
Installation I 3-3
3
Installation
Preparing for Installation
The RQT Standard is easy to install, if you plan the location and prepare the area
properly.
WARNING: Improper installation, operation, or servicing may result in equipment
damage or personal injury.
This equipment should only be installed, adjusted, and serviced by qualied technical
personnel who are familiar with the construction, operation, and potential hazards of
this type of machine.
All wiring, disconnects, and fuses should be installed by qualied electrical technicians
in accordance with electrical codes in your region. Always maintain a safe ground. Do
not operate the equipment at power levels other than what is specied on the machine
serial tag and data plate.
1 Position the RQT Standard as close to the process machine as possible.
2 Make sure the installation area provides:
UA three-phase power source supplying the correct cur-
rent for your RQT Standard model. Check the serial tag
on the unit for required voltage, phase, frequency, and full
load amps. Check the electrical prints for the disconnect
fuse size and minimum wire connection size. All wiring
should be completed by qualied personnel and should
comply with your region’s electrical codes.
UCompressed, dry air (<100psi) if your RQT Standard is equipped with the Mold
Purge option.
UA clean, well-ventilated environment. The room temperature should not exceed
104° F {40° C} with 95% non-condensing humidity and should not fall below
32° F {0° C}.
UMinimum clearance for safe operation and maintenance. The diagram at
the right shows minimum clearance for operation. You also need enough
clearance in rear for water hookups. For maintenance, you should move
the RQT Standard to provide at least 36 inches {91 cm} on any side of the
RQT Standard. Additionally, your required electrical codes may require a larger
service area in front of the electrical panel.
UA source of water for cooling. City, tower or chiller water may be used, as long
as the supply pressure is at least 25 psi and not more than 90 psi for 2 HP models
(95 psi for 3/4 HP models).
UCheck to make sure all piping connections are secure and that all lines are
suitable for water or the coolant in the system at the maximum setpoint tem-
perature and cumulative pressure rating of the maximum pump pressure and the
cooling water supply pressure, or the nameplate rating of the pressure relief valve
(150psi), whichever is greater.
UA location to mount an external three-phased, fused, and grounded electrical
disconnect.
ULockable isolation devices for all utilities, including electrical disconnect, cool-
ing water line valves, and compressed air supply disconnect and bleed-o.
RQT
Process
Machine
Alternate
locations
LowProcess
STOPPED
Setpoint
200°F
InletPres
To
Process
198°F
RUN MP
12 inches
{305 mm}
12 inches
{305 mm}
20 inches
{508 mm}
Pump HP Max Cooling
(PSI)
3/4 95
1 90
2 90
3 85
5 75
7.5 65
10 50
NOTE: If your cooling water
pressure exceeds the cooling water
pressure chart referenced previously,
install a pressure-regulating valve
before the cooling inlet.