- relay («Relay 1», «Relay 2», «Relay 2» terminals) with maximal switching
voltage 100V, mA, max..............................................................................................................100
«+12V»output loading current, mA......................................................................................750+50
«+12V»output short-circuit current, mA, max..............................................................................40
«+12V»output voltage ripple, mV, max .....................................................................................100
BAT-powered operating time in stand-by mode (without
outer load powering), h, min
- Astra-712/4................................................................................................................................48
- Astra-712/8................................................................................................................................36
Battery discharge indication voltage
(without mains voltage), V..................................................................................................11,5±0,3
Battery voltage whereby device is switched to «sleep»mode
(without mains voltage), V..................................................................................................10,5±0,3
Battery voltage whereby device is turned OFF
(without mains voltage), V..................................................................................................10,0±0,3
Zones Parameters («Zone-x», «GND» terminals):
Zone terminal voltage in stand-by mode, V...................................................................from 9 to 14
Zone short circuit current, mA, max .............................................................................................20
Zone Integration time, ms:
- intrusion ..............................................................................................................................70+10
- fire.....................................................................................................................................300+30
Zone wiring resistance (not including remote element), Ohm, max:
- intrusion ..................................................................................................................................220
- fire...........................................................................................................................................150