FIRST DIGIT SECOND DIGIT THIRD DIGIT
CH1 POST PROCESSING
0 Direct Display of Input
(no processing)
1 Square Root of Channel 1
2 Inverse of Channel 1
3–
32-POINT LINEARIZATION FOR CHANNEL 1
0 No Linearization on CH1
1 32-point Linearization on CH1 using Table 1
2 32-point Linearization on CH1 using Table 2. See Note 5
3 32-point Linearization on CH1 using Table 3. See Note 5
4 32-point Linearization on CH1 using Table 4. See Note 5
5 125-point Linearization on CH1 (Tables 1 to 4 cascaded). See
Note 5
6 32-point Linearization on CH1 (Tables 1 to 4 selected from the
rear pins of selected input modules).
The selected table is not available if CH2, CH3, or CH4 is oper-
ating in the analog mode.CH1 must be set to Voltage, Current in
Code 2 [X0X]. See Note 5
7-
Note:
All linearization tables are set up in the Calibration Mode [24X].
SERIAL MODE
0 ASCII Mode
1 Modbus Mode
2 Master mode (used to cus-
tomize print mode protocols
via macro)
3 Print Mode
4 Ethernet Mode. See Note 6
5 Devicenet Mode (requires
Devicenet hardware module).
See Note 6
CODE 3 –CHANNEL 1 FUNCTIONS (POST PROCESSING & SERIAL MODE)
Note 6:
These functions are not available
on all models and in some cases
require additional hardware.
Code 4 –Linearization for Channel 2
To apply a standard thermocouple or RTD (pre-configured) linearization table to Channel 2,
select the required table from the 1st and 2nd digits in Code 4.
To apply a non-preconfigured linearization table to Channel 2, select the required table
from the 3rd digit in Code 4.
0 No user defined Linearization
on CH2
1 32-point Linearization on CH2
using Table 1
2 32-point Linearization on CH2
using Table 2. See Note 5
3 32-point Linearization on CH2
using Table 3. See Note 5
4 32-point Linearization on CH2
using Table 4. See Note 5
5 125-point Linearization on CH2
(Tables 1 to 4 cascaded). See
Note 5
6–
7–
MEASUREMENT TASK
0 Voltage, Current
1 TC (type as per 2nd digit)
2 RTD (type as per 2nd digit)
3 Second Digital Input Channel (type
as per 2nd digit)
FOR VOLTAGE & CURRENT
0 Channel 2 Disabled
1 Direct (no post processing)
2 Square Root of Channel 2
3 Inverse of Channel 2
32-POINT LINEARIZATION FOR CH2
CODE 4 –CHANNEL 2 MEASUREMENT TASK AND 32-POINT LINEARIZATION
FOR THERMOCOUPLE
0 Type J
1 Type K
2 Type R
3 Type S
4 Type T
5 Type B
6 Type N
7 Select user defined table set up in
CAL [24X]
FOR RTD TYPE (3-WIRE)
0 Resistance
1 RTD 385
2 RTD 392
3 RTD 120
4 Cn10
DIGITAL INPUT
0 Frequency - 99.999 Hz range from
0.01 Hz
1 Frequency - 999.99 Hz range from 0.01 Hz
2 Frequency - 99.999 kHz range from 1 Hz
(1 s gate)
3 Frequency - 500 kHz range from 10 Hz
(0.1 s gate)
4 Period - 9.9999 s (100 µs resolution)
5 Period - 999.99 ms (10 µs resolution)
6 Up/Down Counter with Prescaler
7 Set Prescaler
FIRST DIGIT SECOND DIGIT THIRD DIGIT
Use buttons to set
prescale values from 1 to
65535 counts
Note 5:
If only 4 kilobits of memory is
installed, only Table 1 is
available for:
• CH1 in Code 3, 2nd digit.
• CH2 in Code 4, 3rd digit.
• CH3 in Code 5, 1st digit.
• CH4 in Code 6, 1st digit.
• RESULT in Code 7, 2nd digit.
Note 5:
If only 4 kilobits of memory is
installed, only Table 1 is avail-
able for:
• CH1 in Code 3, 2nd digit.
• CH2 in Code 4, 3rd digit.
• CH3 in Code 5, 1st digit.
• CH4 in Code 6, 1st digit.
• RESULT in Code 7, 2nd digit.
Code 3 –Non-preconfigured Linearization for CH1
To apply a non-preconfigured linearization table to Channel 1, select the required table from the
2nd digit in Code 3.