manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Tektronix
  6. •
  7. Power Supply
  8. •
  9. Tektronix PS 503A User manual

Tektronix PS 503A User manual

OOilAAN7TED
TD
D~L
.LEIVCE
~S
503
®tJAL
~~

E~
SUPPL
Y
INSTRUCTION
MANUAL
Tektronix,
Inc
.
P
.O
.
Box500
Beaverton,
Oregon
97077

Serial
Number
070-1834-01

First
Printing
SLPT
1974
Page
SECTION
1

OPERATING
INSTRUCTFONS

1-1
SECTION
2
,
;

SPECIFICATION
AND
PEFIFORMANCE
CHECK

2-1
The
remaining
portion
of
this
Table,of
Contents
lists
servicing
instructions
that
expose
personnel
to
hazardous
voltages
:
These
instructions
are
for qualified
service
personnel
only
.

s
SECTION
3

ADJUSTMENT
SECTION
4

MAINTENANCE
AND
INTERFACING
INFORMATION

4-1
SECTION
5

CIRCUIT
DESCRIPTIpN
±
.=

-

5-1
SECTION
6"

REPLACEABLE
ELECTRICAL
PARTS
LIST

6-1
OPTIONS
'SECTION
7

DIAGRAM
AND
CIRCUIT
BOARD
.ILI
.USTRATION
.

7-1
SECTION
8

REPLACEABLE
MECHANICAL
PARTS
LIST
AND
EXPLODED
VIEW

8-1
CHANGE
INFORMATION
WARNING
TABLE
OF
CONTENTS
PS
503A
Fig
.
1-1
.
PS
503A
Dual
Power
Supply
plug-in
module
.
INTRODUCTION

diode
as
well
as
a
dimming
of
the
VOLTS
indicator
light
if
the
supply
output
voltage
is
above
approximately
10
V
.
These
functions
are
easily
verified
by
momentarily
shor-
Description

ting
the output
of
the
supply
.
The
PS
503A
is
a
dual
0 to
20
V
do
constant-voltage,
current-limited,
floating
power
supply
.
It
is
designed
to
operate
in
the
high-power
compartment
of
the
TM
504
or
TM
506
Power
Module
.
In
the
high-powercompartment,
it
provides a
floating
dual
Oto
20
Vdc
at
1
.0
A
.
Operating
in
a

installation
and
Removal
standard
compartment
of
a
TM
500
Series
Power
Module,
the
PS
503A
supplies
a
floating
dual
0
to
20
V
do
at
400
mA
.

c~~
The
supply
is
designed
for
conveniently
powering
complementary
and
linear
integrated
circuits
such
as
operational
and
differential
amplifiers
as well
as
differen-
tial
comparators
.
A
ground
referenced
+5
V
auxiliary
supply
(suitable
for
bipolar
logic,
light-emitting
diodes,
incandescent
displays
and
similar
applications)
is
also
included
.
With the
floating
supply
available for
powering
discrete
interface
circuits
and
level
shifting,
the
PS
503A
can
be
used
for
many
digital/analog
applications
.
The
plus
and
minus
outputs
from
the dual
floating
power
supplies
are
independently
variable
or
bo
variable-at
a
constant
ratio
by
a
common
controi
Ea
,
.~
.

,--
;
.-
/align
`the
PS503A
chassis
with
the
upper
and
lower
supply
provides
dither
a
plus
or'mir~us
0to 20
V
do
with

`guides
of
the
selected
compartment
.
Push
the
module
in
respect
to
the
common
terminal,
By
connecting
across
the

and
press
firmly to
seat
the
circuit
board
in
the
inter
plus
and
minus
terminals,
the
PS503A
can
provide
0
to

connecting
jack
.
40
V
dc
.
Either
terminal
may
be grounded
or
floated
to
350
V
(dc
+
peak
ac)
.
Each
supply
also features
con-
tinuously
variable
current
limiting
from
less
than
50
mAto

To
remove
the
PS
503A,
pull
on
the
release
latch
400
mA
(standard
compartment)
or
1
A
(high
power
compartment)
at
both
20
V
and
40
V
output
.

located
in
the
lower
left
corner,
until
the interconnecting
jack
disengages
and
the
PS
503A
will
slide
out
.
The
presence
and
variability
of
the
output
voltage
is
verified
by
the
VOLTS
indicator
light
on
the
front
panel
.
The
brightness
of
this
light
varies
with
output voltage
.
A
panel-mounted
light-emitting
diode
(LED)
indicates
when

Controls
and
Connectors
the
PS
503A
is
operating
in
a
standard
compartment
of
a
TM
500
Series
Power
Module
and
the
output
current
is

Refer
to
Fig
.
1-3
.
Even though
the
PS
503A
is
fully
limited
to
a
maximum
of
400
mA
.
Other
panel-mounted,

calibrated
and
ready
to
use,
the
functions
and
actions
of
light-emitting
diodes
indicate
when
either
the
+
or
-

the
controls
and
connectors
should
be
reviewed
before
supply
goes
into
current-limiting
.
Hard
limiting
is
in-

attempting
to
use
it
.
Press
the
OUTPUT
button
to
apply
dicated
by
maximum
brightness
of
the
light-emitting

power
to
the
PS
503A
.
REV
.
CMAR
1977
CAUTION
Section
1-PS
503A
OPERATING
INSTRUCTIONS
Turn the
power
module
off
before
inserting the
plug-
in
;
otherwise,
damage
may
occur
to
the
plug-in
circuitry
.
Because
of
the high
current
drawn
by
the
PS
503A,
it
is
also
recommended
that
the
power
module
be
turned
off
before
removing
the
PS
503A
.
Refer
io
Fig
.
1-2
.
.
Check
to
see
that
the
plastic
barriers
on
the interconnectingjack
of
theselected
power
module
compartment
match
the
cut-outs
in
the
PS
503A
circuit
board
edge
connector
.
OperatingInstructions-PS
503A
Load
and
Monitor
Connections
POWER
MODULE
~~
rrier
Improper
connections
between
the
power-supply
out-
put
and
the
load
(s)
or
monitoring
devices)
are
a
common
cause
of errors
.
Multiple
loadsor
monitoring
devices
must
be
connected
directly
to
the
output
terminals
with
separate
pairs
of
leads
as
shown
in
Fig
.
1-4
.
Avoid
using
clip
leads,
since
their
contact
resistance
can
exceed
the
output
impedance
of
the
PS
503A
and
cause
significant
measurement
error
.
Fig
.
1-2
.
Plug-in
module
installation/removal
.
Bottom
Groove
PLUG-IN
Groundedand
Floating
Operation
OPERATINGCONSIDERATIONS
The
PS
503A
is
a
+
and
-20
V
"floating"
supply
since
no
internal
connections
are
made
to either
the
chassis
or
Overheating

ground
.
The
supply
can
thus
be
used
as
a
positive
or
The
PS
503A
is
designed
to
operate
at
~n
ambient

negative
supply
by
simply,
connecting
between
the
com-
fAmr
"
Qrature
from
0°G
to
+5G"C
.
~lowever,
when

mon
and
the
negative
or
positive
uutpur
terminal
.
operating
saveral
power
supplies
in
a
rpe~?
;
i-p!ug-in
pow~
.
"

However,
there
may
bs
:
:
:,desirable
effects
caused
by
module,
especially
at
low
output
voltages,
or
when

grounding
the
supply
to
the
chassis
while
the
load
is
operating close
to
other
heat-producing
equipment,
inter-

grounded
at
some
point
removed
from
the
supply
chassis
.
nal
temperature
may
exceed
safe
limits
and
actuate a

Forexample,
if
a
remote
load
is
connected
as
shown
in Fig,
thermal cutout
in
the
power
module
.
Refer
to
the
power

1-5
.
ground
currents containing
the
power-line
frequency
module
instruction
manual
for
more
complete
informa-

could
result
and
create
excessive noise
and
ripple
in
series
tion
.

with
the
load
.
Thus,
floating
operation
is
recommended
to
ensure
against
problems
caused
by
undersirable
ground
currents
.
ReverseCurrent
Loading
In
some
bias
supply
and
digital
circuitry
applications
the
load
might
behave
as a
current
source
for
part of
its
operating cycle
.
Since
the
output
circuit
of
a
series-
regulated
supply
is
unidirectional,
current
will
not
pass
in
the opposite
direction
except
through
undesirable paths
.
The
internal
reverse-current
diodes
conduct
only
when
the
PS
503A
terminal
voltage
reverses
and
therefore
will
not
work
when
the
voltage
is
correctly
polarized
.
Connec-
REV
.
A
MAR
1977
4p0
mA
LIMIT
Indicator
Light
emitting
diode
in-
dicates
whenPS
503A
is
installed
in
a
'standard
compartment
of
a
power
module,
limiting
the
current
output
.
VOLTS
Controls
and
Indicators
Variable
coarse
and
tine
controls
provide
con-
tinuously
variable
+
or-
voltage
election
from
the
respective
0-20
voli
supply
The
presence
and
variability
of
output
voltage
is
verified
'by
voltage
indicalor
lights
(OUTPUT
button
pressed)
.
Brightness
of
lights
varies
with
output
voltage
:
REV
.
B
MAR
1977
Floating
Output
Terminals
Fig
.
1-3
.

PS
503A
controls
and
connectors
.
5-way
binding
post
ter-
minals
that
provide
either
a
positive
0-20-
volts
between
the
binding
post
on
the
right (red)
and
t
:OMMON,
or
a
negative
t)-20
volts
between
the
binding
past
on
the
left
(green)
and
COMMON
.
When
the
PS503A
is
in-
stalled
in
he
high
power
compartment
of
aTM
504
or
TM
506
power
module
that
has a
high
;
power
compartment,
tt
e
current
available
at
either
the
r
or
- outputs
is
from
less
than
`
100
mA
to at
least
1
A
:
When
the
PS
503A
is
compartment,
the
current

Output
Terminals
available
is
from
ess
than
100
mA
`to

at
`least

5-way
binding-posttermi-
400
mA
.
0
to
4Q
volt
out-

nals

that

provide

a
put
s'obtained'
between

ground-referenced
+5
V,
the
+
and
-
output
ter-

1
A,
fixed
output
.
urinals
.
Operating
Instructions-PS
503A
VOLTS
DUAL
TRACKING
Control
When
pulled
out,
vanes
both
the'-1-'and
-
outputs
from
0
volts
to
he
value
set
on
the
+
and
-
VOLTS
controls
.'
The
-
ratio
be-
tween
the+and-outputs
is
maintained
throughout
the
range
of
the
VOLTS
DUALTRACKING
con-
trol
.
OUTPUT
Pushbutton
When
pressed,
applies
power
to
both
0-20V
binding
post
terminals
and
the
+5V
binding
post
terminal
.
CURRENT
LIMIT
Controls
and
Indicators
Continuously
variable
controls
that
select
the
and
-output
current
limit
.
Light-emitting
diode
in-
dicates'
when
hard
limiting
occurs
.
installed
in a
standard
_
1834-05
OperatingInstructions-PS
503A
NOTE
Supply
is
connected
for
20
to
40
V
output
.
Over-voltage
POWER
SUPPLY
AC
VOLT
+
METER
ting
a
shunt
resistor
(Rs)
as
shown
in
Fig
.1-6
provides an
external,
reverse-current
path
to
the
power
supply
sources
or
delivers
current
only
.
The
PS
503A
is
protected
from
over-voltageconditions
by
an
over-voltage
protection
circuit
that
shuts
down
the
power
supply
when
the voltage
rises
to
about
26
V
dc
.
POWER
I

I
ACTIVE
SUPPLY

LOAD
Rs
NOTE
Supply
is
connected
for
0
to
40
V
output
.
Fig,
t-4
.
Monitor
and
load
connections
.

Fig
.
1-4
.
Reversr
current
shunt
(Rs)
with
active
load
.
NOTE
The
point
at
which
the overvoltage
protection
blows
the
fuse
may
be
changed
forspeclfic
applications
by
changing
the
Zener
diode
.
OPERATION
The
following
steps
demonstrate
the
use
of
the
PS503A
controls
and
connectors
.
1
.
install
the
PS
503A
into'(preferably)
the
high-power
compartment
of
the
power
module
.
2
.
Press
the
OUT
button
to
apply
power
to
the
PS503A
.Observethatthe+and-VOLTSindicatoriights
come
on
(the
lights
will
be
very
dim
at
low
voltages)
._
Single
Supply
Operation
(t20
V
Maximum)
1
.
Set the
+
and
-
VOLTS
controls
for
approximately
2
V
.
2
.
Turn
the
CURRENT
LIMIT
controls
fully
ccw
(to
NOTE

protect
the
ammeter)
.
Connect
an
ammeter
between
the
supply
is
connected
for
o
to
ao
v
output
.

common
terminal
and
the
+
or
-
terminal
and
adjust
the
appropriate
CURRENT
LIMIT
control
for
the
maximum

)
Fig
.
1-5
.
Ground
loop
created
by grounded
remote
lead
.

desired
current
output
.
REV
.
A
MAR
1977
3
.
Removethe
ammeter
.
Connect
the
load
between
the

Stair-Step
Operation
common
terminal
and
the+or-terminal
.
Adjust
the+or

The
PS
503A
can
be operated
to
provide
a
"stair-step"
,~

-
VOLTS
control
for
the desired
output
.

output
characteristic
by
choosing
certain
load
limits
and
control
settings
.
Forexample,
Fig
.1-7showsthestair-step
output
from
the
PS
503A
when
a
variable
load
(RL)
is
connected
between
the
+
and
-
output
terminals
.
With
each
supply
set for
maximum
voltage
and
current
(40
V,
y

1
A) theoutput
voltage
remains
constant
from
open
circuit
Combined
Supply
Operation
(40
V
Maximum)

~

until
the
load
reachesapproximately
40
S2
as
illustrated
by
1 .

Set the
+
and
-
VOLTS
control
for
approximately

the
solid
line in
Fig
.
1-7
.
At
this
crossover
point,
theoutput
j

2
V
and
turn
the
CURRENT
LIMIT
controls
fully
ccw
(to

voltage
decreases
with the
load
and
the output
current
is
protect
the
ammeter)
.

limited
at
1
A
.
Therefore,
below
approximately
40
S2,
both
supplies
act as
current
sources
with
output
voltage
variable
with
the load
.
Since
both
supplies
are
set
for
the
'

2
.
Connect
an
ammeter
between
the
+
and
-
ter-

same
output
voltage,
each
supply
shares equally
in
the
urinals
.
First
adjust
one
CURRENT
LIMIT
control
for
the

Power
output

I
Z
R
.
If
one
supply
is
set
for
a
lower
output
maximum
desired current
output
;
then
adjust
the
other

voltage
than the
other,
output
power
is
shared
at
the
same
CURRENT
LIMIT
control
until
the
CURRENT
LIMIT

ratio
as
the output
voltage
.
indicator
just
reaches
maximum
brightness,
i
.e
.,
both
1

supplies
at
the
same
CURRENT
LIMIT
setting
.
3
.
Remove
the
ammeter
.
Connect
the
load
between
the
+
and
-
terminals
and
set
the
+
and
-
VOLTS
controls
so
that
both
settings
added
togetherequal
thedesired output
voltage
.
(See
Dual-Tracking
Operation
for
varying
the
output
with
the
VOLTS
DUAL
TRACKING
control
.)
Dual-Tracking
Operation
When
pulled
out,
the
VOLTS
DUAL
TRACKING
control
varies
the output
of
both
supplies
at
a constant
ratio
from
zero
to
the value
set
on
the
+
and
-
VOLTS
controls
.
For
example,
if
the
+
and
-
VOLTS
controls
are
set for
maximum
output (approximately 20
V),
both
outputs
can
be
varied
from
zero
to
20
V
with
the
VOLTS
DUAL
TRACKING
control
(1
:1
ratio)
.
Likewise,
if
one
supply
is
set for
10
V
and
the other
for
20
V,
each
1
V
change
in
the
10
V
output
will
be
matched
by
a2
V
change
in
the 20
V
output
(2
:1
ratio)
.

ao
Note
also that
no
matter
where
the
VOLTS
DUAL

I

w
j
30
TRACKING
control
is
set,
the
outputs
will
return
to
the

~

1
voltage
selected
by
the
+
and
-
VOLTS
control
when
the

~

20
0
VOLTS
DUAL
TRACKING
control
is
pushed
in
.
Therefore,

>
rapid
selection
of
two
preset
outputs
from each
supply
is

~

10
achieved
by
merely
switching the
VOLTS
DUAL

w
TRACKING
control
in
or out
.
REV
.
B
MAR
1977
Now,
by
setting
supplyEzforacurrentlimitof0
.5
Aand
varying the
load
over
the
same
range, the
supplies
act
as
constant-voltage
sources
until
the load
reaches
ap-
proximately
80
S2
.
At
that
crossover
point,
the
supply
set
for
0
.5
A
(Ez)
becomes
a
current
source
and
its
output
OperatingInstructions-PS
503A
!
o
9
0
When
the
+and
-
supplies
are
connected
as
described

I
~

Is
under
Combined
Supply
Operation,
the
VOLTS
DUAL

CURRENT
IN
AMPERES
TRACKING
control
will
vary
the
output
from
zero
to
the
value
selected
by the
+
and
-
VOLTS
controls
added

Fig
.
1-7
.
Output
characteristics
with
various
currents, voltages,
together
.

and
loads
.
OperatingInstructions-PS
503A
voltage
decreases
with
the
load
.
At
approximately
40
f2

Parallel-Connected
Supplies
and
20
V,
supply
Ez
no
longer
contributes
to
the
power
output
.
Subsequently,
supply
E,
supplies
all
the output

"""'
power
and
operates
as a
constant-voltage
source
with

CAUTION
output
current
variable
with
the
load
.
Then,
at
ap-
proximately
20
f2,
supply
E,
crosses over
and
becomes
a

Parallel
operation
is
not
recommended
unless
a
current
source
at
its
maximum
output
of
1
A
.
Thus,
by

forward biased
diode
capable
of handling
the
re-
choosing
the appropriate
load
limits
and
control
settings,

quired current
and
voltage
is
inserted
between
each
any
of
the
four
operating
characteristics
is
possible
.

power
supply
and
the
load
.
Failure
to
do
this
may
cause
power
supply
damage
.
A
second
stair-step
output
can
be
preselected
and
switched
in
or
out
with
the
VOLTS
DUAL
TRACKING

The
outputs
of
two
or
more
PS
503's
can
be
connected
control
(see
Dual-Tracking
Operation
for
details
on the

in
parallel
as
shown
in
Fig
.
1-9
to
obtain
an
output
current
function
of
the
VOLTS
DUAL
TRACKING
control)
.

equal
to
the
sum
of
theoutput
currents
from
each
supply
.
Each
supply
must
be adjusted
individually
to
obtain
the
desired output current
.
Series-Connected
Supplies
The
outputs
of
two
or
more
PS
503A's
can
be
con-
nected
in
series
as
shown
in
Fig
.
1-8
to
obtain
an output
voltage
equal
to
the
sum
of
the
output
voltages
from
each
supply
.
Each
supply
must be
adjusted
individually to
obtain
the
desired
output voltage
(see
Dual-Tracking
Operation
for
varying
the
output
of
both
supplies
with
the
VOLTS
DUAL
TRACKING
control)
.
One
supply
should
be
set for
the
desired
output
voltage
NOTE

and
the other
for
a
slightly
higher
voltage
.
The
supply
set
forthe desired voltage
will
then
become
a constant
voltage
The
PS
503A
has
internal
diodes
connected
across

source, while the
supply
with
the
higher voltage output
the
output
to
protect
the
series-connected
supplies

becomes
a
current
source
(due
to
automatic
crossover),
against
reverse
polarity
if
the load
is
shorted,
or
one

which
results
in
their
output
voltage
decreasing
to
that
of
of
the
supplies
is
not
on
.

the
supply
with
the
lowest
output
voltage
.
POWER
I

I
POWER
SUPPLY

SUPPLY
LOAD
NOTE
Each
supply
is
connected
for
0
to
80
V
output
.
NOTE
The
+
and
-
supplies
are
internally
connected
in
series
.
Therefore,
the
+
and
-
supplies
cannot
be
externally
connected
in
parallel
to
obtain
an
output
current
equal
to
the
sum
of
the
currents
from
each
supply
.
POWER

POWER
SUPPLY
I

I
SUPPLY
NOTE
Each
supply
is
connected
for
0
to
2A
output
.
Fig
.
1-8
.
Supplies
series-connected
.

Fig
.
1-9
.
Supplies
parallel-connected
.
REV
.
B
MAR
1977
SPECIFICATION
AND
PERFORMANCE
CHECK
Performance
Conditions
The
electrical
characteristics
are
valid
only
if
the
PS
503A
has
been
calibrated
at
an
ambient
temperature
between
+20°
C
and
+30°
C
and
is
operating
at
an
ambient
temperature
between
0°C
and
+50°C
unless otherwise
noted
.
Voltage
Outputs
Variable
Current
Limiting
Minimum
Resolution
ELECTRICAL
CHARACTERISTICS
Characteristics

Performance
Requirements

Supplemental
Information
SPECIFICATION
Table
2-1
Plus
and
Minus
20
V
Floating
Supplies
Less
than
100
mA
to
at
least
1
A
when
installed
in
a
high-power
compartment
.
Less than
100
mA
to at
least
400
mA
when
installed
in
a
low
power
compartment
.
50
mV
Section
2-PS
503A
Items
listed
in
the
Pertormance
Requirements
column
are
verified
by
completing
the
Performance
Check
in
this
manual
.
Items
listed
in
the
Supplemental
Information
column
are
not
verified
in this
manual
;
they are
either
explanatory
notes
or
pertormance
characteristics for
which
no
limits
are
specified
.
0V
(1100
mV)
to
at
least
20
V
do
(20
.1,
-
.1,
+
.4
V
dc)
with
re-
spect
to
common
terminal,
or
0
V
to at
least
40
V
do
across
the
plus
and
minus
terminals
.
Outputs
either
ind

bndently
variable
or both
variable
at
a
constant
ratio
of
a
common
control
(Dual
Tracking)
.
Maximum
limit
;
1
.5
A
Maximum
limit
;
600
mA
Specification
and
Performance
Check-PS
503A
Load
Regulation

Within
3
mV
with
a
1
A
load
change
.

I
Within
1
mV
with
a
400
mA
load
change
.
Line Regulation

Within 5
mV
for
a
t10%
line
voltage
change
.
Ripple
and
Noise

3
mV
peak-to-peak
or less
with
a

1
mV
peak-to-peak
or less
with
(2
Hz
to
2
MHz
instrument

1
A
load
.

a
400
mA
load
(noise
and
not
in
current
limiting
.)

ripple
increase
unpredictably
when
current
is
being
limited)
.
Temperature
Coefficent

~

~
0
.025%/°C
or
less
.
Stability

0
.1%
+5
mV
(or
less)
of
drift
in
8
hours
.
Line
voltage,
load
and
tem-
perature
held
constant
.
Supply
Isolation
from

I
350
V
(dc
+
peak
ac)
.
Ground
Dual Tracking
Mode

If
the
two
supplies
are
set
indepen-
Offset
Error

dently
to
any
given
voltage
ratio,
and
if
both
supplies
are then
monitored
and
varied
a
given
amount
(by using
the
VOLTS
DUAL
TRACKING
control),
the
two
supplies
will
maintain the
same
voltage
ratio
as
initially
set
within
50
mV
;
until
oric
supply
roaches
either
Qv
or
20
V
.
f
Output
Load
Regulation
Line Regulation
Ripple
and
Noise
(2
Hz
to
2
MHz)
LongTerm
Stability
Overload
Protection
2-2
Table
2-1 (cont)
Characteristics

~

Performance
Requirements

~

Supplemental
Information
Transient
Recover

~20
ps
for
a constant
voltage
to
recover
within
20
mV
for
a
nominal
output
voltage
after
a
400
mA
change
in
output
current
.
+5
V
Ground
ReferenceSupply
4
.75Vdcto5
.25Vdcwitha5ohm
load
.
Within
100
mV
with
a
1
.
A
load
change
.
Within
50
mV
for
a
±10%
line
volt-
age
change
.
5
mV
peak-to-peak
or less
with
a
1
A
load
.
Measured
at
a
temperature
be-
tween
+20°
C
and
+30°
C
.
Measured
at
a
temperature
be-
tween
+20°
C
and
+30°
C
.
0
.5%
or
less of
drift
.
Fixed
(automatic)
current
limiting
and
over-temperature
shutdown
.
REV
.
A,
AUG
.
1977
Temperature
Operating
Storage
Altitude
Operating
Storage
Vibration
Operating
and
Non-Operating
Shock
Operating
and
Non-Operating
Width
Length
Characteristics
Net
Weight
(Instrument
only)
Characteristic
Overall
Dimensions
(measured
at
maximum
points)
Height
Perf
o
rmance
Requirements

I

Suppl
emental
Information
0°
C
to
+50°
C
.
-40°
C
to
+75°
C
.
To
15,000
feet
.
To
50,000
feet
.
Table
2-2
ENVIRONMENTAL
With
the instruments
complete
and
oper-
ating,
vibration
frequency
swept
from
10
to
50
to
10
Hz
at
1
minuteper
sweep
.
Vibrate
15
minutes
in
each
of
the
three
major
axes
at
0
.015"
total
displace-
ment
.
Hold
3
minutes
at
any
major
re-
sonance,
or
if
none,
at
50
Hz
.
Total
time,
54
minutes
.
30
g's,
1/2
sine,
11
ms
duration,
2
shocks
in
each
direction
along
3
major
axes,
for
a
total
of 12
shocks
.
Table
2-3
PHYSICAL
Specification
and
Performance
Check-PS
503A
5
.0
inches
12
.7
cm
2
.6
inches
6
.6
cm
11
.75
inches
29
.7
cm
1
Ib
13 oz
821
grams
Information
Specification
and
Performance
Check-PS
503A
Introduction
This
procedurechecks
the
electrical
characteristics
of
the
PS
503A
that
appear
in
the
Specification
portion
of
this
section
.
Limits
and
tolerances
given
in
the
Supplemental
Information
column
are provided
for
user
and
service
information
only,
and
should
not
be
interpreted
as
re-
quirements
for
this
Performance
Check
.
The
electrical
characteristics
are
valid
only
if
the
instrument
has
been
calibrated
atan
ambient
temperature
between
+20°
C
and
+30°
C,
and
is
operated
at
an
ambient
temperature
between
0°C
and
+50°C
unless otherwise
noted
.
Special
test
devices are
used
where
necessary
to
Limits
and
tolerances
given
in
this
Performance
Check

facilitate
the
procedure
.
Most
of
these are
available
from
are
for
the instrument
under
test
and
do
not
include
test

Tektronix,
Inc
.
and
can
be
ordered
through
your
local
equipment
error
.
Limits
and
tolerances
in
this
procedure

Tektronix
Field
Office
or
representative
.
Performance
Description

Requirements

Application
Oscilloscope

Bandwidth,
do
to
2
MHz
;

Used
throughout
pro-
minimum
deflection
factor,

cedure
to
provide
1
mV/div
;
sweep
rate,

display
.
10 ms/div
to
1
~s/div
.
Digital
voltmeter

~

Range,
zero
to
1000
volts
;

~

VoItagP
measurements
.
acc!
.!racy,
within
0
.1%
.
Power
Module
Autotransformer
with
ac
volt-
meter
Coaxial
cable
Patch
cord
(2
required)
PERFORMANCE
CHECK
Table
2-4
LIST
OF
TEST
Ef~UIPMENT
REQUIREMENTS
Four
compartments
or
more,

All
tests
.
with
one
high-power
compartment
.
Test
Equipment
Required
Capable
of
supplying
an

Regulation
and
output voltage
from
90

ripple
checks
.
t
o
132
volts,
ac
;
120
W
of
power
at
the
upper
limits
.
Impedance,
50
f2
;
length,

I

Provides
signal
inter-
42 inches
;
connectors,
bnc
.

connection
.
Banana-plug-jack
to
banana-
plug-jack
;
length,
18 inches
.
are instrument
performance
requirements
only
if
stated
as
such
in
the
Specification
portion
of
this
section
.
The
following
test
equipment,
orequivalent,
is
required
to
perform
the
performance
check
and
adjustment
procedure
.
Test
equipment
characteristics
listed
are the
minimum
required
to
verify
the
performance
of
the
equipment
under
test
.
Substitute
equipment
must
meet
or
exceed
the
stated
requirements
.
All
test
equipment
is
assumed
to
be
operating
within
tolerance
.
Provides
signal
inter-
connection
.
Example
Tektronix
5110,
5B10N
Oscilloscope
System
.
Tektronix
DM
501
Digital
Multimeter
.'
Tektronix
TM
504
or
TM
506
.
General
Radio
W10MTR3W
Variac
Autotransformer
.
Tektronix
Part
No
.
012-0057-01
.
Tektronix
Part
No
.
012-0031-00
(black),
012-0039-00
(
red
) .

)
Table
2-4
(cont)
Performance
Description
I

Requirements
I

Application
I

Example
Adapter

I

Bnc
female
to
dual-banana

I

Provides
signal
inter-

I

Tektronix
Part
No
.
plugs
.

connection
.

103-0090-00
.
Load
resistor

20
f2,
20W,
5%,

Load
tests
.

Tektronix
Part
No
.
(two 10
n,
10
W
in
series)
.

I

I

308-0246-00
.
Load
resistor

5
f2,
5
W,
5%
.

Load
tests
.
Resistor

4
.99
kf2,
1/2
W,
1%

Dual
tracking
detector
(2
required)

or
better
.

test
.
1
X
passive
probe
'Requires
TM
500-Series
Power
Module
.
Compatible
with
5A-series

Provides
signal
inter
amplifiers
used
in

connection
.
osci
I
loscope
.
Specification
and
Performance
Check-PS
503A
Tektronix
Part
No
.
308-0179-00
.
Tektronix
Part
No
.
323-0260-00
.
Tektronix
P6028
Probe
.
Preliminary
Procedure

6
.
Adjust the
autotransformer
to
the
nominal
line
1
.
Ensure
that
all
test
equipmentand
the
PS
503A

voltage
and
check
that
the
two
VOLTS
indicator
lights
on
under
test
are
suitably
adapted
to
the
line
voltage
to
be

the
PS
503A
are
on
.
applied
.
Refer
to
the
installation
section
of
the
power
module
manual
.
7
.
Set the
vertical
deflection
factor
for
1
mV/div
and
sweep
rate
for
5
ms/div
on
the
test
oscilloscope
.
Use
ac
coupliny
ioi
fhe
vertical
amplifier
unit
during
this
2
.
.
.Be
.
certain
that
the
POWER
switch
on
the
ptw!er

~
procedure
:
module
is
off
and
that
the
OUTPUT
pushbutton
on
the
PS
503A
is in
the out
position
.
8
.

Connect
all
test
equipment
to
a
suitable
line
voltage
source
.
3
.
Install
the
PS
503A
in
the
far
right
(high
power)
compartment
of
the
power
module
.
9
.
Turn
on
all
test
equipment
and
allow
at
least
twenty
minutes
for
the
equipment
to
warm-up
and
stabilize
.
4
.
Connect
the
power
module
to
the
autotransformer
and
connect
the
autotransformer
to
the
line
voltage
source
.
Set
the
autotransformer
voltageoutput
control
for

NOTE
zero
volt
output
.
During
warm-up
time,
attach
banana
pins
to
the
leads of the
20
f2
and
5
f2
load
resistors
so
that
they
5
.
Set
all
front-panel
controls
on
the
PS
503A
fully

can
be
inserted
in
the
holes
of
the
dual-banana
counterclockwise
(ccw)
.
Apply
power
to
the
power

adapter
.
This
allows
the
load
resistors
to
be
con-
module
and
press
in
the
OUTPUT
pushbutton
on
the

nected
as close as
possible
to
the
output
terminals
PS
503A
.
Push
the
PS
503A
VOLTS
DUALTRACKING

on
the
PS
503A so
contact
resistance
is
kept
to
a
control
in
.

minimum
.
2-5
Specification
and
Performance
Check-PS
503A
Performance
Check
Procedure

b
.
Disconnect
the
red
patch
cord from
the
digital
voltmeter
high
input
terminal
and
set
the
digital
voltmeter
1
.
Check
0-20
Volt
Output
Voltage

to
the
2000
mA
do
range
.
Reconnect
the
red
patch
cord
to
the
digital
voltmeter
high
input
terminal
.
a
.

Check
that
ali
controls
on
the
PS503A
front
panel
are
fully
ccw
and
that
the
400
mA
MAX
indicator
light
is
off
(this light
should
remain
off
as
long
as
the
PS
503A
is
installed
in
the
high-power
compartment
of
the
power
module)
.
Also
check
that
both
CURRENT
LIMIT
indicator
lights
are
off
.
(For
instruments
SN
8022064-below,
these
lights
may
be on
;
if
so, adjust
the
appropriate
CURRENT
LIMIT
control
cw
just
enough
to
turn
them
off)
.
b
.

Set the
digital
voltmeter
to
the
2
volts
do
range
.
Use
patch cords
to
connect
the
+20
V
floating
output
ter-
minals
of
the
PS
503A
to
the
digital
voltmeter
input
terminals
;
connect
the red
patch
cord
from
the
0-20V
red
binding post
to
the
digital
voltmeter high
input
terminal,
and
the black patch cord
from
the
COMMON
(black)
binding
post
to
the
digital
voltmeter
low
input
terminal
.
d
.
Set
the
digital
voltmeter
to
the
200
volts
do
range
and
set the
PS
503A
+
VOLTS
controls
fully
cw
.
e
.
Check-for
a
meter
reading
of
at
least
+20
.1
volts,
but
less
than
+20
.4,volts
.
f
.
Adjust the
PS
503A
+
VOLTS
controls
fully
ccw
and
move
the red patch
cord from
the
0-20V
red
binding post
to
the
0-20V
green
binding post on the
PS
503A
.
g
.
Repeat
parts
1c
through
1e,
using the
PS
503A
-
VOLTS
controls
to
check
the
-20
V
supply
.
h
.
Set the
PS
503A
-
VOLTS
controls
fully
ccw
and
move
the red
patch
cord
back
to
the
0-20V
red
binding
post
on
the
PS
503A
.
Check
to
be
certain
that
ali
PS
503A
front-panel
controls
are
fully
ccw
.
2-6
c
.
Check-for
a current reading
of
less
than
100
mA
for
the
+20
V
supply
.
The
PS
503A
+
CURRENT
LIMIT
light
should
be on
.
d
.
Move
the
red
patch
cord from
the
PS
503A
0-20V
red binding
post
to
the
PS
503A
0-20V
green
binding
post
.
e
.
Check-for
acurrent reading
of
less
than
100
mA
for
the
-20
V
supply
.
The
PS
503A
-
CURRENT
LIMIT
light
should
be
on
.
f
.
Rotate
the
PS
503A-
CURRENT
LIMITcontrolfully
c
w
.
c
.
Check
that
the
PS
503A
+
VOLTS
controls
are
fully
ccw
and
check
for
a
meter
reading
of .0000,
within
f100
mV
.

g
.
Check-for
a
current
reading
of
more
than
1000
mA,
but
less
than 1500
mA
for
the
-20
V
supply
.

,
h
.
Reconnect
the
red
patch
cord
to
the
PS
503A
0-20V
red
binding
post
and
rotate
the
PS
503A
+
CURRENT
LIMIT
control
fully
cw
.
i .
Check-for
a
current
reading
of
more
than
1000
mA,
but
less
than 1500
mA
for
the
+20
V
supply
.
j
.

Set
all
controls
on
the
PS
503A
front
panel
fully
ccw
and
retain
the
digital
voltmeter
connections
to
the
PS
503A
.
3
.
Check
Load
Regulation
a
.
Disconnect
the
red
patch
cord from
the
digital
voltmeter
input
terminal
and
set
the
digital
voltmeter
to
the
20
volts
do
range
.
Reconnect
the red
patch
cord
to
the
digital
voltmeter high
input
terminal
;
the
meter
reading
2
.
Check
Variable
Current
Limiting
.

should
indicate
approximately
zero
volts
.
Both
CURRENT
LIMIT
lights
on
the
PS
503A
front
panel
should
be
off
and
a
.
Adjust
the
PS
503A
+
VOLTS
controls
for
+5
.0
V

remain
off
during the
load
regulation
check
.
output
.
Move
the
red
patch
cord
to
the
PS503A
0-20V
green
binding
post
and
adjust
the
PS
503A
-
VOLTS
controls
for
-5
.0
V
output
.
Move
the
red
patch
cord
back

b
.
Rotate the
CURRENT
LIMIT
control
on
the
PS
503A
to
the
PS
503A
0-20V
red binding post
.

fully
cw
.
I
Specification
and
Performance
Check-PS
503A
c
.
Adjust the
PS
503A
+
VOLTS
fine
and
coarse

b
.
Adjust
the
autotransformer
10%
below
and
10%
controlsforameterreading
between
+19
.900
and+19
.980

above
the
nominal
line
voltage
setting
.
volts
.
Note
and
record
the exact
open-circuit
voltage
reading before applying
the
adapter
(with
load
resistor
I

attached)
in
part
d
of
this
step
.

c
.
Check-that
the
voltage
reading displayed
on
the
digital
voltmeter
does
not
change
more
than
t5
mV
(5
counts)
for
each
10%
line
voltage
change
.
Readjust
the
d
.
Insert
the
leads
of
the
20
f2,
5%
resistor
into
the

autotransformer
to
the
nominal
line
voltage
.
holes
of
a
dual-banana
plug
adapter
and
connect
the
adapter
to
the
patch
cord
jacks,
which
remain
connected
to
the
PS
503A
0-20V
red
and
the
COMMON
binding
post

d
.
Remove
the adapter
(with
load
resistor)
from
the
terminals
.
Observe
correct
polarity
for
the
adapter
(GND

patch
cord
jacks
.
Move
the red
patch
cord
to
the
0-20V
to
COMMON)
.

red binding post
terminal
.
Reconnect
the
adapter
(with
load
resistor)
to
the patch
cord
jacks
.
Observe
correct
polarity
for
the
adapter
(GND
to
COMMON)
.
e
.
CHECK-that
the
meter
reading
does
not
change
more
than
3
mV
(three
counts
of
the
most
right-hand
digit)
.

e
.
Note
the exact
voltage
reading displayed
on
the
digital
voltmeter
with
the
adapter
and
load
resistor
still
attached
to
the
0-20V
red
and
COMMON
binding
post
NOTE

terminals
(+19
.900
to
+19
.980
volts)
.
If
the
reading
on
the
digital
voltmeter
changes
by
more
than
3
mV,
another20
f2,
load
resistorhaving
a

f
.
Adjust the
autotransformer
10%
below
and
10%
resistance value
closer
to
20
f2
should
be
used,
or

above
the
nominal
line
voltage
setting
.
the
voltage
output
from
the
PS
503A
can
be
reduced
to
+19
.000
(step
3c)
.
g
.
Check-that
the
voltage
reading displayed
on
the
digital
voltmeter
does
not
change
more
than
t5
mV
(5
f
.
Remove
the
adapter
(with
load
resistor)
from
the

counts)
for
each
10%
line
voltage
change
.
Readjust the
PS
503A
patch
cord jacks
.
Move
the
red
patch
cord
to
the

autotransformer
to
the
nominal
line
voltage
.
0-20V
green
binding post
terminal
.
g
.
Adjust the
PS
503A
-
VOLTS
fine
and
coarse

5
.
Check
Ripple
and
Noise
controls
for
a
meter
reading
between
-19
.900
and
-19
.980
volts
.
Note
and
record
the
exact
open-circuit voltage

a
.
Disconnect
the patch
cords
from
the
PS
503A
reading
before
applying the
adapter
(with
load
resistor

0-20V
red
and
COMMON
binding post
terminals
and
attached)
in
part
h
of
this
step
.

reconnect
the
dual-banana
adapter
(with
load
resistor)
directly
to
the
0-20V
red
and
COMMON
binding post
terminals
;
observe
correct
polarity of
the
adapter
(,~aND to
COMMON)
:

<
,~,~~
. .
.
.
h
.
Insert
the
leads
of
the 20
f2,
5%
resistor
into
the
holesofadual-banana
adapter
and
connect
theadapterto

b
.
Connect
the output
of
the
adapter
to
the
vertical
the patch cord
jacks,
which
remain
connected
to
the

input
of
the
oscilloscope,
using
a
42-inch
bnc
cable
.
Set
PS
503A
0-20V
green
and
the
COMMON
binding
post
terminals
.
Observe
correct
polarity
for
the
adapter
(GND

the
oscilloscope
vertical
deflection
factor for
1
mV/div
to
COMMON)
.
(calibrated)
.
i .
Check-that
the
meter
reading
does
not
change

c
.
Slowly
adjust
the
autotransformer
output
voltage
more
than 3
mV
(three
counts
of
the
most
right-hand

10%
below
and
then
10%
above
the
nominal
line
voltage
.
digit)
.
d
.
Check-the
signal
display
on
the
oscilloscope
for
less
than 3
mV
peak-to-peak
(within
three
vertical
divisions)
at
all
points
of
the
specified
voltage
limits
.
a
.
Note
the exact
voltage
reading displayed
on
the
digital
voltmeter
with
the
adapter
and
load
resistor
still
attached
to
the
PS
503A
0-20V
green
and
COMMON

e
.
Readjust the
autotransformer
to
the
nominal
line
binding
post
terminals
(-19
.900
to
-19
.980
volts)
.

voltage
.
4
.
Check
Line Regulation
Specification
and
Performance
Check-PS
503A
f
.
Connect
the adapter
(with
load
resistor
attached)
to
the
PS
503A
0-20V
green
and
COMMON
binding
post
terminals
;
observe
correct
polarity of
the
adapter
(GND
to
COMMON)
.
g
.
Repeat
steps
5c
through
5e
to
check
the
ripple
and

7
.
Check
+5
Volt
Output
Voltage
noise
of
the
PS
503A
-20
V
supply
.

a
.
Connect
the
digital
voltmeter~between
the
+5V@1
A
ground
referenced red binding
post
and
the
ground
white
h
.
Readjust
the
autotransformer
to
the
nominal
line

binding post
.
voltage
and
disconnect
all
connections
from
the
PS
503A
.
6
.
Check
Dual
Tracking
Mode
Offset
Error
a
.
Pull
out
the
PS
503A
VOLTS
DUAL
TRACKING
control
and
set
it
fully
ccw
to
ensure
minimum
output
voltage while
connecting
the
resistors
.
b
.
Connect
the
two
4
.99
kS2,
1%
resistors
in
series
between
the
PS
503A
0-20V
green
and
0-20V
red binding
post
terminals
.
Do
not
connect
the
junction
of
the
two
resistors
to
the
COMMON
terminal
or the chassis
.
c
.
Connect
the
black
patch
cord
from
the
digital
voltmeter
low
terminal
to
the
PS
503A
COMMON
binding
post,
and
thered
patch
cord
from
the
digital
voltmeter
high
terminal
to
the
PS
503A
0-20V
red binding
post
.
j
.
Set
the
PS503A
VOLTS
DUAL
TRACKING
control
fully
ccw
and
push
the
control
knob
in
.
Disconnect
both
patch
cords
and
the
two
resistors
from
the
binding
post
terminals
.
b
.
Push
in
the
OUTPUT
button
and
check
that
the
two
VOLTS
indicator
lights
are
on
.
c
.
Check-for
a
meter
reading
of
+4
.75
to
+5
.25
volts
.
d
.
Connect
a 5
i2,
resistor
between
the
+5V@1A
ground
referenced red binding
post
and
the
ground
(white)
binding
post
.
e
.
Check-that
the
meter
reading
does
not
change
by
more
than
100
mV
.
8
.
Check
+5
Volt
Output
Voltage
Regulation
a
.
Adjust the
autotransformer
output
voltage
from
the
low
limit
to
the high
limit
as
indicated
in
Table
2-5
.
d
.
Set the
PS
503A
VOLTS
DUAL
TRACKING
control
fully
cw
and
adjust
the
PS
503A
+
VOLTS
controls
for
a

b
.
Check-that
the
digital
voltmeter reading
does
not
meter
reading
of
+18
V,
t0
.1
volt
.

changemore
than
50
mV
for
a plus
10%
or
minus
10%
line
voltage
change
.
e
.
Connect
the
red
patch
cord
to
the
0-20V
green
binding
post
and
adjust
the
PS
503A-VOLTS
controls
far

c
.
Disconnect
the
digital
voltmeter
.
a
meter
reading
of
-18
V
;
f0
.1
volt
.
d
.
Connect
the
probe
of
the
test
oscilloscope
between
f
.
Disconnect
the
red
patch cord
from
the0-20V
green

the+5V
binding
post
and
the
ground
(white)
binding post
.
binding post
and
connect
it
to
the
junction
of
the
two
4
.99
kf2,
1%
resistors
.
Check
that
the
digital
voltmeter
indicates
a do
voltage
less
than
1
V
.

e
.
Adjust the
autotransformer
output
voltage
from
the
low
limit
to
the high
limit
as
indicated
in
Table
2-5
.
g
.

Set the
digital
voltmeter
to
the
2-volts
do
range
and
adjust
either
the
+
VOLTS
or
-
VOLTS
controls
on
the

f
.
Check-the
test
oscilloscope
display
for
not
more
PS
503A
to
obtain
a
meter
reading
of
0V
do (f100
mV)
.

than 5
mV
peak-to-peak
ripple
and
noise
.
h
.
Adjust the
PS
503A
VOLTS
DUAL
TRACKING

g
.
Return the
autotransformer
to
the
nominal
tine
control
slowly
from
cw
to
ccw
.

voltage
setting
.
i .
Check-that
the
meter
reading
remains
within

h
.
Disconnect
the
test
oscilloscope
probe
from
the
±25
mV
of
zero
volts
.

binding posts
.
2-8
i .
Press
and
release
the
PS
503A
OUTPUT
button
to
turn
off
the
power
to
the
PS
503A
.
POWER
MODULE
UNIVERSAL
TRANSFORMER
Line
Selector
Block
Position
L
M
H
Line
Fuse
Data
Table
2-5
Regulating
Ranges
110-Volts
Nominal

~
220-Volts
Nominal
90
VAC
to
110
VAC
99
VAC
to
121
VAC
~
198
VAC
to
242
VAC
108
VAC
to
132
VAC
~
216
VAC
to
264
VAC
1
.6
A
slow-blow
9
.
Check
Variable
Current
Limiting
180
VAC
to
220
VAC
0
.8
A
slow-blow
a
.
Turn
the
power
off
to
the
TM
500
Series
Power
Module
and
remove
the
PS
503A
from
the
high-power
compartment
and
install
the
PS
503A
in
the
low-power
compartment
.
b
.
Turn
on
the
power
to
the
power
module
and
press
the
PS
503A
OUTPUT
button
in
.
Set
all
front
panel
controls
fully
ccw
and
allow
approximately
three
minutes
for
the
equipment
to
stabilize
.
c
.
Check-that
the
400
mA
MAX
indicator
light
is
on
.
d
.
Adjust
the
PS
503A
+
VOLTS
and
-
VOLTS
coarse
controls
to
the
4V
position
(leave
the
fine
controls
fully
ccw)
.
Specification
and
Performance
Check-PS
503A
f
.
Set the
PS
503A
+
and
-
CURRENT
LIMIT
controls
fully
cw
.
g
.
Check-that
the
digital
voltmeter
indicates
a
current
reading
of
more
than
400mA,
but
less
than
600
mA
.
The
+
CURRENT
LIMIT
light
should
beon
.
h
.
Move
the
red
patch
cordfrom
the
0-20V
red
binding
post
to
the
0-20V
green
binding
post
.
i
.
Check-that
the
digital
voltmeter
display
indicates
a
current
reading
of
more
than
400
mA,
but
less
than
600
mA
.
The
-
CURRENT
LIMIT
light
should
be
on
.
j
.
Set the
PS
503A
-
CURRENT
LIMIT
control
fully
ccw
.
k
.
Check-that
the
digitalvoltmeterindicatesacurrent
reading
of
less
than
100
mA
.
The
-CURRENT
LIMIT
light
should
remain
on
.
I .
Move
the
red
patch
cord
from
the
0-20V
green
binding post
to
the
0-20V
red binding post
and
set
the
PS
503A
+
CURRENT
LIMIT
control
fully
ccw
.
m
.
Check-that
the
digital
voltmeter
indicates
a
current
reading
of
less
than
100
mA
.
The
+
CURRENT
LIMIT
light
should
be
on
.
n
.
Turn
off
all
power
to
the
power
module
.
Push
and
release
the
PS
503A
OUTPUT
button
and
set
all
other
front-panel
controls
fuljyccw
.. . .
e
.

Setthe
digital
voltmetertothe
2000
mA
position
and
connect
the black
patch
cord from
the
digital
voltmeter
low
terminal
to
the
PS
503A
COMMON
binding
post
and
the
red
patch
cord
from
the
digital
voltmeterhigh
terminal

o
.
This
completes
the
Performance
Check
Procedure
to
the
PS
503A
0-20V
red
binding post
.

for
the
PS
503A
.
Introduction
d
.
Install
all
TM
500-series
equipment,
including
the
This
adjustment
procedure
is
to
be
used
to
restore
the

PS
503A
into
the
power
module
.
PS
503A
to
original
performance
specifications
.
Adjust-
ment
need
not
be
performed
unless the instrument
fails
to
meet
the
requirements
listed
in
the
Specification
section,

e
.
Connect
all
test
equipment
to
a
suitable
line
voltage
or
the
Performance
Check
cannot
be
completed
satisfac-

source
.
tori
ly
.
Services
Available
Tektronix,
Inc
.
provides
complete
instrument
repair
and
adjustment
at
local
Field
Service
Centers
and
at
the
FactoryService
Center
.
Contact
your
local
Tektronix
Field
Office
or
representative
for
further
information
.
Test
Equipment
Required
The
test
equipment
listed
in
Table
2-4 or
equivalent,
is
required
for
adjustment
of
the
PS
503A
.
Specifications
given
for
the
test
equipment
are the
minimum
necessary
for
accurate
adjustment
and
measurement
.
All
test
equip-
ment
is
assumed
to
be
correctly
calibrated
and
operating
within
specification
.
If
other
test
equipment
is
substituted,
control
settings
or
calibration
setup
may
need
to
be
altered
to
meet
the
requirements
of
the
equipment
used
.
Preparation
a

Remove
the
left-hand
and
right-hand
side
covers
of
the
PS
503A
to
gain
access
to
the
component
side
of
the
circuit
boards
.
Pull
the
rear
end
of the
side
coveroutward
from
the
side
of
the instrument
(the
cover
snaps
into
place)
.
b
.
Install
the
PS
503A
into
the
far
right
(high
power)

I

'
power
module
compartment,
or
if
appropriate,
connect

~®
the
PS
503A
to
the
power
module
by
means
of
the
flexible
plug
m
extender
If
a
flexible
extender
is
used
current
-

f

JIJ
:
Section
3-PS
503A
ADJUSTMENT
f
.
Turn
on
all
test
equipment
and
allow
at
least
twenty
minutes
for
the
equipment
to
warm-up
and
stabilize
.
g
.
Set the
autotransformer
to
the
nominal
line
voltage
setting
.
Initial
Control
Settings
Set the
following
controls
during
warm-up
time
:
PS
503A
Duai
Power
Supply
-
VOLTS
(coarse
and
fine)

fully
ccw
+
VOLTS
(coarse
and
fine)

fully
cww
CURRENT
LIMIT
Plus
supply

fully
ccw
Minus
supply

fully
ccw
VOLTS
DUAL
TRACKING

pushed
in
and
fully
ccw
limiting
switch
S95
must
.
be
engaged
in
the
maximum

~

~
CJpf"
current
(HI)
position
.
See
Fig
.
3-1
for
switch
location
.
r~
o-

aea

""
~~
.

.
B
R45
+20V
Adj
c
.
Set the
power
module
for
the
line
voltage
to
be

~

~

-20v
Adj
applied
(see
power
module
manual)
and
connect
it
to
the
1

autotransformer,
then
connect
the
autotransformer
to
the
line
voltage
source
.
Be
sure
that
the
power
switch
is
off
.

Fig
.
3-1
.
Location
of
+20
V
and
-20
V
adjustment
.
R
145

Other manuals for PS 503A

1

Other Tektronix Power Supply manuals

Tektronix PS 503A User manual

Tektronix

Tektronix PS 503A User manual

Tektronix Keithley 2260B Series User manual

Tektronix

Tektronix Keithley 2260B Series User manual

Tektronix 620-0295-00 User manual

Tektronix

Tektronix 620-0295-00 User manual

Tektronix PS 5010 User manual

Tektronix

Tektronix PS 5010 User manual

Tektronix PWS4000 Series User manual

Tektronix

Tektronix PWS4000 Series User manual

Tektronix 1106 User manual

Tektronix

Tektronix 1106 User manual

Tektronix PS 503S User manual

Tektronix

Tektronix PS 503S User manual

Tektronix PS 5004 User manual

Tektronix

Tektronix PS 5004 User manual

Tektronix PS280 User manual

Tektronix

Tektronix PS280 User manual

Tektronix PS 505 User manual

Tektronix

Tektronix PS 505 User manual

Tektronix Keithley 2260B Series Owner's manual

Tektronix

Tektronix Keithley 2260B Series Owner's manual

Tektronix PS 503 User manual

Tektronix

Tektronix PS 503 User manual

Tektronix 1101A User manual

Tektronix

Tektronix 1101A User manual

Tektronix PWS2185 Use and care manual

Tektronix

Tektronix PWS2185 Use and care manual

Tektronix 1103 User manual

Tektronix

Tektronix 1103 User manual

Tektronix TM 515 User manual

Tektronix

Tektronix TM 515 User manual

Tektronix TM 515 User manual

Tektronix

Tektronix TM 515 User manual

Tektronix Keithley 2260B Series Owner's manual

Tektronix

Tektronix Keithley 2260B Series Owner's manual

Tektronix Keithley 2281 Series User manual

Tektronix

Tektronix Keithley 2281 Series User manual

Tektronix PWS4205 Operating and maintenance manual

Tektronix

Tektronix PWS4205 Operating and maintenance manual

Tektronix TM 515 User manual

Tektronix

Tektronix TM 515 User manual

Tektronix KEITHLEY 2200 Series Owner's manual

Tektronix

Tektronix KEITHLEY 2200 Series Owner's manual

Tektronix Keithley 2231A-30-3 Installation and operation manual

Tektronix

Tektronix Keithley 2231A-30-3 Installation and operation manual

Tektronix 285 User manual

Tektronix

Tektronix 285 User manual

Popular Power Supply manuals by other brands

Omtech MYJG-50W instruction manual

Omtech

Omtech MYJG-50W instruction manual

SIGLENT SPD1000X Series Service manual

SIGLENT

SIGLENT SPD1000X Series Service manual

Intelligent Charging LSU220A Operator's manual

Intelligent Charging

Intelligent Charging LSU220A Operator's manual

Potter PSN-106 Installation, operation and instruction manual

Potter

Potter PSN-106 Installation, operation and instruction manual

Alpha Node installation manual

Alpha

Alpha Node installation manual

Bogen PRSLSI Specifications

Bogen

Bogen PRSLSI Specifications

Schaudt EBL 101 D instruction manual

Schaudt

Schaudt EBL 101 D instruction manual

Beckhoff PS1061-2420-0000 Documentation

Beckhoff

Beckhoff PS1061-2420-0000 Documentation

Lambda Genesys GENH 750W Technical manual

Lambda

Lambda Genesys GENH 750W Technical manual

Pulsar PSBEN 3024C/LCD manual

Pulsar

Pulsar PSBEN 3024C/LCD manual

Chargery Power A30 manual

Chargery Power

Chargery Power A30 manual

Jinbo JLV-12060K Specifications & user's guide

Jinbo

Jinbo JLV-12060K Specifications & user's guide

StetSom INFINITE BLACK 50A user manual

StetSom

StetSom INFINITE BLACK 50A user manual

Camtec Powersolve HSEUREG04801 Series manual

Camtec

Camtec Powersolve HSEUREG04801 Series manual

Supermicro PWS-1k62A-1R Information

Supermicro

Supermicro PWS-1k62A-1R Information

McPower LAB-3003 Reference manual

McPower

McPower LAB-3003 Reference manual

Altronix eFlow Series installation guide

Altronix

Altronix eFlow Series installation guide

FEAS SNT130-K operating instructions

FEAS

FEAS SNT130-K operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.