Telect LTX User manual

LTX
Patch and Splice Panel
Installation Guide

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 2
Table of Contents
Chapter 1: Introduction...........................................................................................................................................4
1.1 Specications .................................................................................................................................................4
1.2 About this Guide .............................................................................................................................................5
1.3 Terminology ....................................................................................................................................................5
1.4 LTX 4RU, 2RU and 1RU Panel Overview ......................................................................................................6
Chapter 2: Installation Considerations..................................................................................................................9
2.1 Inspection .......................................................................................................................................................9
2.2 Unpacking.......................................................................................................................................................9
2.2.1 LTX 4RU, 2RU and 1RU Panel Contents ...............................................................................................10
2.3 Installation Guidelines .................................................................................................................................. 11
2.4 Location and Space...................................................................................................................................... 11
2.5 Tools and Equipment.................................................................................................................................... 11
Chapter 3: LTX Patch and Splice Panel Installation and Routing.....................................................................12
3.1 LTX Panel Component Installation ...............................................................................................................12
3.1.1 Entry/Exit Arc Installation........................................................................................................................12
3.1.2 Routing Spool Installation.......................................................................................................................12
3.1.3 Splice Tray Installation............................................................................................................................13
3.1.4 Tray Platform Installation........................................................................................................................15
3.1.5 Cable Clamp Bracket Installation ...........................................................................................................15
3.1.6 Cable Clamp Installation.........................................................................................................................17
3.1.7 Central Strength Member Holder Installation .........................................................................................18
3.1.8 Adapter Patch Plate Installation..............................................................................................................19
3.1.9 Panel Doors Installation..........................................................................................................................20
3.1.10 Designation Label Installation...............................................................................................................21
3.1.11 Installing Mounting Brackets on the LTX Panel ....................................................................................22
3.2 Install and Ground the LTX Panel on the Rack ............................................................................................23
Chapter 4: LTX Panel Cable and Fiber Installation and Routing.......................................................................24
4.1 Cable Installation and Routing......................................................................................................................24
4.1.1 IFC Cable Installation and Routing.........................................................................................................24
4.1.2 Install IFC in the Cable Clamp................................................................................................................25
4.1.3 Route Protected 12 Strand Ribbon Fiber in LTX Panel Slack Storage Area .......................................... 26
4.1.4 Install Ribbon Fibers in the Splice Tray .................................................................................................. 27
4.1.5 Route Pigtail Fibers in the Splice Tray....................................................................................................28
4.2 Splice and Route Fibers ...............................................................................................................................31
4.3 Connect Fiber Jumpers to the Patch Panel..................................................................................................31
Chapter 5: Service.................................................................................................................................................34
5.1 Owner Maintenance .....................................................................................................................................34
5.1.1 High Insertion Loss and the Importance of Cleaning Connectors and Adapters....................................34
5.2 Techincal Support.........................................................................................................................................35
5.3 In-Warranty Service......................................................................................................................................35
5.4 Out-of-Warranty Service...............................................................................................................................35
5.5 Repackage for Shipment..............................................................................................................................35

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 3
List of Figures
Figure 1-1 LTX Patch and Splice Panel with SC Adapters ........................................................................................4
Figure 1-2 LTX 4RU Patch and Splice Panel Overview - Front and Rear Views ......................................................6
Figure 1-2-1 LTX 2RU Patch and Splice Panel Overview - Front and Rear Views ...................................................7
Figure 1-2-2 LTX 1RU Patch and Splice Panel Overview - Front and Rear Views ...................................................8
Figure 3-1 Entry/Exits Arcs Installation....................................................................................................................12
Figure 3-2 Routing Spools Installation.....................................................................................................................12
Figure 3-3 4RU Splice Trays Installation .................................................................................................................13
Figure 3-3-1 2RU Splice Trays Installation..............................................................................................................14
Figure 3-3-2 1RU Splice Trays Installation..............................................................................................................14
Figure 3-4 4RU Tray Platform Installation ...............................................................................................................15
Figure 3-5 4RU Cable Clamp Bracket Installation...................................................................................................15
Figure 3-5-1 2RU Cable Clamp Bracket Installation................................................................................................16
Figure 3-5-2 1RU Cable Clamp Bracket Installation................................................................................................16
Figure 3-6 4RU Cable Clamp Installation................................................................................................................17
Figure 3-6-1 2RU Cable Clamp Installation.............................................................................................................17
Figure 3-6-2 1RU Cable Clamp Installation.............................................................................................................17
Figure 3-7 4RU Central Strength Member Holder Installation.................................................................................18
Figure 3-8 4RU Adapter Patch Plate Installation.....................................................................................................19
Figure 3-8-1 2RU Adapter Patch Plate Installation..................................................................................................19
Figure 3-8-2 1RU Adapter Patch Plate Installation..................................................................................................19
Figure 3-9 4RU Door Installation.............................................................................................................................20
Figure 3-9-1 2RU Door Installation..........................................................................................................................20
Figure 3-10 4RU Designation Label Installation......................................................................................................21
Figure 3-10-1 2RU Designation Label Installation...................................................................................................21
Figure 3-10-2 1RU Designation Label Installation...................................................................................................21
Figure 3-11 Installing Mounting Brackets on LTX 4RU Panels................................................................................22
Figure 3-11-1 Installing Mounting Brackets on LTX 2RU Panels.............................................................................22
Figure 3-11-2 Installing Mounting Brackets on LTX 1RU Panels.............................................................................22
Figure 3-12 Install and Ground LTX Panel to the Rack ........................................................................................... 23
Figure 4-1 Securing IFC Cabling to the LTX 4RU Panel .........................................................................................25
Figure 4-1-1 Securing IFC Cabling to the LTX 2RU Panel ......................................................................................25
Figure 4-1-2 Securing IFC Cabling to the LTX 1RU Panel ......................................................................................25
Figure 4-2 Route Protected 12-Stranded Ribbon Fiber through LTX Panel Slack Storage Area ............................26
Figure 4-3 Installing Ribbon Fibers in the Splice Tray.............................................................................................27
Figure 4-4 Routing Pigtail Fibers in the 4RU Splice Tray ........................................................................................28
Figure 4-4-1 Routing Pigtail Fibers in the 2RU Splice Tray..................................................................................... 29
Figure 4-4-2 Routing Pigtail Fibers in the 1RU Splice Tray..................................................................................... 30
Figure 4-5 Connecting Fiber Jumpers to the 4RU Patch Panel .............................................................................. 32
Figure 4-5-1 Connecting Fiber Jumpers to the 2RU Patch Panel ........................................................................... 33
Figure 4-5-2 Connecting Fiber Jumpers to the 1RU Patch Panel ........................................................................... 33

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 4
Chapter 1: Introduction
The Telect LTX Patch and Splice Panel consolidates
network ber splicing, patching and routing
requirements in a 4RU panel.
The LTX panel accommodates up to 288 fiber
terminations and houses eight splice trays.
Front View
Rear View
144 Terminations Shown
Figure 1-1 - LTX Patch and Splice Panel with SC Adapters
1.1 Specications
Dimensions and Weights
Dimensions 4RU: 7" H x 17" W x 17" D
2RU: 3.5" H x 17" W x 17" D
1RU: 1.75" H x 17" W x 17" D
Weight 4RU: 14.65 lbs.
2RU: 11.2 lbs.
1RU: 6.8 lbs.
Mechanical
Connector Type SC/UPC, SC/APC, LC/APC, LC/UPC, MPO/MTP
Access Front and Rear
Capacity Max. 288 port 4RU
Splicing Single Fusion / Mass Fusion / Stranded
Panel Mounting 19" or 23" with ETSI, EIA, or WECO spacing
Adapter Access Front/Rear Patch Panel
Material Aluminum/Steel
Compliance NEBS, ETSI, Zone 4 Seismic reliability
Environmental
Temperature Range -5°C to 55°C
Humidity 90%, non-condensing

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 5
1.2 About this Guide
This manual provides a comprehensive overview and installation guidelines for the LTX Patch and Splice Panel. While
care has been taken to dene all necessary information, complete details may not be covered. If you have any questions,
contact Telect at [email protected] or call 1.509.926.6000.
Throughout this guide, relevant and crucial information is displayed in the form of Notes, Alerts, Cautions and Warnings.
These notications are prominently displayed and their importance is indicated as follows:
NOTE: General information the user should pay special attention to.
Alert! Important information and/or instructions the user should adhere to.
CAUTION! Indicates a hazardous situation, which if not avoided could result in minor
or moderate injury.
WARNING: Indicates a potentially hazardous situation which if not avoided could result in death
or serious injury.
Telect assumes no liability from the application or use of these products. Neither does Telect convey any
license under its patent rights of others. This document and the products described herein are subject to change without
notice.
1.3 Terminology
The following list of acronyms and abbreviations are used throughout this manual.
Acronym/Abbreviation Term
IF IntraFacility Fiber
IFC IntraFacility Cable
LC Local Connector
MPO Multi-Fiber Push-On optical ber module interface type
NE Network Element
NEBS Network Equipment Building System (telecommunications product safety equipment rating
standard)
PC Physical Contact ber optic connector (single or multi-mode)
SC Standard Connector
TIA Telecommunications Industry Association
TIA/EIA-568 B.3 Telecommunication Standards for Commercial Cabling
TUV Technical Inspection Association (global product certication compliance marking)
UL Underwriter Laboratories (electrical standards)
APC Angled Physical Contact ber optic connector (single or multi-mode)
UPC Ultra Physical Contact ber optic connector (single or multi-mode)

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 6
The Telect LTX patch and splice panel consolidates
network ber splicing, patching and routing requirements
in a 4RU panel.
The LTX 4RU panel accommodates:
• Up to 288 fiber terminations
• Stacked splice trays, housing 36 splice sleeve holders
per single fusion tray and 144 per mass fusion tray
• Single fusion/mass fusion options
• Velcro bands that secure trays inside the panel
• Routing spools to manage slack cable routing
• Panel mounted cable clamp for incoming cable
slack maintenance
• Convenient spring-hinged removable front and
rear doors
• Designation labels on front and rear doors
Interconnect and cross-connect cabling enter the LTX
panel at rear corner locations guided over rubber edge
protectors. Slack storage area in the rear of the panel
routes IntraFacility Cables (IFC) through the panel to
splice trays in the center of the panel. After splicing,
pigtail bers connect to patch plate mounted connectors
at the rear of the panel and ber jumpers connect to
patching adapters at the front.
LTX patch and splice panel patch plates
can accommodate:
• SC/UPC, SC/APC, LC/APC, LC/UPC are available in
patch plates with 6 or 8 terminations
• LC/SC available in patch plates with
12 terminations
• LC/UPC and LC/APC available in patch plates with
24 terminations
• MPO/MTP feed through patch plates available with 6
or 8 adapters
In addition, Telect offers a special factory-congured
integrated 4RU patch plate panel with up to 288
terminations (requires use of LC quad adapters).
Adapters are also offered in multi-mode versions. All
adapters include dust covers. All patch plates are
available in white or black.
1.4 LTX Panel Overview
Figure 1-2 - LTX 4RU Patch and Splice Panel Overview
- Front and Rear Views-
Rear Door
Routing Spool
Slack
Storage
Area
Designation Label
(Rear Side)
Cable Clamp Patch Plate with
Connectors
LTX Patch and Splice Panel, Rear View
(144 terminations shown)
Arc
Arc
Cable
Entry
Area Arc Stacked Splice
Trays
Cable
Entry Area
Arc
Velcro Tie
Arc
LTX Patch and Splice Panel, Front View
(144 terminations shown)
Front Door
Fiber
Jumper
Entry
Area
Designation
Card
(Front Side)
Patch Plate with Adapters
Cable Clamp
Arc
Arc
Arc
Arc
Arc Fiber
Jumper
Entry
Area
LTX 4RU

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 7
LTX 1RU
The Telect LTX patch and splice panel consolidates
network ber splicing, patching and routing requirements
in a 1RU panel.
The LTX 1RU panel accommodates:
• Up to 72 fiber terminations
• Stacked splice trays, housing 36 splice sleeve holders
per single fusion tray and 144 per mass fusion tray
• Single fusion/mass fusion options
• Velcro bands that secure trays inside the panel
• Routing spools to manage slack cable routing
• Panel mounted cable clamp for incoming cable
slack maintanence
• Designation label on the front
Interconnect and cross-connect cabling enter the LTX
panel at rear corner locations guided over rubber edge
protectors. Slack storage area in the rear of the panel
routes IntraFacility Cables (IFC) through the panel to
splice trays in the center of the panel. After splicing,
pigtail bers connect to patch plate mounted connectors
at the rear of the panel and ber jumpers connect to
patching adapters at the front.
LTX patch and splice panel patch plates
can accommodate:
• SC/UPC, SC/APC, LC/APC, LC/UPC are available in
patch plates with 6 or 8 terminations
• LC/SC available in patch plates with
12 terminations
• LC/UPC and LC/APC available in patch plates with
24 terminations
• MPO/MTP feed through patch plates available with 6
or 8 adapters
In addition, Telect offers a special factory-congured
integrated 1RU patch plate panel with up to 72
terminations (requires use of LC quad adapters).
Adapters are also offered in multi-mode versions. All
adapters include dust covers. All patch plates are
available in white or black.
Figure 1-2-1 - LTX 1RU Patch and Splice Panel Overview
- Front and Rear Views-
Designation Label
LTX Patch and Splice Panel, Front View
(24 terminations shown)
Bracket
Bracket
LTX Patch and Splice Panel, Rear View
(24 terminations shown)
Bracket Bracket
Routing Spool
Splice Tray
Patch Plate
Patch Plate with Adapters
Velcro Tie

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 8
LTX 2RU
The Telect LTX patch and splice panel consolidates
network ber splicing, patching and routing requirements
in a 2RU panel.
The LTX 2RU panel accommodates:
• Up to 144 fiber terminations
• Stacked splice trays, housing 36 splice sleeve holders
per single fusion tray and 144 per mass fusion tray
• Single fusion/mass fusion options
• Velcro bands that secure trays inside the panel
• Routing spools to manage slack cable routing
• Panel mounted cable clamp for incoming cable
slack maintanence
• Convenient spring-hinged removable front and
rear doors
• Designation labels on front and rear doors
Interconnect and cross-connect cabling enter the LTX
panel at rear corner locations guided over rubber edge
protectors. Slack storage area in the rear of the panel
routes IntraFacility Cables (IFC) through the panel to
splice trays in the center of the panel. After splicing,
pigtail bers connect to patch plate mounted connectors
at the rear of the panel and ber jumpers connect to
patching adapters at the front.
LTX patch and splice panel patch plates
can accommodate:
• SC/UPC, SC/APC, LC/APC, LC/UPC are available in
patch plates with 6 or 8 terminations
• LC/SC available in patch plates with
12 terminations
• LC/UPC and LC/APC available in patch plates with
24 terminations
• MPO/MTP feed through patch plates available with 6
or 8 adapters
In addition, Telect offers a special factory-congured
integrated 2RU patch plate panel with up to 144
terminations (requires use of LC quad adapters).
Adapters are also offered in multi-mode versions. All
adapters include dust covers. All patch plates are
available in white or black. Figure 1-2-2 - LTX 2RU Patch and Splice Panel Overview
- Front and Rear Views-
LTX Patch and Splice Panel, Front View
(48 terminations shown)
LTX Patch and Splice Panel, Rear View
(48 terminations shown)
Designation Label
Patch Plate with Adapters
Front Door
Door Hinge
Bracket
Bracket
Splice Tray Velcro Tie Routing
Spool

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 9
Chapter 2: Installation Considerations
WARNING: Verify all connections meet requirements specied in local electric codes or operating company
guidelines before supplying power. Unit must be protected by a listed circuit breaker or branch-rated fuse
sufcient to interrupt power levels.
WARNING: Use of fully insulated tools is required when working with any AC or DC circuits.
WARNING: Fiber cables transmit invisible infrared light. To avoid eye damage or blindness, never look directly
into bers or connectors.
CAUTION! These instructions presume you have veried that the Telect equipment being installed is compatible
with the rest of the system including power, ground, circuit protection, signal characteristics, equipment from
other vendors and local codes or ordinances.
ALERT! This product must be installed and maintained only by qualied technicians.
ALERT! Install this system according to company requirements. It is recommended to install the
system in a Restricted Access Location (RAL) where access is limited through use of tool (i.e., lock and key) or
other means of security and be controlled by the authority responsible for the location.
ALERT! Prior to panel installation, ensure there is enough space in front and rear to access cabling.
ALERT! Only use components and crimping tools approved by agencies or certifying bodies recognized in your
country or region, such as Underwriter’s Laboratories (UL), TUV, etc.
ALERT! Do not stand on ber or ber cables.
2.1 Inspection
When you receive the equipment, carefully unpack it and compare it to the packaging list. Please report any defective
or missing parts to Telect at [email protected] or call 1.509.926.6000. Keep all documentation that comes with
your shipment.
Please read and understand all instructions before starting installation. If you have any questions, contact Telect at
[email protected] or call 1.509.926.6000.
The panel is wrapped with a high-strength plastic. Exercise care when unpacking and setting the equipment
in place.
Telect is not liable for transit damage. If the product is damaged, please report it to the carrier and
contact Telect at 1.509.926.6000 or through email at [email protected].
2.2 Unpacking
The LTX 4RU patch and splice panel is 7" H x 17" W x 17" D and weighs 14.65 lbs.
The LTX 2RU patch and splice panel is 3.5" H x 17" W x 17" D and weighs 11.2 lbs.
The LTX 1RU patch and splice panel is 1.75" H x 17" W x 17" D and weighs 6.8 lbs.
These panels come pre-assembled as one unit.
Upon receipt of your order, carefully unpack it and compare it with the packing list and the order placed. While items
described below are a comprehensive list that includes the LTX panel, splice trays with splice sleeves, spools, brackets,
and doors, the contents of your order may vary.

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 10
2.2.1 LTX Panel Contents
4 RU
• LTX patch and splice panel
• Tray platform
• Splice trays
• Splice sleeve holders
• Arcs (edge protectors)
• Velcro bands
• Routing spools
• Removable doors (spring-hinged
swing down)
• Designation labels (front and rear)
• Cable clamp bracket
• Cable clamp with bushing sleeves
• Mounting brackets (to mount to 19" or
23" rack)
• Installation guide
2 RU
1 RU
• LTX patch and splice panel
• Splice trays
• Splice sleeve holders
• Arcs (edge protectors)
• Velcro bands
• Routing spools
• Removable doors (spring-hinged
swing down)
• Designation labels (front and rear)
• Cable clamp bracket
• Cable clamp with bushing sleeves
• Mounting brackets (to mount to 19" or
23" rack)
• Installation guide
• LTX patch and splice panel
• Splice trays
• Splice sleeve holders
• Arcs (edge protectors)
• Velcro bands
• Routing spools
• Designation labels (front)
• Cable clamp bracket
• Cable clamp with bushing sleeves
• Mounting brackets (to mount to 19" or
23" rack)
• Installation guide

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 11
2.3 Installation Guidelines
Elevated Operating Ambient Temperature - If installed in a closed or multi-unit rack assembly, the operating ambient
temperature of the rack environment may be greater than room ambient. Therefore, consideration should be given to
installing the equipment in an environment compatible with the maximum ambient temperature (Tma) specified by
the manufacturer.
Mechanical Loading - Mounting of the equipment in the rack should be such that a hazardous condition is not achieved
due to uneven mechanical loading.
2.4 Location and Space
The LTX patch and splice panel requires space in the front and rear for access to patching, splicing and cabling. Leave as
much side clearance for tray and panel removal and worker access as required by your application or local regulations.
Plan the input/output, upward/downward (cable feed) layout of each panel and its position in the rack before beginning
LTX panel installation.
LTX panels adapt to standard 19" or 23" ETSI racks with EIA, ETSI and WECO spacing and nominal 3¼" extensions
beyond the front rack ange.
2.5 Tools and Equipment
No special tools required.

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 12
Chapter 3: LTX Patch and Splice Panel Installation and Routing
3.1 LTX Panel Component Installation
If not already installed, install LTX panel components prior to installing cabling and bers, or mounting the
panel to a rack.
LTX panel components include entry/exit arcs, splice tray platform with routing spools, velcro banding, stacked splice
trays, one or two cable clamp brackets with cable clamps, front and rear doors, designation cards for front and rear of the
panel and an adapter patch plate panel with connectors and adapters.
3.1.1 Entry/Exit Arc Installation
Refer to
Figure 3-1
for this procedure.
The installation instructions apply to the LTX 4RU only
At the front of the LTX panel, four entry/exit split arcs protect
top and bottom corners where ber jumpers enter the panel.
At the rear of the panel, entry/exit split arcs protect top and
bottom corners where IntraFacility Cables (IFC) enter the LTX
panel. Arcs can be removed if needed to accommodate other
LTX panel attachments.
At each corner of the LTX panel:
1. Position the center groove of the entry/exit arc in front of the
metal edge on the LTX panel.
2. Slide the entry/exit arc onto the corner entryway.
NOTE: The arcs install in the rear of the panel.
LTX Patch and Splice Panel
Side View
Arc Arc
Center
Groove
Arc
Front View
Arc
Arc
DoorDoor
3.1.2 Routing Spool Installation
Figure 3-1 - Entry/Exit Arc Installation
Refer to
Figure 3-2
for this procedure.
The installation instructions apply to the LTX 4RU, 2RU
& 1RU
Follow these instruction incase spools are not already installed
by the manufacturer. Routing spools are installed on the tray
platform before the platform is installed in the LTX panel.
Routing spools protect centrally located splice trays and
route IFC in the rear of the LTX panel through the slack
storage area.
1. On the tray platform, locate the four routing spool
screw holes.
2. Position routing spools on the tray platform so that screw
holes align. For correct alignment, the routing spool
overhang should face toward the outside of the platform.
3. Insert a screw from the bottom of the tray platform up
and into the screw hole of each routing spool and
hand tighten.
4. Adjust routing spool positions to best accommodate cable
routing and tighten screws using a Phillips screwdriver.
Routing Spools
Tray Platform
Tie-Down
Slot
Platform
Thumb Screw
Routing Spool Screw
Attaches through bottom of
tray platform
Routing Spool
Overhang
Figure 3-2 - Routing Spool Installation

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 13
3.1.3 Splice Tray Installation
The installation instructions apply to the LTX 4RU
Refer to
Figure 3-3
for this procedure.
Splice trays stack together on the tray platform. Trays
sit in the center platform surrounded by routing spools.
Trays hook together and are secured on the panel with
velcro bands.
1. Attach a velcro zip-tie band at the front and rear
center tie-down slot on the tray platform.
To do this:
a. Slide the band through the tie-down slot
and into the zip-tie opening at the end of
the velcro band.
b. Tighten the band to the slot.
c. Repeat the process at the opposite side,
attaching the velcro band to the platform's
tie-down slot.
2. Place the rst splice tray in the center of the platform
(long side of the tray toward the front of the tray
platform) between routing spools, tie-down slots and
metal tabs. There will be a small amount of space
between the metal tabs and tray.
3. Place the next tray on top of the rst tray. Each side
of the tray has two tabs that snap into slots securing
it to the tray below. Snap trays together.
4. Repeat Step 3 for the remaining trays.
5. Pull each velcro band up and over the stacked splice
trays and attach them together to secure the trays to
the platform.
* The number of splice trays will depend on the
number of connectors.
Figure 3-3 4RU Splice Tray Installation

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 14
The installation instructions apply to the 2RU & 1RU
Refer to
Figure 3-3-
1 & 3-3-2 for this procedure.
Splice trays stack together on the tray platform. Trays
sit in the center platform surrounded by routing spools.
Trays hook together and are secured on the panel with
velcro bands.
1. Attach a velcro zip-tie band at the front and rear
center tie-down slot on the tray platform.
To do this:
a. Slide the band through the tie-down slot
and into the zip-tie opening at the end of
the velcro band.
b. Tighten the band to the slot.
c. Repeat the process at the opposite side,
attaching the velcro band to the platform's
tie-down slot.
2. Place the rst splice tray in the center of the platform
(long side of the tray toward the front of the tray
platform) between routing spools, tie-down slots and
metal tabs. There will be a small amount of space
between the metal tabs and tray.
3. Place the next tray on top of the rst tray. Each side
of the tray has two tabs that snap into slots securing
it to the tray below. Snap trays together.
4. Repeat Step 3 for the remaining trays.
5. Pull each velcro band up and over the stacked splice
trays and attach them together to secure the trays to
the platform.
*The number of splice trays will depend on the
number of connectors.
Figure 3-3-1 2RU Splice Tray Installation
Figure 3-3-2 1RU Splice Tray Installation

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 15
3.1.4 Tray Platform Installation
The installation instructions apply to the LTX 4RU
Refer to
Figure 3-4
for this procedure.
The tray platform sits in the bottom center of the rear
portion of the LTX panel. The platform contains routing
spools, tray banding, tie-down slots and splice trays.
The tray platform can be rotated out from inside the
LTX panel or can be removed for splicing.
1. Position the tray platform on the bottom of the LTX
panel in the rear portion of the tray. Center the
platform tray between the sidewalls. Screw holes
for the tray are near rear door hinges.
2. Align the two thumb screw holes in the platform
tray with the screw holes in the bottom of
the panel.
NOTE: It is recommended that routing spools,
splice tray bands and empty splice trays are
pre-installed before the tray platform is installed
in the panel.
3. Insert thumb screws through the top of the tray
platform into the screw holes in the panel bottom.
4. Rotate screws to tighten. Loosening one of the
screws allows the tray platform to rotate out from
inside the panel when needed.
Figure 3-4 4RU Tray Platform Installation
3.1.5 Cable Clamp Bracket Installation
The installation instructions apply to the LTX 4RU
Refer to
Figure 3-5
for this procedure.
Incoming cables route from above or below and enter the
LTX panel at one of the upper rear corners. The cable
clamp bracket is used to house the cable clamp which
secures the cable to the panel.
1. Position cable clamp bracket with the straight side
up and the angled side facing down on the outside
upper corner edge at the rear of the LTX Panel.
2. Align the two screw holes in the top portion of the
bracket with the screw holes at the top edge of the
rear overhang on the LTX panel.
3. Insert two Phillips screws through the bracket from
the outside into the panel edge screw holes
and tighten.
Upper Rear
Corner
Two
Screws
Figure 3-5 4RU Cable Clamp Bracket Installation
LTX Panel
Cable
Clamp
Bracket

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 16
The installation instructions apply to the
LTX 2RU & 1RU
Refer to
Figure 3-5-1 & Figure 3-5-2
for
this procedure.
Incoming cables route from above or
below and enter the LTX panel at one
of the upper rear corners. The cable
clamp bracket is used to house the
cable clamp which secures the cable to
the panel.
1. Position cable clamp bracket with
the straight side up and the angled
side facing down on the outside
upper corner edge at the rear of the
LTX Panel.
2. Align the two screw holes in the
top portion of the bracket with the
screw holes at the top edge of the
rear overhang on the LTX panel.
3. Insert two Phillips screws through
the bracket from the outside into
the panel edge screw holes
and tighten.
* Leave sufcient IFC slack to allow
drawer to open properly.
Figure 3-5-1 2RU Cable Clamp Bracket Installation
Figure 3-5-2 1RU Cable Clamp Bracket Installation
LTX Panel
Upper Rear
Corner
Cable
Clamp
Bracket
Screws
LTX Panel
Upper Rear
Corner
Screws
Cable Clamp
Bracket

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 17
3.1.6 Cable Clamp Installation
The installation instructions apply to the LTX 4RU
Refer to
Figure 3-6
for this procedure.
The cable clamp, consists of rubber clamp halves that contain
bushing leaves in the center. To snugly t around the cable,
bushing leaves can be removed from the center of the clamp
to accommodate various sizes of incoming cable. The rubber
circle should be removed from the outer rubber square before
starting installation.
Additionally, the clamp can be repositioned after mounting at
the LTX panel if needed.
1. Determine diameter of the incoming cable.
2. Measure the inside of the cable clamp and remove
enough bushing leaves so that the rubber cable clamp
halves and remaining bushing leaves will t snugly
around the cable.
3. Position cable clamp so that screw holes align in both
clamp halves and the cable clamp bracket.
4. Insert the two clamp screws to secure the clamp on
the cable clamp bracket. The bracket allows for some
adjustment of the clamp as needed.
5. Insert nuts to secure the screws in the bracket while
tightening the screws in the cable clamps. The clamp is
mounted at a slight angle when attached to the bracket.
Cable Clamp
Clamp
Bushing
Leaves Clamp
Halves
LTX Panel
Cable Clamp
(Attaches to bracket
with adjustable
screws)
Rear Corner
Figure 3-6 4RU Cable Clamp Installation
The installation instructions apply to the LTX 2RU & 1RU
Refer to Figure 3-6-1 & 3-6-2 for this procedure.
The cable clamp, consists of rubber clamp halves that contain
bushing leaves in the center. To snugly t around the cable,
bushing leaves can be removed from the center of the clamp
to accommodate various sizes of incoming cable. The rubber
circle should be removed from the outer rubber square before
starting installation.
Additionally, the clamp can be repositioned after mounting at
the LTX panel if needed.
1. Determine diameter of the incoming cable.
2. Measure the inside of the cable clamp and remove
enough bushing leaves so that the rubber cable clamp
halves and remaining bushing leaves will t snugly
around the cable.
3. Position cable clamp so that screw holes align in both
clamp halves and the cable clamp bracket.
4. Insert the two clamp screws to secure the clamp on
the cable clamp bracket. The bracket allows for some
adjustment of the clamp as needed.
5. Insert nuts to secure the screws in the bracket while
tightening the screws in the cable clamps. The clamp is
mounted at a slight angle when attached to the bracket.
Figure 3-6-1 2RU Cable Clamp Installation
Figure 3-6-2 1RU Cable Clamp Installation
LTX Panel
Rear Corner
Clamp
Halves
Cable Clamp
(Attaches to bracket
with adjustable
screws)
Clamp
Halves
Cable Clamp
(Attaches to bracket
with adjustable
screws)
LTX Panel
Rear Corner
Clamp
Bushing
Leaves
Clamp
Bushing
Leaves

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 18
3.1.7 Central Strength Member Holder Installation
The installation instructions apply to the LTX 4RU
Refer to
Figure 3-7
for this procedure.
The LTX patch and splice panel central strength
member holder is installed on the same side of the
rear panel sidewall as the cable clamp.
1. Determine position for central strength member
holder below the cable clamp and along the
sidewall of the LTX panel.
2. Align central strength member holder screw hole
with the screw hole in the LTX panel.
3. Insert screw into the holder and through the
sidewall from the inside of the LTX panel.
4. Position holder at desired position and tighten
screw with a Phillips screwdriver.
LTX Panel
Rear Sidewall
Central
Strength
Member
Screw
Cable Clamp
Cable Clamp Bracket
Figure 3-7 4RU Central Strength Member Holder Installation

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 19
3.1.8 Adapter Patch Plate Installation
The installation instructions apply to the LTX 4RU, 2RU
& 1RU
Refer to
Figure 3-8, Figure 3-8-1 & 3-8-2
for this procedure.
The adapter patch plate installs at the front of the LTX
patch and splice panel. The patch plate comes with
adapters pre-installed. Pigtail bers from the splice tray
will connect to connectors at the rear and ber jumpers
will connect to adapters at the front of the patch plate.
1. Position the patch plate at the front of the LTX
patch and splice panel with ber jumper adapters
facing toward the front of the LTX panel and pigtail
connectors facing the rear of the LTX panel.
2. On one side of the LTX panel, align top and bottom
screw holes with patch plate screw holes. (4RU)
3. From the outside of the LTX panel, insert screws and
hand tighten.
4. On the other side of the LTX panel, align top and
bottom screw holes with patch plate screw holes.
5. From the outside of the LTX panel, insert screws and
hand tighten.
6. Ensure patch plate is centered and there is a little
clearance around the plate and the panel.
7. Use a Phillips screwdriver to tighten all four
screws.
Adapter Patch Plate
(144 SC Terminations shown)
Screws Screws
Some clearance between Patch
Plate and LTX Panel
LTX 4RU Panel
Front View
Figure 3-8 4RU Adapter Patch Plate Installation
LTX 2RU Panel
Front View
Adapter Patch Plate
(48 Terminations Shown)
Some clearance between Patch
Plate and LTX Panel
Screws Screws
Figure 3-8-1 2RU Adapter Patch Plate Installation
Figure 3-8-2 1RU Adapter Patch Plate Installation
LTX 1RU Panel
Front View
Adapter Patch Plate
(48 Terminations Shown)
Some clearance between Patch
Plate and LTX Panel
Screws Screws
* Patch plates on the 2RU & 1RU are attached to
the tray, not on the chassis like the 4RU.

LTX Patch and Splice Panel
Installation Guide
© Telect, Inc. All rights reserved. 148326 12.20.16 v2
1.509.926.6000 :: telect.com 20
3.1.9 Panel Door Installation
The installation instructions apply to the LTX 4RU
& 2RU
Refer to
Figure 3-9, Figure 3-9-1 for this procedure.
Spring-hinged doors mount to the front and rear
bottom edges of the LTX panel.
1. On the LTX panel locate the two round mounting
pin holders along the front bottom edge.
2. Position the door at along the edge of the
panel bottom.
3. Press the door edge toward the panel bottom
edge while sliding the hinge pins out toward
the sides.
4. Slowly release the two hinge pins into the
mounting pin holders on the bottom edge of
the LTX panel so that they are inserted into
the slots.
5. Pull the door up to the closed position to ensure
that spring hinges operate correctly.
6. Repeat Steps 1-5 to install the other door.
Latch doors in the closed position by pressing
down on the center door latch (4RU) or door
latch tabs (2RU) while pushing the door in.
Release the latch or door tabs so that the tab
catches in the slot at the top of the LTX panel.
To open, press down on the door latch or door
tabs to release the latch or tabs and swing the
door down.
Door Latch Tab
Door
Door Hinge
Round Mounting Pin Holders
Door
Hinge
LTX 4RU Panel
Door Latch Slot
(on top of panel)
Bottom
(of panel)
Figure 3-9 4RU Door Installation
LTX 2RU Panel
Door Latch Tabs
Door Latch Slots
(on top of panel)
Round Mounting Pin
Holders
Door Hinge Door Hinge
Bottom
(of panel)
Figure 3-9-1 2RU Door Installation
Other manuals for LTX
1
Table of contents
Other Telect Control Panel manuals
Popular Control Panel manuals by other brands

CityGrow
CityGrow CG100HHB-SKY user manual

Siemens
Siemens FIREFINDER-XLS PMI Operation manual

Secutron
Secutron MR-2306-DDR Installation and operation manual

SCE&G
SCE&G EnergyWise troubleshooting guide

vds
vds EURO230M2 instruction manual

Johnson Controls
Johnson Controls FRICK QUANTUM LX/HD installation instructions