaters. The basic components of the TC-24-10 are a microprocessor, a thermistor input, a power output
stage, and potentiometers located on the controller’s circuit board to adjust the temperature set point,
proportional bandwidth, and integral gain settings. While the TC-24-10 lacks some of the features found in our
more sophisticated controllers, such as having a display or being able to directly interface with a computer, its low
cost makes it ideal for projects that have limited budgets.
Mechanically, the controller’s printed circuit board is mounted to a metal bracket. It can be mounted either
horizontally or vertically. The controller can operate in ambient temperatures from 0 °C to 50 °C without generally
requiring additional heat sinking. The controller is intended to be used in locations where the controller can be
protected by a secondary enclosure or other means of protection.

6
Main Features
•Single or dual power supply input configuration:
Single power supply configuration:
(9 to 26) VDC, powering both controller and TE device
Dual power supply configuration:
(9 to 26) VDC at 0.15 A for controller circuitry,
(0 to 40) VDC for TE device
•Maximum output current: 10 A (Note: controller does not have current limiting capability)
•Heat-only or cool-only control modes, selectable by jumper switch
•Temperature control range: –20 °C to +100 °C, requires the MP-3238 thermistor (supplied with the
controller), or its electrical equivalent
•Best-case control stability ±0.5 °C (when controlling a cold plate)
•Proportional (P) bandwidth adjustment: 0.5 °C to 5.0 °C
•Integral Rate (I) adjustment: 0 to 2.55 repeats per minute
•Output: Square wave, 1000 Hz, Pulse-width modulated
•Operating temperature range 0 °C to 50 °C ambient (with aluminum mounting plate in a vertical position
allowing free air convection)
•0.25 inch quick connect terminals for power, cooler, and thermistor connections
•RoHS compliant
The controller’s operating temperature range is 0 °C to 50 °C ambient. The range can be extended to 70 °C with
proper heat-sinking. If the controller is to operate in an ambient greater than 50 °C, consult with TE Technology
engineers for further assistance. See “Mechanical Package Drawing” for dimensional information on the
controller.
For high-volume applications the controller can be customized:
✓Adjustment potentiometers can be replaced with preprogrammed set-point and tuning parameters
✓Resistance versus temperature curves for other types of thermistors can be programmed

7
Pulse-width modulated power output
The controller regulates the output power to the TE using a method called pulse-width modulation (PWM). With
PWM, power to the TE device is switched quickly “ON”and “OFF”at a constant frequency (1000 Hz for this
controller). This creates a square wave “pulse” of power with a constant time period. The “ON” time, or pulse
width, can be varied to create an average output voltage (Vaverage) that is required by the TE device to maintain
the set temperature.
The important advantage to PWM is that it does not cause the extreme temperature excursions that are
experienced with a thermostatic control system. This helps to extend the life and reliability of the TE devices. An
added benefit is that the controller does not generate a large amount of waste heat, so a large heat sink is not
usually required.
Multiple Control Configurations
The controller can be used with either one power supply for powering the controller electronics and the TE device
together or with two power supplies for powering the controller electronics and TE device independently.
Whether the controller is configured to use one or two power supplies, the TE device should not be allowed to
draw more than 10 A at its rated voltage.
When using one power supply, the input voltage is passed directly through the controller to the TE device during
“ON” pulse. The controller electronics operate within a (9 to 26) V range, so the TE device must likewise be rated
for at least 9 V, but no more than 26 V.
If the TE device operates on less than 9 V, the TC-24-10 can be configured to use two power supplies. The power
supply for the controller electronics must be able to provide (9 to 26) V at 150 mA current minimum. The power
supply for the TE device can then be selected to provide the appropriate voltage ranging from (0 to 40) V.

8
Regardless of whether you use one or two power supplies, when making a cooling system from a single TE module,
the maximum operating voltage for that system is usually no more than 75% of the rated Vmax of the TE module.
The 75% rule is based on the TE module being thermally connected to a “good” heat sink; system modeling should
be done to verify this rule is applicable though. If multiple TE modules are used in a series or series-parallel
combination, the Vmax of the system will be approximately 75% of the rated Vmax of each TE module multiplied
by the number of modules in series.
Operating Instructions
1.0 Setup
Portions of the temperature controller (the aluminum frame near the output transistors, for
example) could exceed 60 °C during normal operating conditions. Temperatures greater than 60 °C
can result in a hazard to the user. Use caution! Protect against accidental contact with hot
surfaces.
If the temperature controller is to be used under conditions such that its surface temperatures
could possibly exceed 60 °C, test the surface temperatures under the worst-case operating
conditions of maximum ambient temperature and highest output current and voltage. If any
portion of the temperature controller exceeds 60 °C place adequate guards around the
temperature controller to prevent contact with any hot surfaces.
NOTE: the maximum allowable ambient temperature for the controller is 50 °C. Furthermore, the
maximum allowable temperature of the controller base (underneath the transistor-mounting area)
is 90 °C. Furthermore, the controller might need additional heat sinking, depending on ambient
conditions and how much current is being drawn by the TE device.
Note: See “Controller Wiring Diagram (One Power Supply Setup)” or “Controller Wiring Diagram (Two
Power Supplies Setup)” for additional reference.
1.1 Set the position of jumper JP1.
•To set the controller in cooling mode: JP1 is shorted (jumper is installed)
•To set the controller in heating mode: JP1 is open (jumper is removed)
1.2 Attach the thermistor at an appropriate temperature-control location. Locating the thermistor at the cold
side of the TE device provides better control stability than locating it at the object, liquid, or air that is to be
cooled/heated. However, in doing so, there will be a temperature difference between the TE device and the
object, liquid, or air that is to be cooled/heated. The temperature set point can be adjusted to compensate
for this temperature difference if necessary.
NOTE: When possible, it is recommended that at least 50 mm of the thermistor’s wire be thermally
connected to the cold side of the TE device. This can be accomplished by placing aluminum tape over the
thermistor wires and adhering the wires and tape to the cold side of the cooler. If this is not done, the
thermistor wires will be at a different temperature than the cold side and they will add or remove heat in

9
the region of the thermistor, making the temperature reading significantly less accurate and thermal
response time slower.
The TC-24-10 is supplied with the MP-3238 thermistor. Other thermistor styles directly compatible with the
controller are available as options. See “Thermistor Styles for TC-24-10” for reference.
If you want to use a thermistor that has a different resistance-temperature curve from the standard MP-
3238 (See “Temperature versus Resistance for MP-3238, MP-2444, and MP-2542 Thermistors” for
reference), it can be done as long as the operating resistance range is within that of the standard
thermistor. The thermistor must be a negative temperature coefficient device. Because the temperature
controller is really measuring the thermistor’s resistance and converting this to a temperature, the
temperature controller will be fooled into thinking that the thermistor is at a different temperature than it
really is, and the Set-Temperature will be skewed accordingly. A loss of resolution and control stability may
occur as a result. The user assumes all risks associated with making any substitutions, and TE Technology
assumes no liability whatsoever for the operation of the controller when a non-standard thermistor is used.
1.3 Connect the thermistor wire leads to WP3 and WP4.
1.4 The TC-24-10 can be used with two separate power supplies which allows for the control of TE devices
whose nominal operating voltage is less than 9 V. In this case, one power supply is for the TE device, and
the other power supply is for the controller itself (the microprocessor and associated electronics). Of
course, a single power supply can be used for powering both the controller and the TE device provided that
the TE device’s nominal operating voltage is ≥9 V and ≤26 V.
When using one power supply for powering the controller and the TE device together, the power
supply input voltage is passed directly through the controller to the TE device during the “ON”
pulse. The user should choose an input voltage that is required for the TE device and yet is also ≥9
V but ≤26 V. The controller could be damaged if operated outside this voltage range.
When using two power supplies, the controller input power supply must be ≥9 V and ≤26 V at 150
mA minimum current. The power supply input voltage for the TE device can be ≥0 V but ≤40 V.
The maximum allowable current through the controller is 10 A. The maximum allowable current
draw for the TE device must therefore also be less than 10 A. The 10 A limit applies regardless of
whether you are using one power supply or using two independent power supplies.
The controller does not have an internal fuse or circuitry to limit current. Therefore, an external
fuse, appropriately sized for protecting the controller/TE device, should be connected between the
power supply and the controller to prevent damage to the controller/TE device and to prevent
injury to the user should an over-current condition occur. Alternately, a power supply with integral
over current protection can be used if it is appropriately sized for protecting the controller/TE
device.
When making a cooling system from a single TE device, the maximum operating voltage for that
system is usually no more than 75% of the rated Vmax of the TE module. The 75% rule is based on
the TE module being thermally connected to a “good” heat sink; system modeling should be done
to verify this rule is applicable though. If multiple TE modules are used in series or series-parallel
combination, the Vmax of the system will be approximately 75% of the rated Vmax of each TE
module multiplied by the number of modules in series. Applying a voltage greater than the system
maximum will not necessarily damage the controller (unless voltage and/or current limits are
exceeded), but the TE device could be damaged by overheating as a result.

10
Power supply and TE Device wire leads should be kept as short as possible to minimize electrical
losses and reduce the likelihood of generating unwanted electromagnetic interference. Wire length
must not exceed one meter. Use wires of a sufficient gage appropriate to the amount of electrical
energy each wire is to carry. Wire insulation and size must also be appropriate to the ambient
temperature and/or temperature of objects in contact with the wire. Wire leads supplied by TE
Technology are for prototyping purposes and should be reviewed for appropriateness in the final
application.
Use protection devices to prevent hazardous conditions and/or damage to the load (e.g. cooling
assembly, heater, etc.) and other related equipment. Protection devices must operate
independently of the temperature controller circuitry. Protection devices should be placed at all
points on the load and related equipment where a hazardous condition can be detected. These
protection devices should de-energize the TC-24-10, the load, and, as necessary, other related
secondary equipment. It is further recommended that such devices require the user to remove and
correct the root cause of a fault before allowing the TC-24-10, the load, and related equipment to
be re-energized. Protection devices should include, but are not limited to:
•Fuses to prevent against electrical overloads,
•Over/under temperature thermostats to prevent against hazardous and/or damaging
temperatures,
•Liquid flow meters to prevent against damage due to loss of coolant flow
The TC-24-10 controller (in conjunction with the standard and optional sensors) can not detect
under-temperature and over-temperature conditions. Therefore, hazards and/or risk of loss or
damage to the load (e.g. cooling assembly, heater, etc.), and/or secondary equipment could
occur if the temperature controller and/or sensors were to malfunction. Therefore, independent,
redundant protection devices are recommended in addition to the safeguards provided by the
temperature controller.

11
1.4.1 One Power Supply Operation:
Make sure the power supply is NOT energized while making electrical connections to the
controller.
Power supply should be of voltage needed for TE device.
If voltage is not between 9 V to 26 V then a two power supply configuration is necessary.
c) Connect the constant DC voltage power supply, (9 to 26) V to the controller:
Positive (+) power supply terminal to WP5
Negative (-) power supply terminal to WP6
Turn on the power supply to the controller.
b) Do NOT connect the TE device to the controller at this time.
c) See the “Controller Wiring Diagram (One Power Supply Setup)” for further details.
1.4.2 Two Power Supplies Operation:
Make sure the power supplies are NOT energized while making electrical connections to the
controller.
c) Connect the constant DC voltage power supply (9 to 26) V, 150 mA minimum to the controller (for
powering the controller):
Positive (+) power supply terminal to WP5
Negative (-) power supply terminal to WP6
Turn on the power supply to the controller.
b) Connect the constant DC voltage power supply (0 to 40) V to the controller (for powering the module):
Negative (-) power supply terminal to WP6
NOTE: both power supplies must connect their negative terminals to WP6
c) Do NOT connect the TE device negative (-) terminal to the controller at this time.
d) See the “Controller Wiring Diagram (Two Power Supplies Setup)” for further details.
1.5 Turn on the power supply to the controller, and adjust the temperature set point using potentiometer R7.
The potentiometer range corresponds to -20 °C at full counter-clockwise to +100 °C at full clockwise. This is
a 25-turn potentiometer, so each full turn corresponds to a 4.8 °C change in the set point.
Verify that the set point is set to a temperature that is within the allowable temperature range of
the TE device. DO NOT CONNECT THE TE DEVICE TO THE OUTPUT OF THE CONTROLLER UNTIL
THE APPROPRIATE CONTROL TEMPERATURE HAS BEEN SET.
The TC-24-10 does not have a display for indicating the set temperature or sense temperature. However,
you can measure the sensor (thermistor) voltage across WP3 to WP4, and the set point voltage across Pin 2
(+) to Pin 3 (-) on potentiometer R7. The “Temperature vs. Sensor/Potentiometer Voltage” graphs and
tables show the relationship between voltage and temperature for the sensor and the set point.

12
1.6 Turn off the power to the controller and connect the TE device to the controller:
COOLING MODE:
One Power Supply Operation
a) Connect the positive terminal (+) of ONLY the TE device to WP1.
b) Connect the negative terminal (-) of ONLY the TE device to WP2.
c) Verify that JP1 is shorted (that is, a jumper is installed, which is the factory default).
Two Power Supplies Operation
a) Connect the positive (+) terminal of ONLY the TE device to the positive terminal of the
power supply that will be used for the TE device.
b) Connect the negative (-) terminal of ONLY the TE device to WP2.
c) Verify that JP1 is shorted (that is, a jumper is installed, which is the factory default).
HEATING MODE:
One Power Supply Operation
a) Connect the positive terminal (+) of ONLY the TE device to WP2.
b) Connect the negative terminal (-) of ONLY the TE device to WP1.
c) Verify that JP1 is open (that is, no jumper is installed).
Two Power Supplies Operation
a) Connect the negative (-) terminal of ONLY the TE device to the positive terminal of
the power supply that will be used for the TE device.
b) Connect the negative (+) terminal of ONLY the TE device to WP2.
c) Verify that JP1 is open (that is, no jumper is installed).

13
TE Technology’s standard thermoelectric cooling assemblies (TCA) have at least one fan on the heat
sink. The standard configuration has the thermoelectric modules and fan(s) wired to a terminal block
with jumpers across the terminals so that the fans and modules are connected in parallel. However,
this configuration is applicable only when applying power directly from the power supply. When using
the TCA with the temperature controller, the jumpers MUST be removed so that the controller is
controlling power only to the thermoelectric modules. There must be no electrical connection
between the fans and the modules; fans must be connected directly to the power supply, not to the
controller. The controller will be damaged if this is not followed. See the cooler manual for further
details, but the picture below shows the basic setup.

14
1.7 Turn on power supply to the controller (and power supply to the TE device if applicable), and set tuning
parameters as necessary. Controller tuning is discussed in section 3.
Do not mount the controller to a surface which is exposed to a source of heat, such as from
electronics, machinery, or solar radiation.
Do not cover the controller with any object or otherwise restrict natural convection airflow around
the controller. Doing so could cause the controller to overheat.
Do not mount the controller to an insulating surface. Doing so could cause the controller to
overheat.
Do not operate the controller in such a manner as to cause the surface temperature of the circuit
board or its frame to reach 70 °C. Otherwise the controller might be damaged and there might be a
risk of fire as a result.
Do not allow the controller to be exposed to water (such as from dripping or leaking water lines or
from water-vapor condensation if the surface temperature of the controller is below the dew point
temperature).
Do not allow metallic dust/shavings to contact the controller electronics.
2.0 Control Function Description
2.1 Proportional control: This eliminates much of the temperature cycling inherent in on/off control. The
proportioning bandwidth is the temperature span over which the power is proportioned from 0% to 100%
power, centered about the temperature set point. That is, the controller output decreases to 50% power as
it reaches the set point and to 0% as it reaches the end of the bandwidth range above the set point.
For example, suppose the controller is being operated in the cooling mode, the set point is 10.0 °C, and the
bandwidth is set to 5 °C. The controller power starts to proportionally decrease as the sensor temperature
cools below 12.5°C. The power will be reduced to 50% when the sensor is at 10.0 °C. Finally, the power will
be at 0% when the sensor is at 7.5°C. (Of course, this example presumes that the cooler would have
enough capacity to cool to 7.5 °C.)
If the bandwidth is set too narrow, the temperature will oscillate around the set point. If the bandwidth is
too wide, the controller will be slow to respond or may never reach set point.
2.2 Integral Control: This corrects for any offset between the set temperature and the sense temperature by
averaging the offset with respect to time. This essentially shifts the proportioning bandwidth.
For example, suppose the set temperature is 10.0 °C, the bandwidth is set to 5 °C, and the controller settled
to a constant 11.2 °C (corresponding to 74% power). If the integral control is set to 1 repeat per minute,
the controller will increase the power to 98% in 1 minute. In this example, after one minute of operation
the controller calculated that the error from the desired temperature to actual temperature was +1.2 °C
above set point. With a bandwidth of 5 °C, the controller then calculated that it needed an additional 24%
output (100% output / 5 °C * 1.2 °C = 24 %). This additional 24% output was added to the existing 74%
output to yield 98% output. The integral portion of the output is recalculated at the frequency specified by
the integral potentiometer. Thus, at the next update period for the integral the controller will add or
subtract as necessary from the 98% output. Of course, the maximum output is limited to 100% and the
minimum is limited to 0%.
If the integral control is set too high, the temperature will oscillate. If integral control is set too low, it will
take a long time for the temperature to settle to steady state.

15
3.0 Controller Tuning
Tuning of Proportional and Integral (PI) control requires knowing two parameters:
1. The natural period of the system, and
2. The bandwidth used to achieve this cycle.
This tuning method follows the Ziegler Nichols closed-loop tuning principals. Briefly, the controller will first be set
to a low gain (high Bandwidth) setting with no integral function (Integral rate = 0). Then, the gain is gradually
increased until the temperature approaches set point, and a small, sustained oscillation in temperature is
observed. The tuning parameters are then readjusted based on the time period of the temperature oscillation
(natural period) and the Bandwidth needed to cause this oscillation.
Improper tuning of this temperature controller can lead to excessive thermal cycling and/or
overheating of the thermoelectric device, either of which are known to reduce the lifetime of any
thermoelectric device. Care should be taken to prevent the temperature of the TE device from going
beyond the range specified by the device manufacturer. Care should also be taken so that any
thermal cycling of the TE device is a result of changes in the controller’s set-point temperature and
not instability at a given set point due to improper selection of the tuning variables.
The potentiometers used on this controller are 25-turn devices. When the potentiometer has been adjusted to the
“maximum clockwise”or “maximum counterclockwise”position, the adjustment pawl will ratchet on the screw-
driven gear, making a slight clicking sound.
3.1 Set the Integral Rate Potentiometer (R8) to zero by adjusting it to maximum counterclockwise.
3.2 Set the Proportional Bandwidth Potentiometer (R2) to 5 °C by adjusting it to maximum clockwise.
3.3 Set the desired control temperature by adjusting the Set Temperature Potentiometer (R7). See the
“Temperature vs. Sensor/Potentiometer Voltage” graphs and tables for the potentiometer voltage-set point
relationship.
3.4 Adjust the Proportional Bandwidth Potentiometer counterclockwise until a small, sustained temperature
oscillation is observed. (You can adjust in initial increments of 1 V, or 5 turns. Then, once an initial
oscillation is observed, adjust the potentiometer clockwise until the oscillations are barely detectable).
3.5 Record the number of turns (counterclockwise from the maximum clockwise position) on the Proportional
Bandwidth Potentiometer that are required to barely sustain this temperature oscillation.
_________________________ Turns
3.6 Calculate the bandwidth that corresponds to this potentiometer setting using the formula: Bandwidth = 5
°C –0.18 °C/turn x (number of turns recorded in section 3.5). (See Tuning Example below)
Bandwidth = _____________________ °C
3.7 The time that it takes to go from one peak temperature to the next peak temperature is the natural period.
Record the time of the natural period in minutes.
_________________________ Minutes

16
3.8 Double the bandwidth calculated in section 3.6, and then adjust the Proportional Bandwidth Potentiometer
to this new value. Fully counterclockwise = 0.5 °C, and fully clockwise = 5 °C. Each full turn of the
Proportional Bandwidth Potentiometer corresponds to 0.18 °C increment. If doubling the bandwidth yields
a value greater than 5 °C, set the bandwidth to 5 °C.
3.9 Calculate the inverse, or reciprocal, of the natural period recorded in section 3.7, and adjust the controller
Integral Rate (the number of repeats per minute) to this value. Each full turn of the Integral Rate
Potentiometer corresponds to 0.102 repeats per minute increment.
3.10 These Proportional and Integral settings are approximate settings and may need further minor adjustments.
Record the final number of turns used on the Proportional Bandwidth Potentiometer and Integral Rate
Potentiometer.
Final number of turns on the Proportional Bandwidth Potentiometer =__________________ from
maximum clockwise.
Final number of turns on the Integral Rate Potentiometer =__________________ from maximum
counterclockwise.
Additional systems with the same thermodynamic properties will operate using the Potentiometer settings
listed above.
Tuning Example:
A. Suppose that 16 counterclockwise turns of the Proportional Bandwidth Potentiometer (R2) were
required to just sustain a temperature oscillation. This corresponds to a proportional bandwidth of
about (5 °C –0.18 °C/turn x 16 turns =) 2.1 °C. (Reference section 3.6)
B. It was then observed that the natural period of this oscillation was 2 minutes. (Reference section 3.7)
C. The Proportional Bandwidth Potentiometer (R2) should be adjusted to double the bandwidth to 4.2 °C.
(Reference section 3.8) This is about 20.5 turns clockwise from the full counterclockwise position (0.5
°C + 0.18 °C/turn x 20.5 turns = 4.2 °C).
D. The Integral Rate variable should be set to the inverse of the natural period by adjusting the Integral
Rate Potentiometer (R8). This is 1/(2 min) = 0.5 repeats per minute. Since each turn of the
potentiometer equals 0.102 repeats per minute, the potentiometer should be adjusted 4.9 turns
clockwise from the full counterclockwise position. (Reference section 3.9)

17
Controller Wiring Diagram (One Power Supply Setup)
Notes: R2 = Proportional bandwidth adjustment (0.5 to 5 °C), clockwise to increase
R7 = Set-point temperature adjustment (-20 to +100 °C), clockwise to increase
R8 = Integral rate adjustment (0 to 2.55 repeats per minute), clockwise to increase
All potentiometers have a 25-turn adjustment range.
WP1, WP2, WP3, WP4, WP5 and WP6 are 0.25 inch quick-connect terminals
When one or more external fans are used on the TE device, these should be wired directly to a fixed
voltage power supply for constant operation.
When connecting the controller to a TE Technology Thermoelectric Cooling Assembly (TCA) verify that
the electrical jumpers (shorts) located on the TCA terminal block are installed/removed per the TCA
operating manual before powering the controller.
THERMISTOR
TE DEVICE
(shown in cooling mode)
POTENTIOMETER
PIN IDENTIFICATION
DC
POWER SUPPLY (+)(-)
(+)
(-)
WP1
WP5
WP6
WP2
WP4 WP3
R8 R7
JP1
R2
1
2
3
=9 V, =26 V, 10 A maximum
FUSE
THERMOSTAT AND
OTHER PROTECTIVE
DEVICES

18
Controller Wiring Diagram (Two Power Supplies Setup)
THERMISTOR
DC
POWER SUPPLY
(+)
(-)
WP1
WP5
WP6
WP2
WP4 WP3
R8 R7
JP1
R2
(-)
(+)
DC
POWER SUPPLY
=9 V, =26 V, 150 mA
=0 V, =40 V, 10 A maximum (+) (-)
TE DEVICE
(shown in cooling mode)
CONNECT POWER SUPPLY
GROUNDS TOGETHER AT WP6
FUSE
THERMOSTAT AND
OTHER PROTECTIVE
DEVICES

19
Mechanical Package Drawing
PROPORTIONAL
BANDWIDTH POTENTIOMETER
HEAT/COOL MODE JUMPER
SET TEMPERATURE
POTENTIOMETER
INTEGRAL RATE
POTENTIOMETER
45.7
38.1
69.8
50.8
63.5
3.96
Ø3.96
NOTE: ALL DIMENSIONS IN MILLIMETERS
WP5
WP1
WP6
WP2
WP4 WP3
R7
JP1
R2
R8

20
Temperature vs. Sensor/Potentiometer Voltage (graphs)
Sensor Voltage Vs. Temperature
0.0
0.4
0.8
1.2
1.6
2.0
2.4
2.8
3.2
3.6
4.0
4.4
4.8
5.2
-20 -12 -4 412 20 28 36 44 52 60 68 76 84 92 100
Temperature (°C)
Voltage (V)
Potentiometer Voltage Vs. Set-point Temperature
0.0
0.4
0.8
1.2
1.6
2.0
2.4
2.8
3.2
3.6
4.0
4.4
4.8
5.2
-20 -12 -4 412 20 28 36 44 52 60 68 76 84 92 100
Temperature (°C)
Voltage (V)
Table of contents
Other TE Technology Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

Jackson Systems
Jackson Systems THE GREEN ZONE Z-200-HC-MS Installation and operation instructions

Siemens
Siemens REA23 operating instructions

STORK TRONIC
STORK TRONIC ST48-WHDVM.04 manual

Busch-Jaeger
Busch-Jaeger 1094 U product manual

Ropex
Ropex CIRUS UPT-6010 operating instructions

Vector
Vector SRC-C1T1 manual

Viessmann
Viessmann VITOTROL 100 OT Operating Instructions for the System User

Apogee
Apogee TS-100 owner's manual

Störk-Tronic
Störk-Tronic TRT252-31.34 Wiring diagram

Define Instruments
Define Instruments PRO-TC-LV manual

GreenTech
GreenTech pureComfort YEAR-ROUND owner's manual

Oregon Scientific
Oregon Scientific S+ARCK PS-R01 user manual