RNA ESK 2002 User manual

Operating Instructions
Controller
for Vibratory Drive Systems
ESK 2002

Rhein-Nadel Automation GmbH 2
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
Table of Contents
1. About this document ..............................................................................................................4
2. Safety directives.....................................................................................................................4
2.1. Design of safety directives..................................................................................................4
2.2. Fundamental safety directives ............................................................................................4
2.3. Personnel............................................................................................................................4
2.4. Intended use.......................................................................................................................5
2.5. Residual hazards................................................................................................................5
2.5.1. Device ..........................................................................................................................5
2.5.2. Protection of the drive system......................................................................................5
2.5.3. Degree of protection - Protection of persons and equipment .......................................5
3. Product information................................................................................................................6
3.1. Characteristic features........................................................................................................6
3.2. CE conformity .....................................................................................................................6
3.3. Technical data.....................................................................................................................7
3.4. Accessories ........................................................................................................................7
4. Note on start-up .....................................................................................................................8
4.1. Modes of operation.............................................................................................................8
4.2. Automatic mode change.....................................................................................................9
4.3. Sensor inputs and sensor linkages.....................................................................................9
4.4. Sensor connection............................................................................................................10
4.5. Status outputs and relays .................................................................................................11
5. Operation .............................................................................................................................12
5.1. General.............................................................................................................................12
5.2. Starting-up the controller...................................................................................................13
5.3. Main menu / Setpoint entry and display for channels 1, 2 and 3.......................................13
5.4. Description of individual codes for controller programming...............................................14
5.5. Application-specific changes to default settings................................................................15
5.5.1. Code C001 for channel 1, (feed rate output 1, bowl feeder).......................................15
5.5.2. Code C002 for channel 2, (feed rate output 2, vibratory or belt hopper) ....................15
5.5.3. Code C012 for channel 3, (feed rate output 3, vibratory or belt drive)........................16
5.5.4. Code C003 Seal setpoint ...........................................................................................16
5.5.5. Code C004 sensor input 1 and code C005 sensor input 2.........................................16
5.5.6. Code C006 Sensor linkage.........................................................................................17
5.5.7. Code C008 cycle monitoring ......................................................................................18
5.5.8. Code C009 Show status.............................................................................................19
5.5.9. Code C200 Inhibiting all code entries.........................................................................19
5.5.10. Code C143 Saving parameters...............................................................................20
5.5.11. Code C210 Retrieving parameters..........................................................................20
6. Dimensioned drawing...........................................................................................................21
7. Connection diagram.............................................................................................................22

Rhein-Nadel Automation GmbH 3
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
Declaration of Conformity
According to the Low-Voltage Directive 2014/35/EU
and Electromagnetic Compatibility Directive 2014/30/EU
We hereby declare that the product meets the following requirements:
Low-Voltage Directive 2014/35/EC
Electromagnetic Compatibility Directive 2014/30/EU
Applied harmonised standards: DIN EN 60204 T1
EN 61439-1
Note:
Rhein-Nadel-Automation
---------------------------------
Managing Director
Jack Grevenstein

Rhein-Nadel Automation GmbH 4
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
1. About this document
Document description:
This document provides assistance in choosing your product. You will also find information on mechanical and electri-
cal installation, operation, product extensions and accessories.
Non-observance may cause trouble with the product or the environment, reduce the product lifetime or lead to other
damage.
2. Safety directives
2.1. Design of safety directives
2.2. Fundamental safety directives
Non-observance of the following fundamental safety measures and directives may lead to severe injury and damage
to property!
Meeting the requirements given in the related documentation is a precondition for safe and trouble-free operation and
for achieving the product properties specified.
Further additional safety directives in the other sections must be observed as well.
2.3. Personnel
Only qualified professionals are allowed to work on or with the product. IEC 60364 or CENELEC HD 384 define the
qualification of these persons:
•They are familiar with set-up, installation, commissioning and operation of the product.
•They possess the qualification required for performance of their work.
•They know all regulations for the prevention of accidents, directives and laws applicable to set-up, installa-
tion and commissioning on site, and they are able to apply the same.
•They have knowledge and skills of First Aid.
Attention
Read this document carefully and observe the safety directives before commencing any work.
Notice
This notice identifies useful tips for use of the controller.
Attention!
This symbol identifies hazardous situations.
Non-observance of such warnings may cause irreversible injury or even death!
Attention!
Any work on electrical equipment of the machine/system shall be carried out exclusively by a professional
electrician, or by instructed persons working under the direction and supervision of a professional electri-
cian, according to electrotechnical rules.

Rhein-Nadel Automation GmbH 5
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
2.4. Intended use
Please observe the following directives for intended use of the controllers:
•The devices herein described must only be stored, fitted and operated under the conditions specified in
this documentation.
•Here you are not concerned with domestic devices! They are solely intended to be used as components
for commercial or professional applications pursuant to EN 61000−3−2.
•They satisfy the protection requirements of 2014/35/EU: Low Voltage Directive.
•They do not constitute a machine as defined by 2006/42/EU: Machinery Directive.
•A machine comprising the product must not be commissioned or put into operation for the intended use
until it has been declared to be in conformity with the EC Directive 2006/42/EU: Machinery Directive; Ob-
serve EN 60204−1.
•Commissioning or starting operation for the intended use is only permitted in compliance with the EMC
Directive 2014/30/EU.
•Use of the product in living areas may lead to EMC disturbance. The user is responsible for taking interfer-
ence suppression measures.
•They are optimised for operation of RNA bowl feeders and linear feeders. Observe the limits indicated in
the technical specification.
2.5. Residual hazards
Residual hazards may remain even if all directives have been observed and protective measures taken.
Such residual hazards must be considered by the user in the risk assessment of his machine/equipment.
Non-observance may lead to severe injury and damage to property!
2.5.1. Device
Pay attention to the warning signs fitted to the device!
Symbol
Description
Hazardous voltage:
Prior to commencing any work on the product check for absence of voltage on all power con-
nections!
Leakage current:
Make fixed installation and PE connection according to EN 60204−1!
2.5.2. Protection of the drive system
Certain device parameter settings may overheat the connected drive magnet, e.g., by prolonged operation with the
wrong voltage set.
2.5.3. Degree of protection - Protection of persons and equipment
•All specifications relate to installed condition ready for operation.
•All slots not used must be closed by protection caps or dummy plugs in order not to reduce the protection
against accidental contact.
Attention!
•Prior to start-up make sure that the protective earth conductor is connected and in proper condi-
tion. Make the PE conductor test with approved test devices only.
•Never start up despite detected damage.
•Do not make any technical modifications to the device, except as described in this document.
•Never start up in an incompletely installed state.
•Never operate the device without the required guards in place.
•Connect, disconnect or change any electrical connections only in the absence of voltage.

Rhein-Nadel Automation GmbH 6
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
3. Product information
3.1. Characteristic features
The compact controller is designed for operation of a combination of bowl feeder, linear feeder and hopper. Channel 1
is provided for connection of a vibratory feeder, channels 2 and 3 for connection of vibratory feeders or belt feeders.
You can also connect two sensors for accumulation and level monitoring, allowing you to operate a complete feeding
system using the controller. Of course, other combinations are possible as well, e.g. three independently controlled
linear feeders. Any belt feeders connected must be equipped with an AC capacitor motor.
Controller type ESK 2002-10 is rated for a total current of 10 A, and controller type ESK 2002-16 for a total current of
16 A. The unit offers the following characteristic features:
•Three power outputs:
oChannel 1 bowl feeder max. 10A, variable
oChannel 2 linear feeder max. 4A, variable
or AC capacitor motor max. 3A, not variable
oChannel 3 linear feeder max. 4A, variable
or AC capacitor motor max. 3A, not variable
•Two sensor amplifiers with independently adjustable timers (On/Off delay).
•External enabling inputs 24 VDC
•Two relay outputs and four optocouplers for status messages and other links.
•Membrane keypad for setting and changing the operating parameters in the set-up menus.
•Plug-type connections for
oBowl feeder
oLinear feeder
oHopper
oSensors
oCommunication with higher-level controller
•Bipolar main disconnect switch.
3.2. CE conformity
The controller is compliant with the following standards:
EC EMC Directive 2014/35/EU
EC Low-Voltage Directive 2014/30/EU
Applied harmonised standards:
DIN EN 60204, part 1
EN 61439-1

Rhein-Nadel Automation GmbH 7
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
3.3. Technical data
Technical data:
230 V AC, 50/60 Hz, +20 / -15%
115 V AC, 50/60 Hz, +10 / -10%
Supply voltage:
0 ... 208 Veff; (230V in motor mode) at 230V mains voltage
0 ... 98Veff; (115V in motor mode) at 115V mains voltage
Device type
ESK2002 - 10
ESK 2002 - 16
Channel 1 max. load current:
10 Aeff
10 Aeff
Channel 2 max. load current:
4 Aeff
4 Aeff
Channel 3 max. load current:
4 Aeff
4 Aeff
Total max. load current
10 Aeff
16 Aeff
Minimum load current:
80 mA
Internal fusing:
F1 = 10AmT / F2 = 4AmT / F3 = 4AmT
Soft start delay, soft stop delay for 3 channels:
0 ... 5 sec. separately selectable
Sensor inputs:
2
3 enabling inputs:
24V DC (10-24VDC)
Sensor supply:
24V DC, max. 60 mA (per sensor input)
Sensor ON delay:
0 ... 60 sec. separately adjustable
Sensor OFF delay::
0 ... 60 sec. separately adjustable
Outputs:
2 relays (max. 6A 250V AC)
2 floating changeover contacts
2 normally-open contacts carrying supply voltage
Status outputs:
2 optocouplers (max. 30V DC 10mA)
Ambient temperature:
0 ...45 ° C
Cooling:
free convection
Mounting:
vibration-free
Degree of protection:
IP 54
3.4. Accessories
ID
Designation
RNA mat. No
XS1, XS2, XS5
Load connector, 5-pin
31002322 (50HZ drive)
XS1, XS2, XS5
Load connector, 5-pin
31002323 (100Hz drive)
XS3
Male connector, 5-pole, straight
35051144
XS3
Male connector, 5-pole, right-angled
35002546
XS4
Female connector, 12-pole, straight
35051641
XS4
Female connector, 12-pole, right-angled
35051642
for X3
Y-adapter
39905940

Rhein-Nadel Automation GmbH 8
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
4. Note on start-up
Attention:
Make sure that following points are checked prior to making connection to power supply and switching on
the controller:
•Is the controller casing properly closed with all screws tightened?
•Are all plug hooks engaged / firmly screwed in place?
•Are all cables and glands in proper condition?
•Is operation for the INTENDED USE made sure?
•Does the supply voltage specified on the controller match the local supply system?
•Does the supply frequency specified on the vibratory drive match the local supply system?
•Is the correct mode set on the controller?
•(See description under "Modes of Operation")
•Is sufficient cooling of the controller ensured?
•Is the controller mounting vibration-free?
Only if you can clearly answer all the above questions with "Yes" should the controller be put into operation.
Attention:
Set the controller to minimum output before switching-on for commissioning or start-up after repairs or
replacement of controllers/vibratory drives. Then watch proper operation while the output is increased.
4.1. Modes of operation
RNA vibratory drive systems employ mechanical spring vibrators which are set to a vibrating frequency near the mains
frequency or near double mains frequency depending on weight and/or size.
This is why two modes of operation are possible:
Mode 1: Asymmetric half-wave mode:
The vibrating drive operates at mains frequency.
Mode 2: Symmetric full-wave mode:
The vibrating drive operates at double mains frequency.
To assist the operator the cable glands on the drive connector are colour-coded.
Mode 1: black
Mode 2: grey
In terms of the vibrating frequency this means:
Mains frequency 50 Hz
Mains frequency 60 Hz
Cable gland colour
Mode 1
Half-wave mode
Vibration frequency
50 Hz ≙3000 min-1
Vibration frequency
60 Hz ≙3600 min-1
black
Mode 2
Full-wave mode
Vibration frequency
100 Hz ≙6000 min-1
Vibration frequency
120 Hz ≙7200 min-1
grey

Rhein-Nadel Automation GmbH 9
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
4.2. Automatic mode change
Vibratory drive systems by RNA do not require the operator to take care of selecting the right operating mode.
The operating mode is determined by a code in the RNA vibrating drive connector.
A wire jumper from pin 3 to 4 in the connector switches the controller to mode 2: 100 or 120 Hz.
In the absence of this wire jumper the controller operates in mode 1: 50 or 60 Hz.
The RNA vibratory drive systems come with the right code in the connector.
Mode changes are made only and exclusively via the coding in the vibrating drive connector.
(Where frequency controllers with selectable output frequency are used, an EMC metal gland and a shielded cable are
provided.)
4.3. Sensor inputs and sensor linkages
The controller has two sensor inputs which are used for accumulation checking, level checking, cycle monitoring and
other monitoring functions. The following basic assignments are made:
Sensor input 1 acts on channel 1, unless otherwise programmed in menu C 006.
Sensor input 2 acts on channel 2. Sensor input 1 is reserved for accumulation check (if this function is required).
The sensor inputs can be evaluated only if they are activated. For sensor connection (connector XS3) please refer to
the connection diagram.
M20 gland
Black: 50/60Hz vibration frequency
Grey: 100/120Hz vibration frequency
(EMC metal gland if frequency controllers are used.)

Rhein-Nadel Automation GmbH 10
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
4.4. Sensor connection
The controller has two sensor inputs which can be used for accumulation checking and/or level monitoring purposes.
You can connect sensors of type NPN or PNP.
Proximity switch
general NPN
output
Proximity switch
general PNP
output
Sensor 2
Proximity switch
general NPN
output
Sensor 1
Proximity switch
general PNP
output
Contact
EGF40 (optical
sensor w/o
amplifier)
Connection of 2 sensors via Y adapter
PNP switching sensors may re-
quire a 10K resistor between sen-
sor output and 0V.
Floating contact
EGF40 (optical sen-
sor w/o amplifier)

Rhein-Nadel Automation GmbH 11
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
4.5. Status outputs and relays
The status outputs are used for remote diagnostics of the controller status or of the links of several controllers with one
another.
They are designed as freely available NPN-doped transistor circuits and they are floating.
With the status output READY the transistor circuit is switched through whenever the controller is connected to power
supply and switched on by its power switch closed.
The status output ACTIVE requires the same conditions for switching-through as "READY".
In addition, the channel must be energized, the transistor blocks in case of ACCUMULATION, OFF or STOP.
The status outputs as well as the external enabling inputs are to be wired via plug connector XS4.
The two relays have different functions.
K1 operates as a status relay parallel to the ACTIVE status output.
K2 serves either for a blowing air switch-off delay (4 sec.) or for cycle monitoring of one of the two sensor channels.
Connections and cable entry are on the right-hand side of the controller with the terminal block behind the panel.

Rhein-Nadel Automation GmbH 12
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
5. Operation
5.1. General
Controller plug connections
Main disconnect
switch
Double-pole isolation of the controller from power supply
XS 3
Connector for sensors
Channel 1 (XS1)
Connector for vibratory feeder (<10 A)
Channel 2 (XS2)
Connector for linear feeder or AC motor (<4 A)
Channel 3 (XS5)
Connector for linear feeder or AC motor (<4 A)
XS 4
Connector for optocoupler outputs and external enabling inputs
The controller display (membrane keypad)
On / Off
Pressing this button switches off all connected devices. The display shows "OFF".
The controller remains ready for operation.
UP cursor and DOWN cursor
Use these buttons to scroll through the controller menu or set the parameters.
Enter
Press this button to acknowledge the parameters entered with the cursor.
Decimal point in display
The decimal point is not blinking. You cannot make any entry.
The decimal point is blinking, an entry can be made.
Main disconnect
On/Off
Cursor UP
Cursor DOWN
Enter
XS3
Chnl 1
Chnl 2
Chnl 3
XS 4

Rhein-Nadel Automation GmbH 13
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
5.2. Starting-up the controller
To start up the controller, close the main disconnect switch. The main menu appears on the display showing the last
setpoint entered in channel 1 (feed rate of the bowl feeder).
KANAL l
KANAL 2
CODE
Alternatively, the following may appear on the display depending on the switching status of the device:
KANAL l
KANAL 2
CODE
External enabling signal has been activated but it is withdrawn from the device at the mo-
ment. (medium priority)
KANAL l
KANAL 2
CODE
Device has been switched off by operating the top left button of the membrane keypad, in-
hibiting all functions. (highest priority)
KANAL l
KANAL 2
CODE
The accumulation monitoring sensor is operated, switching off channel 1 (the vibratory
feeder). (low priority)
5.3. Main menu / Setpoint entry and display for channels 1, 2 and 3
Display of setpoint or feed rate of
channel 1 (bowl feeder)
Alternatively: STOP, OFF or ACCUMU-
LATION (see above)
No entry possible
Entry of the codes to change or exe-
cute the required settings.
Enter code.
Description of codes see
under 4.4
Setpoint entry for channel 1
(bowl feeder)
Entry in %;
return to display mode
for saving
Setpoint entry for channel 2
(Linear feeder or belt hopper
with AC motor)
(not available with belt feeder)
Entry in %; return to
display mode for sav-
ing
Setpoint entry for channel 3
(Linear feeder or belt hopper with AC
motor)
(not available with belt feeder)
Entry in %; return to
display mode for sav-
ing
Use the cursor buttons (UP/ DOWN) to scroll through these five basic screens of the main menu. In each individual
item of the main menu you can press ENTER to activate this item for setting or changing. Upon pressing of the EN-
TER button the decimal point starts blinking. Now you can make changes using the cursor buttons (UP/DOWN). Press
ENTER again to acknowledge the entries made. The decimal point is no longer blinking. Using the cursor buttons you
can continue scrolling in the menu. Same procedure analogously applies to the code menus described below.
All the following display screens show the default setting. If the actual display on the controller differs from what is
shown here, the default setting has been changed in individual codes to suit a specific application.
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
CODE
KANAL 2

Rhein-Nadel Automation GmbH 14
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
5.4. Description of individual codes for controller programming
Settings for channel 1
In this sub-menu you can set or limit the following functions for channel 1:
- Vibrating amplitude - Signal direction of external enabling input
- External enabling - Soft start and stop delay
Settings for channel 2
In this sub-menu you can set or limit the following functions for channel 2:
- Vibrating amplitude - Signal direction of external enabling input
- External enabling - Soft start and stop delay
- Selection of vibratory feeder or belt feeder
Settings for channel 3
In this sub-menu you can set or limit the following functions for channel 3:
- Vibrating amplitude - Signal direction of external enabling input
- External enabling - Soft start and stop delay
- Selection of vibratory feeder or belt feeder
Sealing a setpoint
In this sub-menu you can lock the setpoints (vibrating amplitude) of the main menu. It is no longer possible
to change the setpoints for channel 1, channel 2 and channel 3 in the main menu. This avoids accidental
changes to performance parameters. You can only make any changes now through codes C001, C002 and
C012.
Setting the sensor input 1
This is the sub-menu for activation of sensor input 1. In addition you can set the following functions:
- Invert input signal direction - Start delay
- Stop delay
Setting the sensor input 2
This is the sub-menu for activation of sensor input 2. In addition you can set the following functions:
- Invert input signal direction - Start delay
- Stop delay
Choosing the sensor links
In this sub-menu you can link the sensors activated by codes C004 and C005 with one another.
Setting the cycle watchdog
Here you can set which sensor input is to be monitored and how the controller is to react to an error.
Show status
This sub-menu serves for checking of the set vibrating frequency and of the sensor inputs.
Calling-up the software version
Definition: 411. 57. 10. 23.11.99
Date
Version No.
Device type
Internal No.
Device type:
59 = ESK 2001
58 = ESG 2001
57 = ESK 2000
56 = ESG 2000
Saving parameters
Open this sub-menu for saving the (application-specific) settings previously made in various sub-menus.
Inhibiting all setting functions
With the aid of this code you can disable all input facilities of the controller. It is no longer possible to
change any values. The only way now to enable the menu again is through this code.
Retrieving parameters
Inn this sub-menu you can return the controller to the default settings. You can also return to application-
specific settings, if previously saved.
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE

Rhein-Nadel Automation GmbH 15
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
5.5. Application-specific changes to default settings
5.5.1. Code C001 for channel 1, (feed rate output 1, bowl feeder)
Objective: Setting and limiting the vibration amplitude, external enabling, soft start delay and soft stop delay.
Select code
Set code
Code C001
Set vibrating amplitude
0 - 100% (*)
Limit vibrating amplitude
50 - 100 %
External enabling
I = active
0 = not active
External enabling signal direction
I = Start = 24V DC
0 = Stop = 24V DC
Soft start delay
0 - 5 sec.
Soft stop delay
0 - 5 sec.
Return
Save and return to
main menu
(*) For RNA feeders with 200 V magnets = 90 %
5.5.2. Code C002 for channel 2, (feed rate output 2, vibratory or belt hopper)
Objective: Setting and limiting the vibration amplitude, external enabling, soft start delay and soft stop delay, and the
vibratory or belt feeder function.
Select code
Set code
Code C002
Set vibrating amplitude
Only in controller mode
0 - 100 %
Limit vibrating amplitude
50 - 100%(*)
External enabling
I = active
0 = not active
Delayed stoppage
InP = 1 and InT = 11)
External enabling signal direction
I = Start = 24V DC
0 = Stop = 24V DC
Soft start delay
0 - 5 sec.
Soft stop delay
0 - 5 sec.
Switching to vibratory or belt feeder
0 = vibratory drive
1 = belt feeder
Return
Save and return to
main menu
(*) For RNA feeders with 200 V magnets = 90 %
1) After removal of the enabling signal channel 2 switches off with a delay (5 minutes).
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE

Rhein-Nadel Automation GmbH 16
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
5.5.3. Code C012 for channel 3, (feed rate output 3, vibratory or conveyor drive)
Objective: Setting and limiting the vibration amplitude, external enabling, soft start delay and soft stop delay, and the
vibratory or belt feeder function.
Select code
Set code
Code C002
Set vibrating amplitude
Only in controller mode
0 - 100 %
Limit vibrating amplitude
50 - 100 % (*)
External enabling
I = active
0 = not active
External enabling signal direction
I = Start = 24V DC
0 = Stop = 24V DC
Soft start delay
0 - 5 sec.
Soft stop delay
0 - 5 sec.
Switching to vibratory or belt feeder
0 = vibratory drive
1 = belt feeder
Return
Save and return to
main menu
(*) For RNA feeders with 200 V magnets = 90 %
5.5.4. Code C003 Seal setpoint
Objective: Sealing-in the setpoints in the main menu. A direct change of the values is no longer possible. You can
only make any changes now through code C001, code C002 and code C012.
Select code
Set code
Code C003
Setpoint (vibrating amplitude)
1 = adjustable
0 = input inhibited
Return
Save and return to
main menu
5.5.5. Code C004 sensor input 1 and code C005 sensor input 2
Objective: Activating and setting the sensor inputs
Select code
Set code
Code C004
Sensor 1 input
I = active
0 = not active
Invert input signal direction
I = Start = 24V DC
0 = Stop = 24V DC
Delay of sensor status
CLEAR, Start delay.
0 - 60 sec.
Delay of sensor status
OPERATED, Stop delay.
0 - 60 sec.
Return
Save and return to
main menu
Same applies analogously to code C005 (sensor input 2).
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE

Rhein-Nadel Automation GmbH 17
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
5.5.6. Code C006 Sensor linkage
Objective: Linking of the two previously activated sensor inputs
Select code
Set code
Code C006
You can activate only one of the eight sensor links at a time
AND logic with blowing-off
the exit tracks
I = active
0 = not active
AND logic with blowing-off
the exit tracks
I = active
0 = not active
OR logic
I = active
0 = not active
Min/Max logic
I = active
0 = not active
AND / S2 logic
I = active
0 = not active
Level check with external
controller
I = active
0 = not active
Level check indicator light
I = active
0 = not active
Individual link
I = active
0 = not active
Use the following link to set priority of the channels.
Channel 2 follows Channel 1
I = active
0 = not active (both chan-
nels operate independently)
Return
Save and return to
main menu
Brief description of individual links
AND logic of the sensor inputs with blowing-off the exit track.
Example:
Application:
Twin-track feeders with accumulation checker.
Solution:
Track 1 (sensor 1) full = Blow-off track 1 (relay K1)
Track 2 still clear
Track 2 (sensor 2) full = Blow-off track 2 (relay K2)
Track 1 still clear
Track 1 + Track 2 full = Bowl feeder (channel 1) Stop about 4 sec. later blowing air
stop
AND logic of the two sensor inputs without blowing-off the exit track.
The bowl feeder (channel 1) stops when both sensors are operated. Orienting air can be switched off
with delay (4 sec.) via relay K2.
AND / S2 logic
The bowl feeder (channel 1) stops when both sensors are operated. It starts when sensor 2 is cleared
again. Orienting air can be switched off with delay via relay K2.
OR logic of the two sensor inputs.
Bowl feeder (channel 1) stops when one of the two sensors is operated. Orienting air can be switched
off with delay (4 sec.) via relay K2.
Min/Max logic of the two sensor inputs.
The bowl feeder stops when both sensors are operated. The vibratory feeder (channel 1) will re-start
only after both sensors are cleared again.
Relay K1 operates on stopping of bowl feeder. Relay K2 operates 4 sec. later
(stopping the blowing air)
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE

Rhein-Nadel Automation GmbH 18
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
Level check for hopper control by external controller
Sensor 2 operates relay K1 following the delay period entered (C005). When sensor 1 is operated, re-
lay K1 drops out. (Hopper interlock)
Application:
Sensor 1 = accumulation check
Sensor 2 = level check
Relay K1 = hopper control
Level check with indicator light
Sensor 2 operates relay K1 following the delay period entered (C005) without taking into account sensor
1 (accumulation check).
Application:
Sensor 2 is used as a level checker (e.g., LC-N 24V DC). Relay K1 operates an indicator
light: Bowl feeder empty.
5.5.7. Code C008 cycle monitoring
Objective: Monitoring of sensors 1 (accumulation check) and/or 2.
When activating the cycle monitoring function, the "AND, SOL" links in code C006 must not be activated!!!
Select code
Set code
Code C008
Sensor input 1 is monitored
I = active
0 = not active
Sensor input 2 is monitored
I = active
0 = not active
Monitoring depending on
Channel 1
I = active
0 = not active
Monitoring depending on
Channel 2
I = active
0 = not active
Time till alarm comes up
3 - 240 sec.
Switching off channel 1 and channel 2
I = see below
0 = see below
Switch (relay K1)
I = Alarm on relay K1
0 = Alarm on relay K2
Return
Save and return to
main menu
The cycle watchdog monitors the CLEAR sensor status. The time (A 180) sets the maximum duration
for which a sensor is allowed to be clear before an alarm message is generated.
In case of an alarm the relay K2 is clocked on and off. Reset takes place automatically when the sensor
is operated again.
If OUT = 1 the alarm operates relay K2 (indicator light: Error) and also stops the bowl feeder. An ER-
ROR message appears on the panel display. Use the bottom right cursor button for reset.
If OUT = 0 the alarm only operates relay K2 (indicator light: Error). Reset takes place automatically
when sensor 1 is operated.
If A.I. = 1 relay K1 is clocked on and off in response to the alarm (switching from relay K2 to relay K1).
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE

Rhein-Nadel Automation GmbH 19
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
5.5.8. Code C009 Show status
Objective: Checking of the set vibrating frequency and of the sensor inputs.
Select code
Set code
Code C009
External enabling signal
Channel 1
I = active
0 = not active
Channel 1 vibrating frequency
I = 50 Hz
0 = 100 Hz
External enabling signal
Channel 2
I = active
0 = not active
Channel 2 vibrating frequency
I = 50 Hz
0 = 100 Hz
External enabling signal
Channel 3
I = active
0 = not active
Channel 3 vibrating frequency
I = 50 Hz
0 = 100 Hz
Signal at sensor input 1
I = active
0 = not active
Signal at sensor input 2
I = active
0 = not active
Return
Save and return to
main menu
Under menu item HA = half wave you can check whether the operating mode (100 - 50 Hz) is selected
correctly.
5.5.9. Code C200 Inhibiting all code entries
Objective: An (accidental) change of the set values by the user is not possible any more.
Select code
Set code
Code C200
Inhibiting the setting functions
I = enable
0 = disable
Return
Save and return to
main menu
Only code C200 is accepted!!!
You can still change the setpoints for channels 1, 2 and 3 in the main menu (see under 5.3).
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE

Rhein-Nadel Automation GmbH 20
VT-BA-ESK2002_EN-2020 / 06.05.2020 SJ
5.5.10. Code C143 Saving parameters
Objective: Saving of application-specific parameters.
Select code
Select code
Code C143
Save
Return
Save and return to
main menu
Having pressed ENTER to acknowledge PUSH you can save the selected parameters separately by
pressing a cursor button.
5.5.11. Code C210 Retrieving parameters
Objective: Resetting to default values or retrieving stored application-specific settings
Select code
Set code
Code C210
Default setting
Application-specific parameters
Return
Save and return to
main menu
FAC Select and acknowledge FAC to apply the factory default settings
US.PA. Select and acknowledge US.PA to retrieve the application-specific set of parameters previ-
ously saved under C143.
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
KANAL l
KANAL 2
CODE
Other manuals for ESK 2002
2
This manual suits for next models
2
Table of contents
Other RNA Controllers manuals
Popular Controllers manuals by other brands

Ltech
Ltech LT-3800-5A manual

Teledyne
Teledyne THCD-101 instruction manual

Nortek Security & Control
Nortek Security & Control GoControl WI15VZ-1 instructions

Xantrex
Xantrex LINK 2000-R owner's manual

Distech Controls
Distech Controls DA-008S230DX installation instructions

Johnson Controls
Johnson Controls Hitachi C4IRK01 Operation manual