1
1. Introduction
The scrubber is a Venturi scrubber designed to recirculate water to remove
fumes from a gas stream. The primary design of the scrubber is the removal of fumes
from a furnace installation however, it can be used for a wide variety of applications.
Absorption of fumes is achieved in the spray venturi contact with scrubbing liquor
recirculated by a sump pump from the column sump tank.
A General Layout Drawing of the unit is included in the documentation manual.
2. Installation
The scrubbing unit should be sited on a level surface. It is recommended the base frame
be through bolted to the floor.
The gas inlet and outlet are of plain spigot arrangement, the connecting flexible duct
should be secured with jubilee type clamps.
The scrubber should be connected to a water supply. The connection is a ½” BSP female
threaded connection as labelled, it is generally recommended an isolation valve be fitted
in the water supply to the scrubber.
The drain connection may be connected to a suitable drain. This is not essential as liquid
should not be discharged during normal operation.
The pump should be connected to a single phase 240V supply. DO NOT RUN DRY.
3. Start-Up
Following installation or a shut-down period the integrity of the scrubber unit should be
visually checked.
The position of valves should be as follows: Drain Valve :Closed
Sampling Valve :Closed
Recirculation Valve :Open
The water supply can then be turned on to the scrubber and allowed to come up to level.
The scrubber is fitted internally with a ball float valve, this will maintain the correct liquid
level in the scrubber.
Once the liquid level has reached operating level the pump can be switched on and the
system inspected for leaks.
NOTE: DO NOT OPERATE THE PUMP WITH NO WATER. RUNNING THE PUMP DRY
WILL CAUSE SIGNIFICANT DAMAGE.
Having ensured there no leaks, the unit is ready for normal operation.