ABC Logic™ Self Calibration
System
ABC Logic™ (Automatic Background Calibration)
self calibration allows the sensor to continually re-
calibrate itself when the indoor concentrations drop
to outside levels while the building is unoccupied.
Generally a building must be regularly unoccupied
for 4 hours or more for this self-calibration system
to operate properly. Under these conditions, ABC
Logic™ should maintain sensor calibration over the
lifetime of the sensor. The ABC Logic™ should be
turned OFF where a building is continuously oc-
cupied 24 hours per day, or where there could be
significant sources of non-occupant related CO2
such as greenhouses, breweries and other industrial
and food processing applications.