GATEWAY ANALOG OUTPUTS
13
INSTALLATION GUIDE PLUS WGW420
01 Follow steps 06 and 07 of the PLUS Wireless Gateway Configuration.
02 In Tekon Configurator Software select PLUS >> Gateway >> Analog Outputs menu
2
1
3
NOTE:
Transmitter analog input 1 data is received and stored at the Gateway Modbus address [9].
03 Considering the transmitter configuration with GTW Modbus Index=1, there is a Gateway Modbus Address
Window corresponding to Modbus address window [0-19].
MB Add
0
19
HOLDING REGISTERS - TRANSMITTERS DATA
Description Address
Serial Number (Transmitter Modbus Index-1) x 20+0
Transmitter Model (Transmitter Modbus Index-1)x20+2
RSSI (Transmitter Modbus Index-1)x20+3
Communication Period (Transmitter Modbus Index-1)x20+4
Elapsed Time (Transmitter Modbus Index-1)x20+5
Power Voltage (Transmitter Modbus Index-1)x20+6
Data 0 (Transmitter Modbus Index-1)x20+7
Data 1 (Transmitter Modbus Index-1)x20+9
Data 2 (Transmitter Modbus Index-1)x20+11
Data 3 (Transmitter Modbus Index-1)x20+13
Data 4 (Transmitter Modbus Index-1)x20+15
FW Version Major Minor (Transmitter Modbus Index-1)x20+17
FW Version Revision (Transmitter Modbus Index-1)x20+18
HW Version Major Minor (Transmitter Modbus Index-1)x20+19
9
(Transmitter Modbus Index-1)x20+9(Transmitter Modbus Index-1)x20+9(Transmitter Modbus Index-1)x20+9