en-us Installation requirements and clearances
8
3.4 Distance from cooking surface
¡Hood installation height above a cooktop, rangetop or
range can vary.
¡The installation height ranges from a minimum height of
30'' (762 mm) to a suggested maximum height of 40''
(1,016 mm). However, it is necessary to follow the
cooking appliance manufacturer’s installation
instructions for proper hood height.
NOTICE:
The hood could incur some damage from heat if a
Thermador Professional® Series range or rangetop is
operated with multiple burners at high settings under a
hood that is installed at minimum clearances while the
hood is turned off.
3.5 Unit weight
¡This vent hood is heavy. Adequate structure and
support must be provided in all types of installations.
¡When calculating the load for the housing support
system, be sure to consider the weight of the ventilation
unit.
Description Weight
HPIN42WS 105 lbs (47.6 kg)
HPIN54WS 122 lbs (55.3 kg)
NOTICE:
The supplied weights address only the ventilation unit and
blower. The installer must account for weight of any
materials of construction when calculating the total dead
weight load of installation, including but not limited to: wall,
tile, mortar, plaster, brick, finishes, partitions, and other
similarly incorporated architectural and structural items. It
is the responsibility of the owner and the installer to
determine if additional requirements and/or standards
apply to specific installations.
3.6 Support structure
¡Framing must be fastened together and to ceiling joists
to provide enough structural strength to support the
weight of the hood and internal blower, if applicable.
¡Wall framing should be made of 2"x 4" lumber at
minimum. Proper structural support is required to
accommodate the weight of the hood.
3.7 Venting
¡The hood requires the ducting to be vented to the
exterior of the building.
3.8 Electrical requirements
WARNING
This appliance must be properly grounded.
¡The appliance requires a 120VAC, 60Hz. 15A branch
circuit.
¡The VTN2FZ blower in conjunction with a PHxxGWS
requires a 20A circuit breaker.
¡The appliance should only be connected to a dedicated
circuit (with ground) that has been installed according to
relevant regulations.
¡When connected to a GFCI-protected supply,
Thermador Professional® Series hoods are suitable for
use in damp locations that are protected from outside
weather conditions and not subject to saturation with
water and other liquids, but can be subject to moderate
degrees of moisture, such as an outdoor covered patio
or lanai area. Refer to local codes, NEC/CEC, and/or
the Authority Having Jurisdiction (AHJ) for additional
information.
¡Check your local building codes for proper method of
installation. This appliance should be installed in
accordance with applicable local codes or, in the
absence of local codes, with the National Electrical
Code, NFPA 70 or the Canadian Electric Code, CSA
C22.1-02.
¡The 25ft. remote and in-line blower extension cable
accessory (EXTNCB25W) will only work for distances
up to 25ft. The accessory cable must be purchased
separately. DO NOT use more than one blower
extension cable per installation.
¡Electrical data:
Refer to the rating plate for product data, including the
model and serial number.
→
"Rating plate location", Page19