TECOM ChallengerPlus Owner's manual

ChallengerPlus Installation
and Quick Programming
Manual
P/N MAINST-TS-CHPLUS • REV 1.7 • ISS 16AUG19

Copyright
© 2019 UTC Fire & Security Australia Pty Ltd. All rights reserved.
Trademarks and
patents
The Challenger name and logo are trademarks of UTC Fire &
Security Australia Pty Ltd.
Other trade names used in this document may be trademarks or
registered trademarks of the manufacturers or vendors of the
respective products.
Manufacturer
Made in China by United Technologies Safety Systems
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Imported by UTC Fire & Security Australia Pty Ltd t/a Interlogix
10 Ferntree Place
Notting Hill, Victoria, 3168, Australia
ACMA compliance
Contact information
For contact information, see www.interlogix.com.au.

ChallengerPlus Installation and Quick Programming Manual i
Content
Important information.........................................................................................ii
Agency compliance ............................................................................ii
Limitation of liability ............................................................................ii
Regulatory requirements for New Zealand.........................................iii
Preface ................................................................................................................iv
Product overview ................................................................................................1
Product contents................................................................................ 1
Before you begin.................................................................................................2
Enclosure Access Restrictions........................................................... 2
Cabling requirements......................................................................... 2
System configurations ....................................................................... 6
Installing the control panel.................................................................................9
Installation guidelines ........................................................................ 9
Installation procedures......................................................................10
Board details ....................................................................................11
Application notes..............................................................................14
Initial programming...........................................................................................21
Disarming the system.......................................................................21
Accessing the Challenger menu.......................................................21
Clearing the memory ........................................................................26
Basic programming sequence ..........................................................26
Working with multi-area systems ......................................................28
Default installer PIN..........................................................................28
Enabling communications.................................................................29
Programming users ..........................................................................40
Firmware upgrade process ....................................Error! Bookmark not defined.
Requirements..................................... Error! Bookmark not defined.
Getting ready...................................... Error! Bookmark not defined.
Upgrade process................................ Error! Bookmark not defined.
Appendix C: Operating temperature................................................................41

ii
Important information
Agency compliance
This product conforms to the standards set by Standards Australia on behalf of
the Australian Communications and Media Authority (ACMA). Enclosure covers
must remain fitted in order to maintain ACMA compliance.
Limitation of liability
To the maximum extent permitted by applicable law, in no event will Interlogix (a
division of UTC Fire & Security Australia Pty Ltd) be liable for any lost profits or
business opportunities, loss of use, business interruption, loss of data, or any
other indirect, special, incidental, or consequential damages under any theory of
liability, whether based in contract, tort, negligence, product liability, or otherwise.
Because some jurisdictions do not allow the exclusion or limitation of liability for
consequential or incidental damages the preceding limitation may not apply to
you. In any event the total liability of Interlogix shall not exceed the purchase
price of the product. The foregoing limitation will apply to the maximum extent
permitted by applicable law, regardless of whether Interlogix has been advised of
the possibility of such damages and regardless of whether any remedy fails of its
essential purpose.
Installation in accordance with this manual, applicable codes, and the instructions
of the authority having jurisdiction is mandatory.
The customer is responsible for testing and determining the suitability of this
product for specific applications. The customer is responsible for testing the
product at least once every three months.
While every precaution has been taken during the preparation of this manual to
ensure the accuracy of its contents, Interlogix assumes no responsibility for
errors or omissions.

ChallengerPlus Installation and Quick Programming Manual iii
Regulatory requirements for New Zealand
Some parameters required for compliance with Telecom’s Telepermit
requirements are dependent on the equipment (PC) associated with this device.
In order to operate within the limits for compliance with Telecom’s Specifications,
the associated equipment shall be set to ensure that:
•There shall be no more than 10 call attempts to the same number within any
30 minute period for any single manual call initiation.
•The equipment shall go on-hook for a period of not less than 30 seconds
between the end of one attempt and the beginning of the next attempt.
•Automatic calls to different numbers are spaced such that there is no less
than 5 seconds between the end of one call attempt and the beginning of
another.
•This equipment shall not be set up to make automatic calls to the Telecom
‘111’ Emergency Service.
•The associated equipment shall be set to ensure that calls are answered
between 3 and 30 seconds of receipt of ringing.
Refer to the ChallengerPlus Programming Manual for details about programming
these parameters.

iv
Preface
This manual applies to the following ChallengerPlus control panels. The product
name “Challenger” will often be used in this manual for ChallengerPlus.
The ChallengerPlus Installation and Quick Programming Manual is for installation
technicians to install a Challenger panel.
Refer also to other Challenger manuals in the suite.
•The ChallengerPlus Programming Manual is for system administrators and
installers who need to manage the Challenger system via its
text-based user interface (in particular the “Install” menu”).
•The ChallengerPlus Users Manual is suitable for most users of the Challenger
system to perform everyday tasks.
•The ChallengerPlus Administrators Manual is for users and system
administrators who need to manage the Challenger system via its text-based
user interface (in particular the User menu).
Notes:
•The permissions assigned to you may not allow you to do everything
described in this manual. You may not be able to see all menu items
described in this manual.
•A qualified service person, complying with all applicable codes, should
perform all required hardware installation.

ChallengerPlus Installation and Quick Programming Manual 1
Product overview
Challenger is a scalable intrusion detection and access control system.
Challenger panels use one, and optionally a second, RS-485 data bus (LAN) to
provide continuous polling of remote arming stations (RAS) and data gathering
panels (DGP). These devices extend the system’s intrusion detection and access
control functions.
Refer to the ChallengerPlus Programming Manual for details.
Product contents
Table 1 below lists the items that are shipped with Challenger control panels.
Table 1: Challenger panel shipping list
Quantity
Item
1
Metal enclosure (with four spring standoffs fitted)
1
Challenger panel board
1
604 to RJ12 lead line, 1.5 m
1
ChallengerPlus Administrators Manual
1
ChallengerPlus Users Manual
1
ChallengerPlus Installation and Quick Programming Manual
1
16 Volt AC plug pack
1
Tamper switch
1
Tamper switch metal bracket
1
Ring terminal
5
M3 x 14 pan head screws
15
3-way plug-on screw terminal connectors
10
2-way plug-on screw terminal connectors
1
Red battery lead with QC terminal
1
Black battery lead with QC terminal
1
1K 1/4 watt resistor
40
10K 1/4 watt resistors
Inspect the package and contents for visible damage. If any components are
damaged or missing, do not use the unit; contact the supplier immediately.

2
Before you begin
This section contains items that govern the installation of many different
Challenger system devices (including but not limited to the Challenger panel).
When installing a Challenger panel, or any other parts of the system, you need to
be aware of requirements for cabling and earthing, and plan accordingly.
NOTICE! A qualified service person, complying with all applicable codes, should
perform all required hardware installation.
Disclaimer: This manual contains requirements based on Australia and New
Zealand codes. It is not an authoritative reference regarding codes and has not
been reviewed by the responsible authorities. The codes may change and may
not be reflected in this document.
Enclosure Access Restrictions
According to the requirements of AS/NZS 60950-1, the interior of the
enclosure presents hazards to general users and thus physical access
restrictions must be instituted ensure safety. To comply with the
requirements related to safety:
Access to the interior of the Enclosure must be limited to suitably
trained and qualified installation and maintenance technicians.
Access to the interior of the enclosure should require the use of a
tool.
These restrictions can be met by suitably securing the enclosure door as
follows:
Fit a lock to the enclosure. Ensure that it is always locked when not
under the immediate control of suitably qualified technicians.
Seal the enclosure door using standard head (non-knurled) screws,
firmly tightened.
When using finger operable screws (knurled head, etc) to seal the
enclosure door, tighten to 2Nm (typically >1/4 turn beyond the
finger tight point).
Cabling requirements
This section contains requirements for installers for the application and wiring of
Challenger equipment with respect to:
•System earthing
•RS-485 data cable (LAN) cabling
•Power supply from LAN or from external 12 V supply

ChallengerPlus Installation and Quick Programming Manual 3
System earthing
The following requirements are essential to the reliable operation of the
Challenger system.
•Each device’s GND link (if applicable) must be removed.
•Connect the earth conductor from the 240/16 VAC plug pack earth to the
Challenger panel’s earth terminal (Figure 5 on page 11, item 3).
•Some Challenger devices have an earth lug (or stud) on the PCB and are
fitted with a link labelled “GND” or “EARTH”. In such cases, the device’s GND
or EARTH link must be removed. When configured correctly, there will be a
resistance value greater than 100 kΩ between the device’s earth lug (or stud),
or power earth terminal (similar to Figure 5 on page 11, item 3), and any “C”
or “0V” terminal on the device.
•Install LAN isolation devices between multiple buildings and maintain
independent earthing systems. For example, use TS0893, TS0894, or
TS0896 Isolation Interface modules to provide electrical isolation and/or to
extend distance.
Earthing of one cabinet containing several devices. All devices designed for
the system have earth connections via metal studs to the metal housing. Take
care that these metal studs have a good connection to bare metal (no paint).
Earthing of panels in a single building. In a single building several cabinets or
devices are earthed. A licensed electrician should check the integrity of the
building earth system.
Earthing of panels in more than one building. If the wiring extends to separate
buildings, use more than one common earth system. Install LAN isolation
devices, such as TS0893, to isolate the system LAN between buildings to protect
the system against differences in earth potential. See Figure 3 on page 7.
Guidelines for retrofitting a Challenger V8 system
When replacing a Challenger V8 panel with a ChallengerPlus panel in an existing
installation:
•Where used, a device’s GND or EARTH link must be removed (if fitted).
Note: ChallengerPlus panels do not have a GND link.
•Where 240/16 VAC plug packs are used, connect the earth conductor to the
device’s power earth terminal (similar to Figure 5 on page 11, item 3).
•Connect one end only of the RS-485 data cable shield to a device’s LAN
earth terminal or earth lug (similar to Figure 5 on page 11, item 1).
•All other wiring compliant with Challenger V8 earthing via a Communications
Earth Terminal (CET) may remain unchanged.
Guidelines for new Challenger installations
When installing a Challenger panel in a new installation, follow the wiring
requirements of this manual including:

4
•Where used, a device’s GND or EARTH link must be removed (if fitted).
Note: ChallengerPlus panels do not have a GND link.
•Where 240/16 VAC plug packs are used, connect the earth conductor to the
device’s power earth terminal (similar to Figure 5 on page 11, item 3).
•Connect one end only of the RS-485 data cable shield to a device’s LAN
earth terminal or earth lug (similar to Figure 5 on page 11, item 1).
•Connections to building earth via CET are no longer required.
Note: For new installations the earthing and configuration instructions in this
manual supersede all previously-released installation instructions supplied with
other devices (unless otherwise noted).
RS-485 LAN cabling
The cabling requirements for an RS-485 system LAN are:
•Use 2-pair twisted shielded data cable such as Belden 8723.
•In each segment of LAN cabling, connect one end only of the data cable
shield to a device’s LAN earth terminal. Join data cable shields where cable
extends past a device that doesn’t have a LAN earth connection.
•The length of the LAN cable run should not exceed 1.5 km, unless LAN
isolation devices are used to extend the distance.
Power supply to RS-485 LAN devices
Devices on the LAN may be supplied from the panel’s or DGP’s + and –LAN
power terminals. Use an external 12 V power supply (such as TS0073 2 A Power
Supply) when:
•The device is more than 100 m (data cable length) from the panel
•Electrical isolation is required
•More power is needed than can be provided by the LANs
When powering a LAN device from an external 12 V power supply:
•Connect the external power supply’s ‘+’ terminal to the device’s ‘+’ terminal.
Do not connect the power supply + to the LAN +.
•Connect the external power supply’s ‘-’ terminal to the device ‘-’ terminal.
•Connect the LAN cable black wire ‘-’ to the device ‘-’ terminal.

ChallengerPlus Installation and Quick Programming Manual 5
Figure 1: RS-485 LAN 1 or LAN 2 and earth system block diagram

6
Figure 1 legend
Item
Description
1.
RS-485 LAN cable. We recommend the use of 2-pair twisted shielded data cable such as
Belden 8723 for optimal performance.
2.
Join data cable shields where cable extends past a device that doesn’t have a LAN earth
connection.
3.
In each segment of LAN cabling, connect one end only of the data cable shield to a
device’s LAN earth terminal.
4.
External 12 VDC power supply (if needed).
5.
Do not connect the + from the external 12 VDC power supply to the + of the LAN.
6.
Terminate the control panel and the most distant device, or the devices at the ends of the
two longest LAN cable runs, as applicable.
7.
The RAS earth point should typically be connected to the data cable shield. Alternatively,
it may be connected to building electrical earth (for example, if mounting to an earthed
metal fixture).
System configurations
A Challenger LAN may be configured in a variety of ways:
•Straight LAN, where the Challenger panel is at one end of a LAN cable run
•Star LAN, where multiple LAN cable runs are used in a branched
configuration
•Multi-building, where the LAN extends to more than one building
LAN 1 is required and LAN 2 is optional. Each LAN must be independently
configured and terminated.
Straight LAN
In a straight configuration (Figure 1 on page 5), the Challenger panel is at one
end of the LAN cable run and all other devices are connected to the LAN cable.
The termination would be ON for the Challenger panel and for the last device on
the LAN.
Star LAN
In a star configuration, the LAN has at least two branches (Figure 2 on page 7)
optionally connected via a TS0844 Power Distribution Board (see “TS0844
Power Distribution Board” on page 8). The termination would be ON for the two
devices at the ends of the two longest cable runs.
Note: A star LAN configuration may consist of a number of cable runs
(branches). LAN termination should be ON only at the devices at the far ends of
the two longest branches. A star LAN that has multiple branches in excess of 100
m may need to use LAN isolation devices such as TS0893 LAN Isolation
Interface modules to isolate the LAN segments that do not have LAN termination
set to ON.

ChallengerPlus Installation and Quick Programming Manual 7
Figure 2: Star LAN configuration
Multi-building or long-distance LAN cabling
If the RS-485 LAN extends to more than one building, each building must have
its own earth system. LAN isolation devices, such as TS0893 LAN Isolation
Interface modules, are used to isolate the system LAN between buildings to
protect the system against differences in earth potential.
Figure 3 below shows the use of two TS0893 modules to extend the RS-485 LAN
across two electrical installations. Each TS0893 module has a pair of termination
links, used to terminate (if applicable) the LAN segment on each side of the
module’s isolation barrier.
Figure 3: RS-485 LAN cabling between two buildings

8
Figure 3 legend
Item
Description
1.
LAN segment 1 extends from the Challenger panel to one side of the TS0893 LAN
Isolation Interface. Termination is ON at the panel and the panel’s side of the TS0893.
Maximum cabling distance for segment 1 is 1500 metres.
2.
LAN segment 2 extends from the TS0893 in building A to the TS0893 in building B.
Termination is ON at both TS0893 modules. Maximum cabling distance for segment 2 is
1500 metres.
3.
Earth point on Challenger panel connected to building earth via plug pack earth wire
(green).
4.
Earth point on remote device connected to building earth via plug pack earth wire (green),
or earth wire from local power supply.
5.
Plastic-body LAN device. Join data cable shields where cable extends past a device that
doesn’t have a LAN earth connection.
Using LAN devices to facilitate cabling
Various LAN devices may be used to provide electrical isolation and to reduce
cabling costs. LAN isolation devices can also be used to extend the distance of
LAN cabling beyond what can be achieved by a single cable run of 1.5 km. LAN
devices include the following:
•TS0844 Power Distribution Board. The TS0844 module can be used in
either data or power mode, as set by a pair of onboard links. The TS0844
module expands the number of physical connections that can be made to the
panel’s power or data output terminals.
•In data mode, each TS0844 module provides five sets of LAN out
connections and five sets of + and –auxiliary power output terminals.
•In power mode, each TS0844 module provides 10 sets of + and –auxiliary
power output terminals.
A TS0844 module is shown in Figure 2 on page 7.
•TS0893 LAN Isolation Interface. Provides an optical isolation barrier
between components on a Challenger (or Intelligent Access Controller) LAN.
The TS0893 can be also used as a LAN repeater; with up to three stages
cascaded together to increase the maximum LAN cabling run from 1.5 km to
6 km. TS0893 modules are shown in Figure 3 on page 7.
•TS0896 RS-485 to Fibre Optic Interface. A pair of TS0896 modules, with
suitable optical fibre cable, may be used to extend the LAN to remote
buildings or locations within a building (for example where unused optical
fibre cable already exists).
•TS0098 Challenger IP LAN Adaptor: Multiple IP LAN Adaptor modules
enable Challenger LAN data to be carried over an IP network and to be
converted back to RS-485 communications for connection to LAN devices.
Visit the Interlogix Web site at www.interlogix.com.au for details and images of
LAN devices.

ChallengerPlus Installation and Quick Programming Manual 9
Installing the control panel
See Figure 4 below for overall details of a TS-CHPLUS ChallengerPlus panel
installed in a TS0307 Universal Enclosure.
Figure 4: Challenger panel board mounted in enclosure (models TS-CHPLUS)
Figure 4 legend
Item
Description
1.
Enclosure mounting points
2.
Board mounting points
3.
Location of tamper switch
Installation guidelines
Challenger panels are designed, assembled and tested to meet the requirements
related to safety, emission and immunity with respect to environmental electrical
and electromagnetic interference, as of current relevant standards.
In addition to the general installation guidelines, installers must adhere to any
country dependent requirements of local applicable standards. Only a qualified
electrician or other suitably trained and qualified person should wire to and
provide General Purpose Outlets (GPO) or attempt to wire to the Public Switched
Telephone Network (PSTN).

10
The general installation guidelines are as follows:
•Mount the unit using screws or bolts through the four mounting holes in the
base. Ensure that the unit is mounted on a flat, solid, vertical surface so that
the base will not flex or warp when the mounting screws or bolts are
tightened.
•Allow 50 mm clearance between the equipment enclosures mounted side by
side, and 25 mm between the enclosure and any side wall or ceiling.
•ChallengerPlus panels are powered and earthed via a 16 Volt AC plug pack.
•A power outlet (GPO) must be in proximity to the panel. Only qualified
Electricians should provide a GPO.
•The Challenger panel has an onboard dialler. Telephone connections must be
in proximity to the panel. Only ACMA Cablers should provide telephone
cabling.
•If the upper and/or lower cabinet entry cable holes are used to route wiring
into the control panel, always use a proper pipe fitting system by means of an
appropriate conduit and junction box. For this purpose, use only materials of
suitable flammability class.
•Avoid loops of wire inside the control panel cabinet and route cables so that
they do not lie on top or underneath the printed circuit board. The use of cable
ties is recommended and improves neatness of the wiring within the box.
•The battery used with this unit must be made of materials of suitable
flammability class (HB or better).
•Install equipment in a clean environment and where environmental conditions
are within the range specified in the product data sheet.
Installation procedures
A Challenger panel may need to be fitted with various add-on modules and
interfaces. See each product’s installation instructions for details.
Note: Expander modules must not be fitted to a powered Challenger panel.
Remove power before plugging an expander module onto the Challenger PCB.
To mount the Challenger enclosure:
1. Fix the enclosure to the wall via the enclosure’s four mounting holes (for
example, Figure 4 on page 9, item 1).
Make sure the enclosure is level, and the tamper switch (item 3) location isn’t
sitting over a line of mortar if you’re installing the enclosure on a brick wall.
To mount the tamper switch:
The two-way tamper switch detects removal of the cover from the enclosure,
and removal of the enclosure from the wall.
1. Insert the tamper switch into its metal bracket.

ChallengerPlus Installation and Quick Programming Manual 11
2. Insert the bracket with tamper switch into the 1 cm slot on top left-hand side
of the enclosure (for example, Figure 4 on page 9, item 3).
To mount the Challenger board to the enclosure:
1. Remove the Challenger board from its antistatic bag.
2. Use M3 x 14 pan head screws to fix the Challenger board to the enclosure’s
standoffs (for example, Figure 4 on page 9, item 2).
3. Slide the board’s terminal connectors together and mount them to the board.
Board details
See Figure 5 below for the TS-CHPLUS ChallengerPlus panel.
Figure 5: Model TS-CHPLUS board details

12
Figure 5 legend
Item
Description
1.
Connect one end of each LAN cable shield to the ring terminal and fasten with M3 screw
to the Challenger panel board’s LAN earth terminal.
2.
Connect the power terminals to a 16 Volt AC plug pack. Maximum current drawn by the
panel with no peripheral devices connected is approximately 200 mA.
3.
Connect the power earth terminal to the plug pack earth wire.
4.
Connect the + and –terminals to a 12 V sealed lead acid battery (7.6 Ah recommended),
not supplied.
Note: A battery must be connected in order to use internal or external siren speakers.
–Both 8 ohms and 12VDC
5.
Connect the + and –auxiliary power output terminals to devices that require 12 Volt DC
power, such as detectors. See “Auxiliary power terminals” on page 15.
6.
Connect the D+ and D–terminals to the RS-485 data cable for LAN 1.
If the + and –terminals are used, consider the current draw as part of the auxiliary power
output. See “Auxiliary power terminals” on page 15.
7.
Input and common terminals for panel tamper switch (supplied). Short circuit for sealed,
open circuit for unsealed. Must be sealed if not used. Can only be used with normally
closed contacts such as the panel tamper switches.
8.
Connect the S+ and S–terminals to an external 8 siren speaker or external device that
requires 12 Volt DC power. If an external device is not used, connect the S+ and S–
terminals to a 1K 1/4 watt resistor (supplied).
The maximum current draw for the external 8 siren and the strobe is 700 mA.
Current draw for external 12 VDC device for DC Volt mode is maximum 700mA and for
Standard Siren Mode is 2 8 ohms speakers.
The internal and external siren speaker outputs are relay 16 and are mapped to event
flag 1.
9.
Connect the S+ and S–terminals to an internal 8 siren speaker or internal device that
requires 12 Volt DC power.
If an internal device is used, consider the current draw as part of the auxiliary power
output. See “Auxiliary power terminals” on page 15.
10.
Connect the + and –terminals to the strobe. The maximum current draw for the external
8 siren and the strobe is 700 mA. The strobe output is relay 2 and is mapped to event
flag 2.
11.
Connect the D+ and D–terminals to the RS-485 data cable for LAN 2 (if required).
If the + and –terminals are used, consider the current draw as part of the auxiliary power
output. See “Auxiliary power terminals” on page 15.
12.
Zone input terminals. See “Zone inputs” on page 16.
13.
RJ-12 socket to telephone system (dialler). See “Telephone connection” on page 20.
14.
Slot for SD card.
15.
100BT LED on when Ethernet speed is 100 Mbps.
16.
Ethernet port.
17.
Link Active LED flashes to indicate Ethernet activity.
18.
J18 USB port for “Type A Male to Type B Mini Male” or “Type A Male to Type B Micro
Male” cable (depending on board revision number).

ChallengerPlus Installation and Quick Programming Manual 13
Item
Description
19.
Transmit and receive LEDs to indicate activity on the serial port (J15).
Tx0 transmit LED flashes to indicate data being sent from the Challenger to a device
connected to J15 (serial port) and is on solid when J15 is ready (inactive).
Rx0 receive LED flashes to indicate data being received from device connected to J15
(serial port).
20.
J15 terminals (also called STU port) for RS-232 serial connection to computer. See “J15
serial port” on page 20.
21.
J14 10-way cable socket for TS0840, TS0841, TS0842, or TS1041 relay or output
expansion modules.
Note: The J14 connector can provide power to one relay controller. If connected to a
device that will be powered from an auxiliary power supply (not powered by the
Challenger panel), then you must ensure that the +12V wire is not connected.
22.
Test links 1 and 2. Both links are used when updating firmware (see “Error! Reference
source not found.” Error! Bookmark not defined.).
Link 1 is used when resetting the master installer code (“Restoring the default installer
PIN” on page 28) and for defaulting the panel (“Clearing the memory via the Challenger
panel PCB” on page 26).
23.
LED 1 flashes slowly to indicate panel operation, and flashes quickly during firmware
update or panel default.
24.
Transmit and receive LEDs to indicate activity on LAN 1.
Tx1 transmit LED flashes to indicate the Challenger panel is polling remote units (RASs
and DGPs) on LAN 1. The Tx1 LED should always be active.
Rx1 receive LED flashes to indicate remote units on LAN 1 are replying to polling.
25.
TERM link for LAN 1. See “RS-485 LAN” on page 15.
26.
Transmit and receive LEDs to indicate activity on LAN 2.
Tx2 transmit LED flashes to indicate the Challenger panel is polling remote units (RASs
and DGPs) on LAN 2. Tx2 flashes quickly for 1 second each minute when nothing is
polled on LAN 2.
Rx2 receive LED flashes to indicate remote units on LAN 2 are replying to polling.
27.
TERM link for LAN 2. See “RS-485 LAN” on page 15.
See Figure 6 on page 14 for connection details for terminal blocks J1 to J5.

14
Figure 6: Connection details for terminal blocks J1 to J5
Application notes
16 VAC plug pack
•Use the 16 VAC plug pack supplied with the Challenger panel.
•When installing plug packs, do not power the unit until you have terminated all
necessary wires and checked that you do not have a short circuit. Fused plug
packs cannot be replaced under warranty as the fuse operation can only be
caused by a direct short circuit.
12 V Battery
The Challenger panel should be connected to a 12 V 7.6 Ah battery compliant
with AS/NZS 2201.1:2007, Appendix C.
The batteries must have a nominal terminal voltage of 12V and must have an
initial charging current limit >1.5A.
Table of contents
Other TECOM IP Access Controllers manuals
Popular IP Access Controllers manuals by other brands

ACT
ACT ACTPRO 3000 ACCESS CONTROL UNITS Operating and installation instructions

Rosslare
Rosslare AC-425 Hardware installation and user's guide

H3C
H3C WX Series Registration and activation guide

Idemia
Idemia VisionPass installation guide

Idemia
Idemia MorphoWave Compact installation guide

SECO-LARM
SECO-LARM ENFORCER SLI SK-B141-PQ Quick installation

Digiplex
Digiplex Paradox ACM12 Installation instructions and instructions for use

urmet domus
urmet domus Alpha 1168 instruction manual

Stanley
Stanley PAC iPAC quick start guide

MVC-Data
MVC-Data AccessZone GC501 user manual

Inokey system
Inokey system BT 502 user manual

Roger
Roger MCT82M-IO-CH installation manual